Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations

Encyclopedia
Field: Encyclopedia
0
China

In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.

According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity and the threat they pose to safe operation: critical, serious, and general.

1. Critical Defects

Critical defects refer to those with severe nature and urgent conditions that directly threaten safe operation. Emergency measures should be taken immediately, and resources organized to eliminate them. Critical defects include:

a) Electronic transformer (including acquisition unit) failure;

b) Merging unit failure;

c) Intelligent terminal failure;

d) Process layer network switch failure;

e) Protection device failure or abnormal withdrawal;

f) Abnormal pilot protection channel with inability to send/receive data;

g) SV, GOOSE disconnection and abnormal status changes in input quantities that may cause incorrect protection operation;

h) Control circuit disconnection or DC power loss in control circuit;

i) Other situations directly threatening safe operation.

2. Serious Defects

Serious defects refer to those with severe conditions showing deterioration trends that affect correct protection operation, posing threats to power grid and equipment safety, and potentially causing accidents. For serious defects, the corresponding protection may be requested to be withdrawn when specialized maintenance personnel arrive on site. During the period before defect handling, on-site operators should strengthen monitoring and take timely measures when protection misoperation risks exist. Serious defects include:

a) Increased attenuation in pilot protection channels exceeding 3dB; significantly abnormal frame loss in pilot protection channels;

b) Protection device only issuing abnormal or alarm signals without blocking protection;

c) Fault recorder or process layer network analyzer device failure or power loss;

d) Indicator lights on operating box not illuminated but without control circuit disconnection signal;

e) Incomplete or missing accident reports after protection device operation;

f) Normal local signals but abnormal background or central signals;

g) Communication interruption of protection information in unattended stations;

h) Abnormal auxiliary contact inputs of busbar protection isolating switches, but not affecting correct operation of busbar protection;

i) Communication anomalies between substation and main station of relay protection fault information system, between substation and protection devices, between substation and integrated monitoring system, as well as self-check anomalies of the substation;

j) Defects that occur frequently but can automatically recover;

k) Other situations that may affect correct protection operation.

3. General Defects

General defects refer to those other than critical and serious defects, with ordinary nature, relatively minor conditions, allowing protection to continue operating with minimal impact on safe operation. General defects include:

a) Inaccurate time or uncalibratable clock in protection devices;

b) Poor contact of buttons on protection panels;

c) Abnormal liquid crystal display on protection devices;

d) Communication interruption of protection information in attended stations;

e) Occasional defects that can automatically recover;

f) Other defects with minimal impact on safe operation.

Give a tip and encourage the author!

Recommended

Analysis of Lightning Protection Measures for Distribution Transformers
Analysis of Lightning Protection Measures for Distribution TransformersTo prevent lightning surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable lightning protection measures that can effectively enhance their lightning withstand capability.1. Lightning Protection Measures for Distribution Transformers1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.According to SDJ7–79 Technical Code for Overvol
12/24/2025
Transformer Protection Settings: Zero-Sequence & Overvoltage Guide
1. Zero-Sequence Overcurrent ProtectionThe operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.2.Overvoltage ProtectionOvervoltage protection is a critical com
12/17/2025
Electrical Protection: Grounding Transformers and Bus Charging
1. High-Resistance Grounding SystemHigh-resistance grounding can limit ground fault current and appropriately reduce ground overvoltage. However, there is no need to connect a large high-value resistor directly between the generator neutral point and ground. Instead, a small resistor can be used together with a grounding transformer. The primary winding of the grounding transformer is connected between the neutral point and ground, while the secondary winding is connected to a small resistor. Ac
12/17/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)