Calculate three-phase short-circuit current (Iₖ₃F) for electrical engineers per IEC 60909 at MV line, transformer, and LV line ends using grid MVA, uₖ%, and cable data.
The tool computes short-circuit current using the IEC 60909 method:
Note: c = 1.1(voltage factor per IEC 60909). Transformer impedance is derived solely from Voltage fault (%uk).
| Parameter | Description | Typical Regional Values |
|---|---|---|
| Power net fault | Grid short-circuit capacity in MVA — defines upstream source strength | Europe: 500 – 5,000 MVA North America: 1,000 – 3,000 MVA Oceania: 800 – 4,000 MVA Industrial sites: Often <500 MVA |
| Primary voltage | Transformer primary voltage in kV (e.g., 20 kV) | Europe: 10 kV, 20 kV, 30 kV North America: 12.47 kV, 13.2 kV, 24.9 kV, 34.5 kV Oceania: 11 kV, 22 kV Standardized per national grid codes |
| Secondary voltage | Transformer secondary rated voltage in V (e.g., 220 V, 400 V) | Europe / Oceania: 230/400 V (±10%) North America: 120/208 V, 277/480 V, 347/600 V Industrial LV: Often 400 V or 480 V globally |
| Transformer power | Rated apparent power in kVA | Commercial buildings: 100 – 1,000 kVA Industrial plants: 500 – 5,000 kVA Common standard sizes: 100, 160, 250, 400, 630, 1000 kVA |
| Voltage fault (%uk) | Transformer short-circuit impedance percentage — critical for accuracy | Dry-type (≤1 MVA): 4% – 6% Oil-immersed (≥1 MVA): 5% – 8% High-impedance units: Up to 10% Region-independent (depends on design) |
| Joule effect losses | Transformer copper losses as % of rated power (typically 1%–2%). Used only for internal verification, not in fault calculation. | Dry-type: ~1.0% – 1.8% Oil-immersed: ~0.8% – 1.5% Efficiency class (e.g., IE3) affects value Not used in IEC 60909 fault calc |
| Medium voltage line length | Length of MV cable or overhead line in meters | Urban substations: 100 – 1,000 m Rural feeders: 1,000 – 10,000 m Industrial plants: Often <500 m |
| Line type | Overhead or underground — affects unit reactance | Europe: Predominantly underground in cities North America: Overhead common in suburbs/rural Oceania: Mix; underground in new developments |
| Medium voltage wire size | Conductor gauge in AWG | Note: AWG mainly used in North America Europe/Oceania: mm² (e.g., 95 mm² ≈ 3/0 AWG) Typical MV: 1/0 AWG to 500 kcmil (50–250 mm²) |
| Medium voltage conductors in parallel | Number of parallel runs (reduces total impedance) | Usually 1 (single run) High-current feeds: 2–4 parallel cables Rarely >4 due to current imbalance |
| Conductor | Material (Copper/Aluminum) — impacts resistivity | Copper: Common in Europe, industrial apps Aluminum: Widely used in North America (cost) Resistivity ratio: Al ≈ 1.6× Cu |
| Low voltage line length | Length of LV cable in meters | Building distribution: 10 – 100 m Feeder to motor: Often <50 m Long runs (>100 m) require voltage drop check |
| Low voltage wire size | AWG size of LV conductors | North America: #12 AWG (20 A), #10 AWG (30 A), #2 AWG (100 A) Europe/Oceania: 2.5 mm², 6 mm², 16 mm², etc. Small sizes increase LV fault impedance significantly |
| Low voltage conductors in parallel | Number of parallel LV conductors | Typically 1 Large feeders (>200 A): May use 2 in parallel Requires proper derating and balancing |
Example result for a 400 kVA transformer with 4% uk, 100 m MV/LV lines (1 AWG Cu):
Key Insight: Short-circuit current decreases significantly along the distribution path due to cable impedance — especially critical in LV circuits with small conductor sizes.
Q:What is substation short-circuit current?
A substation short-circuit current refers to the maximum prospective fault current that can flow through a substation under short circuit conditions. It is crucial for determining the ratings of switchgear, cables, and other electrical equipment.
Q:How do you calculate short-circuit current at a substation?
The calculation involves determining the total impedance from the power source to the point of fault, including contributions from the grid, transformers, and cables. The formula used is Ik3F = (c × U2n) / (√3 × ZTK), where c is the voltage factor, U2n is the nominal secondary voltage, and ZTK is the total impedance.
Q:Why is it important to know the short-circuit current at substations?
Knowing the short-circuit current helps in selecting appropriate protective devices and ensuring that the installed equipment can withstand potential fault currents without damage. This ensures safety and reliability of the power system.
Q:Is Joule effect losses considered in short-circuit current calculations?
No, Joule effect losses are not used in short-circuit current calculations. These losses represent energy dissipation due to resistance and are more relevant to efficiency studies rather than fault analysis.
Q:Can this tool be used for both MV and LV systems?
Yes, this tool supports calculations for both medium-voltage (MV) and low-voltage (LV) systems. It allows users to analyze faults at different points in the distribution network, including the end of MV lines, transformer secondaries, and LV line ends.