Description
Calculate how much current flows during a short circuit at transformer output. Get three-phase, single-phase & peak fault currents (kA) per IEC 60865 for breaker, fuse, and cable sizing.
Calculate the maximum symmetrical short-circuit current at the output of an MV/LV transformer substation. Input network and transformer data to obtain three-phase, single-phase, and peak fault currents—essential for protective device selection and equipment safety verification.
Why Use This Tool?
- Determine if your breakers, fuses, and cables can safely interrupt fault currents
- Prevent equipment damage, fires, or arc flash incidents due to underrated components
- Meet utility interconnection requirements and regulatory safety standards
- Perform quick preliminary studies without complex power system software
How It Works
The calculator uses the upstream network strength, transformer impedance, and MV/LV line parameters to compute total impedance at the fault point. Based on IEC 60865 and IEEE C37.100, it then derives:
- Three-phase short-circuit current (Isc, kA)
- Single-phase short-circuit current (Isc1, kA)
- Peak short-circuit current (Ip, kA)
- Equivalent impedance (Zeq, Ω)
- Short-circuit power (Ssc, MVA)
Understanding Your Inputs
- Power Net Fault (MVA): Short-circuit capacity of the upstream grid (provided by utility).
- Voltage Fault (%): Transformer short-circuit impedance (Uk%), found on nameplate.
- Joule Effect Losses (%): Load losses (Pc) as % of rated kVA; used to estimate resistance.
- Line Type & Size: Affects conductor resistance and reactance (choose overhead, unipolar, or multipolar).
- Conductor Material: Copper has lower resistivity than aluminum—impacts total impedance.
Example Calculation
Scenario: 500 kVA transformer, Uk% = 5%, fed by 80 m copper unipolar cable (95 mm²), secondary voltage = 400 V.
- Fault at MV cable end: 33.47 kA
- Fault at transformer secondary: 19.395 kA
- Fault at LV cable end (20 m): 9.794 kA
These values guide breaker selection (e.g., minimum 25 kA interrupting rating at secondary).
What Do the Results Mean?
- Isc (kA): RMS symmetrical fault current — used for thermal withstand checks (e.g., busbars, cables).
- Ip (kA): Peak current (≈ 2.5 × Isc) — determines electrodynamic forces on equipment.
- Zeq (Ω): Total impedance at fault location — useful for coordination and sensitivity studies.
- Ssc (MVA): Short-circuit power — often required in utility interconnection applications.
Typical Applications
- Protective Device Coordination – Verify interrupting ratings of breakers and fuses
- Equipment Specification – Ensure switchgear complies with IEC 61439 withstand requirements
- Substation Retrofit Projects – Assess fault levels when upgrading transformers
- Arc Flash Studies – Provide input data for IEEE 1584 hazard analysis
- Utility Interconnection – Submit fault current data for new customer connections
Who Should Use This Tool?
This calculator is designed for professionals responsible for electrical system safety and reliability:
- Electrical Design Engineers
- Power System Analysts
- Facility & Plant Managers
- Consulting Engineering Firms
- Utility Distribution Engineers
Compliance & Standards
All calculations align with internationally recognized standards:
- IEC 60865-1: Short-circuit currents – Calculation of effects
- IEEE C37.100: Guide for AC high-voltage circuit breakers
- IEC 61439: Low-voltage switchgear assemblies
- IEEE 1584: Arc flash hazard calculations
Results are suitable for use in technical reports, safety assessments, and utility submissions.
Frequently Asked Questions
How much current will a short circuit have?
It depends on source strength, transformer impedance, and line resistance. Use our calculator to determine exact values for your system.
What does short circuit current mean?
Short-circuit current (SCC) is the maximum current that flows during a fault. It's critical for selecting protective devices like breakers and fuses.
Is higher SCC better?
No. Higher SCC increases stress on equipment and requires more robust protection. The goal is to limit it through proper design and impedance.
What is the 125% rule for breakers?
Breakers must be rated for at least 125% of continuous load current, but also need sufficient short-circuit interrupting rating (e.g., 25 kA), which this tool helps verify.
Does a short circuit mean no current?
No. A short circuit means very low resistance, causing extremely high current flow—often tens of thousands of amperes.