What is a First Order Control System?

09/15/2024


What is a First Order Control System?


First Order Control System Definition


A first order control system uses a simple type of differential equation to relate inputs and outputs, focusing on the first derivative of time only.

 

4616c6a0ccfd0246e468d25c1b64388c.jpeg

 

The transfer function (input-output relationship) for this control system is defined as:

 

9660c72a9648773ea0a57b33d2f729eb.jpeg

 

  • K is the DC Gain (DC gain of the system ratio between the input signal and the steady-state value of output)


  • T is the time constant of the system (the time constant is a measure of how quickly a first-order system responds to a unit step input).


First Order Control System Transfer Function


A transfer function represents the relationship between the output signal of a control system and the input signal, for all possible input values.


Poles of a Transfer Function


The poles of the transfer function are the value of Laplace Transform variable(s), which cause the transfer function to become infinite.The denominator of a transfer function is actually the poles of function.


Zeros of a Transfer Function


The zeros of the transfer function are the values of the Laplace Transform variable(s), that causes the transfer function becomes zero.The nominator of a transfer function is actually the zeros of the function.


First Order Control System


Here we discuss the first-order control system without zeros. The first-order control system tells us the speed of the response that what duration it reaches the steady-state.If the input is a unit step, R(s) = 1/s so the output is a step response C(s). The general equation of 1st order control system is , i.e is the transfer function.

 

026b61ba6d622e5653f1e5c94cc2e207.jpeg

 

There are two poles, one is the input pole at the origin s = 0 and the other is the system pole at s = -a, this pole is at the negative axis of the pole plot.Using MATLAB’s pzmap command, we can identify the poles and zeros of the system, crucial for analyzing its behavior.We now taking the inverse transform so total response become which is the sum of forced response and natural response.

 

7b44e6d264096673d40e3476b96b49a9.jpeg


Due to the input pole at the origin, produces the forced response as name describe by itself that giving forced to the system so it produces some response which is forced response and the system pole at -a produces a natural response which is due to the transient response of the system.


After some calculation, here General form of the first-order system is C(s) = 1-e-at that is equal to forced response which is “1” and natural response which is equal to “e-at”. The only thing which is needed to find is the parameter “a”.


Many techniques like a differential equation or inverse Laplace Transform, these all solve the total response but these are time-consuming and laborious.


The use of poles, zeros, and there some fundamental concept gives us the qualitative information to solve the problems and due to these concepts, we can easily tell the speed of response and the time of a system to reach the steady-state point.


Let us describe the three transient response performance specifications, the time constant, rise time, and settling time for a first-order control system.


Time Constant of a First Order Control System


The time constant can be defined as the time it takes for the step response to rise up to 63% or 0.63 of its final value. We refer to this as t = 1/a. If we take reciprocal of time constant, its unit is 1/seconds or frequency.


We call the parameter “a” the exponential frequency. Because the derivative of e-at is -a at t = 0. So the time constant is considered as a transient response specification for a first-order control system.


We can control the speed of response by setting the poles. Because the farther the pole from the imaginary axis, the faster the transient response is. So, we can set poles farther from the imaginary axis to speed up the whole process.


Rise Time of a First Order Control System


The rise time is defined as the time for the waveform to go from 0.1 to 0.9 or 10% to 90% of its final value. For the equation of rising time, we put 0.1 and 0.9 in the general first-order system equation respectively.


For t = 0.1

 

For t = 0.9

 


Taking the difference between 0.9 and 0.1


Here the equation of rising time. If we know the parameter of a, we can easily find the rise time of any given system by putting “a” in the equation.

 

8125b82726fa75671aac319f71c62846.jpeg


Settling Time of a First Order Control System


The settling time is defined as the time for the response to reach and stay within 2% of its final value. We can limit the percentage up to 5% of its final value. Both percentages are a consideration.

 

The equation of settling time is given by Ts = 4/a.


 

By using these three transient response specifications, we can easily compute the step response of a given system that’s why this qualitative technique is useful for order systems equations.

 


Conclusion of First Order Control Systems


After learning all things related to 1st order control system, we come to the following conclusions:

 


  • A pole of the input function generates the form of the forced response. It is because of the pole at the origin which generates a step function at the output.



  • A pole of the transfer function generates a natural response. It the pole of the system.



  • A pole on the real axis generates an exponential frequency of the form e-at. Thus, the farther the pole to the origin, the faster the exponential transient response will decay to zero.



  • Understanding poles and zeros allows us to enhance system performance and achieve faster, more accurate outputs. 

 


The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being
07/31/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!