• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


HV Breaker Fault Basics: Training Guide for New Engineers

Felix Spark
Felix Spark
Field: Failure and maintenance
China

High-Voltage Circuit Breakers: Classification and Fault Diagnosis

High-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.

I. Classification of High-Voltage Circuit Breakers

1. By Installation Location:

  • Indoor-type: Installed in enclosed switchgear rooms.

  • Outdoor-type: Designed for external installation, with weather-resistant enclosures.

2. By Arc-Quenching Medium:

  • Oil Circuit Breaker
    Uses insulating oil as the arc-quenching medium.

    • Bulk Oil Circuit Breaker (Multi-oil): Oil serves both as arc-extinguishing medium and insulation between live parts and grounded enclosure.

    • Minimum Oil Circuit Breaker (Less-oil): Oil is used only for arc extinction and contact insulation; external insulation (e.g., porcelain) insulates live parts from ground.

  • Vacuum Circuit Breaker:Extinguishes arcs in a high-vacuum environment, leveraging vacuum’s high dielectric strength. Widely used in medium-voltage applications due to long life and low maintenance.

  • Sulfur Hexafluoride (SF₆) Circuit Breaker:Uses SF₆ gas—known for excellent arc-quenching and insulating properties—as the interrupting medium. Dominant in high-voltage transmission systems for reliability and compact design.

  • Compressed Air Circuit Breaker:Employs compressed air to extinguish the arc and provide post-interruption insulation. Less common today due to complexity and maintenance needs.

  • Magnetic Blow-Out Circuit Breaker:Uses electromagnetic force to drive the arc into narrow slits where it cools and deionizes. Typically used in DC or specialized AC applications.

II. Common Faults and Troubleshooting of High-Voltage Circuit Breakers

1. Failure to Close (Refusal to Close)

This may stem from mechanical issues, control circuit faults, or operational errors. Check both electrical control circuits and mechanical components.

Electrical faults include:

(1) Indicator light not working or abnormal

  • Check if control power voltage matches rated value.

    • If red light does not illuminate when switch is in "close" position, likely causes: open closing circuit or blown fuse.

    • If green light (trip position) turns off but red light (close position) fails to illuminate, check red lamp integrity.

    • If green light extinguishes and relights: possible low voltage or mechanical failure in operating mechanism.

    • If red light flashes briefly then goes out and green light flashes: breaker momentarily closed but failed to latch—likely mechanical fault or excessively high control voltage causing impact failure.

(2) Closing contactor does not operate

  • If green light is off: check control bus fuses (positive/negative).

  • If green light is on: use test pen or multimeter to inspect control switch, anti-pumping relay, auxiliary contacts, and check for coil open circuit or secondary wiring break.

(3) Closing contactor operates but breaker does not move

  • Possible causes: poor contactor contact, arc chute jamming, open closing coil, or blown AC fuse in closing rectifier.

(4) Closing contactor operates, breaker moves but fails to close fully
Possible reasons:

  • Mechanical failure in operating mechanism

  • Low DC bus voltage

  • Secondary wiring mix-up accidentally energizing trip circuit

  • Improper operation (e.g., operator releasing control switch too early)

2. Failure to Trip (Refusal to Trip)

More dangerous than failure to close, as it can lead to upstream breaker tripping (cascade tripping), expanding outage scope.

(1) Causes of failed electric trip

  • Red light not lit: indicates open trip circuit.

    • Check: lamp integrity, fuse, control switch contacts, breaker auxiliary contacts.

    • Check: anti-pumping relay coil, trip circuit continuity.

  • Trip coil operates weakly: may be due to high coil pickup voltage, low operating voltage, stuck trip plunger, or coil fault.

  • Trip plunger moves but breaker does not trip: likely mechanical jamming or detached drive linkage pin.

(2) Handling refusal to trip

  • Manual trip fails: Immediately report to dispatch.

    • If bypass switch available: transfer load to bypass, open bus-side disconnectors of faulty breaker, then trip bypass breaker to de-energize the circuit.

  • Upstream breaker trips due to cascade fault:

    • With power off, open disconnectors on both sides of the faulty breaker.

    • Manually open all feeders on the affected bus.

    • Report to dispatch for system restoration.

3. Unintended Opening or Closing (False Operation)

(1) Unintended Tripping (False Trip)
Occurs when breaker trips without protection activation or operator action. Possible causes:

  • Two-point DC grounding in control circuit—check and eliminate ground fault before reclosing.

