Common Faults and Troubleshooting for ABB VD4 Vacuum Circuit Breakers!

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Does Your Plant Use ABB VD4 Breakers?Despite the VD4's proven reliability in global markets, no equipment is immune to faults with prolonged use. Below, we’ve compiled common VD4 faults and their solutions—hopefully this helps you in daily maintenance!

Fault 1: Energy Storage Mechanism Failure

Symptom:
Motor cannot store energy, but manual storage works.

Possible Causes & Solutions:

1. Power Not Connected

Check if power is reaching the terminal block in the switchgear and confirm that the control power switch 2ZK in the storage circuit is in the closed position.

2. Faulty Energy Storage Limit Switch (S1)

The S1 limit switch in the VD4-12 controls motor start/stop and signal circuits. Two normally closed (NC) contacts in series control the motor: when the spring is fully charged, S1 actuates mechanically, opening the NC contacts and cutting power to the motor. When the spring is released or uncharged, the NC contacts close to allow recharging.

  • Unplug the aviation connector and measure the resistance between pins 25# and 35#.

  • If abnormal, check NC contacts 31–32 and 41–42. Burnt contacts indicate S1 failure—replace the S1 switch.

  • After replacement, adjust the S1 drive rod gap to 2.5–2.8 mm after full charging.

3. Worn Motor Brushes

Severe brush wear prevents normal motor operation. Replace the carbon brushes.

4. Burnt Storage Motor (MO)

If the control circuit is intact but resistance is abnormal, the motor may be burnt.

  • Disconnect wiring, remove the three mounting bolts, and replace the motor.

Fault 2: Breaker Fails to Close

Symptoms:

  • Electrical close fails; closing solenoid (trip coil) does not actuate.

  • Electrical close fails due to weak solenoid action, but manual close succeeds.

  • Electrical and manual closing both fail.

For Symptom 1 (Solenoid Not Actuating):

1. Drawer Unit Not Fully Seated
If the withdrawable unit is not fully racked in, two limit switches in the chassis won’t close the interlock coil circuit, preventing closing.

  • Check the position indicator on the switchgear.

  • Ensure the unit is correctly positioned in either "Service" or "Test" position.

2. Faulty Closing Interlock Solenoid (Y1) or Microswitch (S2)
A faulty Y1 solenoid or improperly actuated S2 microswitch can interrupt the closing circuit.

  • Measure Y1 coil resistance. If abnormal (shorted or open), replace the Y1 module.

  • If resistance is normal, check S2 actuation. Use needle-nose pliers to gently bend the S2 spring contact outward by 1–2 mm. Manually operate the Y1 plunger and listen for a click from S2.

3. Faulty Auxiliary Switch (S3) or Aviation Plug Pin Dropout
Open contacts in S3 or loose pins in the aviation connector will interrupt the closing circuit.

  • In the open position, if S3’s NC contact fails to close, adjust the S3 drive rod gap.

  • If pins are damaged or loose, replace the aviation connector.

For Symptom 2 (Weak Solenoid, Manual Close Works):
Likely due to low closing voltage or faulty closing coil rectifier bridge.

  • Check power supply voltage.

  • Test output of the rectifier bridge; replace the closing coil module if faulty.

For Symptom 3 (Both Electrical and Manual Close Fail):
Usually caused by the mechanical interlock plate in the spring mechanism being stuck or not resetting after racking in, preventing the closing pawl from releasing.

  • Inspect the interlock plate carefully.

  • If deformed, replace the entire actuator module.

⚠️ Prolonged energizing of the closing coil in this state may cause coil burnout.

Fault 3: Breaker Fails to Trip (Trip Rejection)

This is a critical emergency fault.

Symptoms:

  • Electrical trip fails; trip solenoid (Y2) does not actuate.

  • Electrical trip fails due to weak solenoid action, but manual trip succeeds.

For Symptom ① (Solenoid Not Actuating):

1. Faulty Trip Solenoid (Y2)

Measure the resistance of Y2 coil. If abnormal, replace the trip coil.

2. Poor Contact in Auxiliary Switch (S4)

After closing, S4’s normally open (NO) contact must close to complete the trip circuit. After tripping, it must open quickly to prevent prolonged coil energization. Frequent operation can damage S4 contacts.

  • For minor damage, adjust the S4 drive rod gap.

  • For severe damage, replace the S4 auxiliary switch.

3. Loose Wiring or Aviation Plug Pin Dropout

Loose connections or broken pins in the secondary control circuit will prevent tripping.

  • Inspect and tighten loose wires.

  • Replace the aviation connector if pins are damaged or missing.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.