Flux Linkage Equation

Edwiin
Field: Power switch
China

The Constant Flux Linkage Principle in Alternator Transients

The constant flux linkage concept is fundamental to analyzing alternator transients. It states: In a closed circuit with zero resistance and capacitance, flux linkages remain unchanged following a sudden disturbance, preserving their pre-disturbance values.

In alternators, armature and field windings exhibit negligible capacitance, and their resistances are insignificant compared to inductances. Thus, these windings can be treated as purely inductive. Consequently, any abrupt change in current within one winding must be offset by a corresponding current adjustment in the other winding to maintain constant flux linkages—an essential mechanism for transient stability.

Proof of the Constant Flux Linkage Theorem

Mesh voltage equations for electrical circuits can be generally expressed as:

Using the symbol Ψ for the flux linkage (Nϕ), the equations may be written as follows:

Where e1 denotes the resultant voltage, a function of time t.Integrating equation (2) yields the change in flux linkage from an arbitrary initial time, expressed as:

Where Δt represents a small time interval. As Δt approaches zero, the integral term vanishes, leading to ∑Ψ=0.Thus, the instantaneous change in flux linkage is zero.

Give a tip and encourage the author!

Recommended

Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Understanding Transformer Neutral Grounding
I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
01/29/2026
Voltage Imbalance: Ground Fault, Open Line, or Resonance?
Single-phase grounding, line break (open-phase), and resonance can all cause three-phase voltage unbalance. Correctly distinguishing among them is essential for rapid troubleshooting.Single-Phase GroundingAlthough single-phase grounding causes three-phase voltage unbalance, the line-to-line voltage magnitude remains unchanged. It can be classified into two types: metallic grounding and non-metallic grounding. Inmetallic grounding, the faulted phase voltage drops to zero, while the other two phas
11/08/2025
Composition and Working Principle of Photovoltaic Power Generation Systems
Composition and Working Principle of Photovoltaic (PV) Power Generation SystemsA photovoltaic (PV) power generation system is primarily composed of PV modules, a controller, an inverter, batteries, and other accessories (batteries are not required for grid-connected systems). Based on whether it relies on the public power grid, PV systems are divided into off-grid and grid-connected types. Off-grid systems operate independently without relying on the utility grid. They are equipped with energy-s