  • Faulty interlock mechanism—isolate breaker (open source-side disconnector) and test close once.

  • If evidence suggests internal fault despite no relay activation, investigate accordingly.

(2) Unintended Closing (False Close)
A de-energized breaker closes without command. Causes:

  • Two-point DC grounding energizing closing circuit.

  • Stuck auto-reclose relay contact.

  • Low pickup voltage + high coil resistance, causing false closure during DC transient pulses.

4. Overheating of Circuit Breaker

Main symptoms: overheated tank (especially in minimum-oil breakers), heated frame.

  • Cause: Poor contact or oxidation in conductive parts.

  • Risks: Insulation damage, cracked porcelain, smoking, oil spraying, or even explosion.

  • Action: Strengthen patrols, detect early, and address promptly.

5. Other Common Faults

(1) Oil Circuit Breaker Fire
Fire may result from dirty or damp bushings causing ground flashover, or internal arcing.

  • If fire just started: Immediately remotely trip the breaker.

  • If fire is severe: Use upstream breaker to isolate the circuit, then open disconnectors on both sides to fully isolate the unit. Extinguish with dry-type fire extinguisher (e.g., CO₂ or powder).

(2) Trip/Close Coil Smoking
Trip/close coils are designed for short-time duty. Prolonged energizing causes overheating and burnout.

  • Action: Immediately report to dispatch and request replacement.

  • If closing fuse blows during operation, replace only with specified rating—never use oversized fuse to prevent coil damage.

(3) Emergency Manual Trip Required
Immediately take oil circuit breaker out of service if any of the following occur:

  • Severe porcelain insulator cracking, flashover, or explosion

  • Melting or disconnection of conducting parts

  • Loud internal arcing sounds

  • Severe oil deficiency

Summary

This guide provides a comprehensive overview of high-voltage circuit breaker types, common operational faults, and corrective actions. Proper classification, regular inspection, and prompt troubleshooting are essential for ensuring system reliability, personnel safety, and equipment longevity.

Give a tip and encourage the author!
Recommended
Hazard Points in Transformer Operation and Their Prevention Measures
Hazard Points in Transformer Operation and Their Prevention Measures
The main hazard points in transformer operation are: Switching overvoltages that may occur during the energizing or de-energizing of no-load transformers, endangering transformer insulation; No-load voltage rise in transformers, which may damage transformer insulation.1. Preventive Measures Against Switching Overvoltages During No-Load Transformer SwitchingGrounding the transformer neutral point is primarily aimed at preventing switching overvoltages. In 110 kV and higher large-current grounding
Felix Spark
12/04/2025
126(145)kV Vacuum Circuit Breaker Installation & Adjustment Guide
126(145)kV Vacuum Circuit Breaker Installation & Adjustment Guide
High-voltage vacuum circuit breakers, owing to their excellent arc-quenching characteristics, suitability for frequent operation, and long maintenance-free intervals, have been widely applied in China’s power industry—particularly in urban and rural power grid upgrades, as well as in chemical, metallurgical, railway electrification, and mining sectors—and have received widespread acclaim from users.The primary advantage of vacuum circuit breakers lies in the vacuum interrupter. However, the char
James
11/20/2025
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
The 145 kV disconnector is a critical switching device in substation electrical systems. It is used in conjunction with high-voltage circuit breakers and plays an important role in power grid operation:First, it isolates the power source, separating equipment under maintenance from the power system to ensure personnel and equipment safety;Second, it enables switching operations to change the system operating mode;Third, it is used to interrupt small-current circuits and bypass (loop) currents.Re
Felix Spark
11/20/2025
Revolutionary 550 kV Capacitor-Free Arc-Quenching Circuit Breaker Debuts in China
Revolutionary 550 kV Capacitor-Free Arc-Quenching Circuit Breaker Debuts in China
Recently, a Chinese high-voltage circuit breaker manufacturer, in collaboration with numerous renowned enterprises, successfully developed a 550 kV capacitor-free arc-quenching chamber circuit breaker, which has passed the full suite of type tests on its first attempt. This achievement marks a revolutionary breakthrough in the interrupting performance of circuit breakers at the 550 kV voltage level, effectively resolving the long-standing “bottleneck” issue caused by reliance on imported capacit
Baker
11/17/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.