What is Long Transmission Line?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is Long Transmission Line?

Definition of Long Transmission Line

A long transmission line is defined as a transmission line longer than 250 km (150 miles), which needs a different modeling approach.

608826d6bbd922e09ba1119f2645705c.jpeg

A long transmission line is defined as a transmission line with a length greater than 250 km (150 miles). Unlike short transmission lines and medium transmission lines, long transmission lines need detailed modeling of their distributed parameters along the entire length. This makes calculating the ABCD parameters of transmission line more complex but allows us to find the voltage and current at any point on the line.

In a long transmission line the line constants are uniformly distributed over the entire length of line. This is because the effective circuit length is much higher than what it was for the former models (long and medium line) and hence we can no longer make the following approximations:

Ignoring the shunt admittance of the network, like in a small transmission line model.Considering the circuit impedance and admittance to be lumped and concentrated at a point as was the case for the medium line model.

Instead, we must consider the circuit impedance and admittance as distributed over the entire length. This makes the calculations more rigorous. For accurate modeling of these parameters, we use the circuit diagram of the long transmission line.

bc92416d4e3f867f27265ab70c48edd6.jpeg

 


Here a line of length l > 250km is supplied with a sending end voltage and current of VS and IS respectively, whereas the VR and IR are the values of voltage and current obtained from the receiving end. Lets us now consider an element of infinitely small length Δx at a distance x from the receiving end as shown in the figure where.

V = value of voltage just before entering the element Δx.

I = value of current just before entering the element Δx.

V+ΔV = voltage leaving the element Δx.

I+ΔI = current leaving the element Δx.

ΔV = voltage drop across element Δx.

zΔx = series impedance of element Δx

yΔx = shunt admittance of element Δx

Where, Z = z l and Y = y l are the values of total impedance and admittance of the long transmission line.

Therefore, the voltage drop across the infinitely small element Δx is given by

Now to determine the current ΔI, we apply KCL to node A.

Since the term ΔV yΔx is the product of 2 infinitely small values, we can ignore it for the sake of easier calculation.

Therefore, we can write

a4a00349758d819ce18b2ae7e64a8730.jpeg

Now derivating both sides of eq (1) w.r.t x,

Now substituting from equation (2)

The solution of the above second order differential equation is given by.

Derivating equation (4) w.r.to x.

Now comparing equation (1) with equation (5)

8a5521aba7918f13bc1dc8932b3aba95.jpeg


 

Now to go further let us define the characteristic impedance Zc and propagation constant δ of a long transmission line as

Then the voltage and current equation can be expressed in terms of characteristic impedance and propagation constant at

Now at x=0, V= VR and I= Ir. Substituting these conditions to equation (7) and (8) respectively.

98a203d221e03efcab8c7f886415a8af.jpeg

Solving equation (9) and (10),We get values of A1 and A2 as,


c594a1ba76f79bb1a6bcba021804de86.jpeg

Now applying another extreme condition at x = l, we have V = VS and I = IS.Now to determine VS and IS we substitute x by l and put the values of A1 andA2 in equation (7) and (8) we get

81cc39b0a1f4e8660328fe12c3592a79.jpeg

By trigonometric and exponential operators we know

Therefore, equation (11) and (12) can be re-written as

Thus compared with the general circuit parameters equation, we get the ABCD parameters of a long transmission line as,

a044409c56548215ef1aa86d05c25753.jpeg


Give a tip and encourage the author!
Recommended
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025
How Does Power Dispatching Ensure Grid Stability and Efficiency?
How Does Power Dispatching Ensure Grid Stability and Efficiency?
Electric Power Dispatching in Modern Power SystemsThe power system is a critical infrastructure of modern society, providing essential electrical energy for industrial, commercial, and residential use. As the core of power system operation and management, electric power dispatching aims to meet electricity demand while ensuring grid stability and economic efficiency.1. Basic Principles of Electric Power DispatchingThe fundamental principle of power dispatching is to balance supply and demand by
Echo
10/30/2025
How to Improve Harmonic Detection Accuracy in Power Systems?
How to Improve Harmonic Detection Accuracy in Power Systems?
The Role of Harmonic Detection in Ensuring Power System Stability1. Importance of Harmonic DetectionHarmonic detection is a critical method for assessing the level of harmonic pollution in power systems, identifying harmonic sources, and predicting the potential impact of harmonics on the grid and connected equipment. With the widespread use of power electronics and the increasing number of nonlinear loads, harmonic pollution in power grids has become increasingly severe. Harmonics not only disr
Oliver Watts
10/30/2025
Load Bank Applications in Power System Testing
Load Bank Applications in Power System Testing
Load Banks in Power System Testing: Applications and AdvantagesThe power system is a core infrastructure of modern society, and its stability and reliability directly affect the normal operation of industry, commerce, and daily life. To ensure efficient operation under various operating conditions, load banks—critical testing equipment—are widely used in power system testing and validation. This article explores the application scenarios and unique advantages of load banks in power system testin
Echo
10/30/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.