Inductance in Transmission Line

Electrical4u
Field: Basic Electrical
0
China

What Is Inductance In Transmission Line

Reason of Transmission Line Inductance

Generally, electric power is transmitted through the transmission line with AC high voltage and current. High valued alternating current while flowing through the conductor sets up magnetic flux of high strength with alternating nature. This high valued alternating magnetic flux makes a linkage with other adjacent conductors parallel to the main conductor. Flux linkage in a conductor happens internally and externally. Internally flux linkage is due to self-current and externally flux linkage due to external flux. Now the term inductance is closely related to the flux linkage, denoted by λ. Suppose a coil with N number of turn is linked by flux Φ due to current I, then,

But for transmission line N = 1. We have to calculate only the value of flux Φ, and hence, we can get the transmission line inductance.

Calculation of Inductance of Single Conductor

Calculation of Internal Inductance due to Internal Magnetic Flux of a Conductor

Suppose a conductor is carrying current I through its length l, x is the internal variable radius of the conductor and r is the original radius of the conductor. Now the cross-sectional area with respect to radius x is πx2 square – unit and current Ix is flowing through this cross-sectional area. So the value of Ix can be expressed in term of original conductor current I and cross-sectional area πr2 square – unit

inductance of single conductor

Now consider small thickness dx with the 1m length of the conductor, where Hx is the magnetizing force due to current Ix around the area πx2.

And magnetic flux density Bx = μHx, where μ is the permeability of this conductor. Again, µ = µ0µr. If it is considered that the relative permeability of this conductor µr = 1, then µ = µ0. Hence, here Bx = μ0 Hx.

dφ for small strip dx is expressed by

Here entire cross-sectional area of the conductor does not enclose the above expressed flux. The ratio of the cross sectional area inside the circle of radius x to the total cross section of the conductor can be thought about as fractional turn that links the flux. Therefore the flux linkage is

Now, the total flux linkage for the conductor of 1m length with radius r is given by

Hence, the internal inductance is

External Inductance due to External Magnetic Flux of a Conductor

Let us assume, due to skin effect conductor current I is concentrated near the surface of the conductor. Consider, the distance y is taken from the center of the conductor making the external radius of the conductor.
external inductance due to external magnetic flux of a conductor
Hy is the magnetizing force and By is the magnetic field density at y distance per unit length of the conductor.

Let us assume magnetic flux dφ is present within the thickness dy from D1 to D2 for 1 m length of the conductor as per the figure.

As the total current I is assumed to flow in the surface of the conductor, so the flux linkage dλ is equal to dφ.

But we have to consider the flux linkage from conductor surface to any external distance, i.e. r to D



Inductance of Two Wire Single Phase Transmission Line

Suppose conductor A of radius rA carries a current of IA in opposite direction of current IB through the conductor B of radius rB. Conductor A is at a distance D from conductor B and both are of length l. They are in close vicinity with each other so that flux linkage takes place in both of the conductors due to their electromagnetic effects.
two wire single phase

Let us consider the magnitude of current in both conductors are same and hence IA = – IB,
Now, total flux linkage in conductor A = flux linkage by self-current of conductor A + flux linkage on conductor A due to current in the conductor B.
Similarly, flux linkage in conductor B = flux linkage by self-current of conductor B + flux linkage on conductor B due to current through conductor A.
flux of two wire single phase
Now if we consider a point P in close vicinity both conductor A and B, the flux linkage at point P would be, flux linkage at point P for current carrying conductor A + flux linkage at point P for current carrying conductor B i.e.

Now,……… shown in the figure below in figure (a) and (b).

  • λAAP is the flux linkage at point P for conductor A due to current through conductor A itself.

  • λABP is the flux linkage at point P for conductor A due to current through conductor B.

  • λBAP is the flux linkage at point P for conductor B due to current through conductor A.

  • λBBP is the flux linkage at point P for conductor B due to current through conductor B itself.



λABP and λBAP are negative in value because the directions current are opposite with respect to each other.

If we consider that both conductor are with same radius, i.e. rA = rB = r and point P is shifted to infinite distance then we can write that


If conductor A becomes bundled conductor, then its geometrical mean radius (GMR) will be calculated for n number of conductors per bundle.

Where, d is the distance between the central axis of conductors within the bundle.

Inductance in Three Phase Transmission Line

In the three phase transmission line, three conductors are parallel to each other. The direction of the current is same through each of the conductors.

Let us consider conductor A produces magnetic flux φA,
Conductor B produces magnetic flux φB,
And conductor C produces magnetic flux φC.
When they carry the current of the same magnitude “I”, they are in flux linkage with each other.
three phase transmission line
Now, let us consider a point P near three conductors. So, flux linkage at point P due to current through conductor A is,

Flux linkage at point P for conductor A due to current through conductor A =

Flux linkage at point P for conductor A due to current through conductor B =
Flux linkage at point P for conductor A due to current through conductor C =
Therefore, flux linkage at point P for conductor A,

As,andin balanced system, then we can write that




If we arrange them in matrix form, then we get

Where, λA, λB, λC are the total flux linkages of conductor A, B and C.
LAA, LBB and LCC are the
self inductances of conductor A, B and C.
LAB, LAC, LBC, LBA, LCA, LCB are the
mutual inductances of between conductors A, B and C.

Again balanced system

And

In balanced system, then we can write that


Similarly,

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.