High-Voltage Circuit Breakers: Classification and Fault Diagnosis

Ang mga high-voltage circuit breakers mao ang mga kritikal nga protective devices sa mga power systems. Sila nag-intererrupt sa current ngadto sa pag-occur og fault, nang maprevent ang pag-damage sa equipment gikan sa overloads o short circuits. Sa wala pa, tungod sa long-term operation ug uban pang factors, ang mga circuit breakers mahimong mag-develop og faults nga angay nga i-diagnose ug troubleshoot niadtong maayo nga panahon.

I. Classification of High-Voltage Circuit Breakers

1. By Installation Location:

  • Indoor-type: Installed in enclosed switchgear rooms.

  • Outdoor-type: Designed for external installation, with weather-resistant enclosures.

2. By Arc-Quenching Medium:

  • Oil Circuit Breaker
    Uses insulating oil as the arc-quenching medium.

    • Bulk Oil Circuit Breaker (Multi-oil): Oil serves both as arc-extinguishing medium and insulation between live parts and grounded enclosure.

    • Minimum Oil Circuit Breaker (Less-oil): Oil is used only for arc extinction and contact insulation; external insulation (e.g., porcelain) insulates live parts from ground.

  • Vacuum Circuit Breaker:Extinguishes arcs in a high-vacuum environment, leveraging vacuum’s high dielectric strength. Widely used in medium-voltage applications due to long life and low maintenance.

  • Sulfur Hexafluoride (SF₆) Circuit Breaker:Uses SF₆ gas—known for excellent arc-quenching and insulating properties—as the interrupting medium. Dominant in high-voltage transmission systems for reliability and compact design.

  • Compressed Air Circuit Breaker:Employs compressed air to extinguish the arc and provide post-interruption insulation. Less common today due to complexity and maintenance needs.

  • Magnetic Blow-Out Circuit Breaker:Uses electromagnetic force to drive the arc into narrow slits where it cools and deionizes. Typically used in DC or specialized AC applications.

II. Common Faults and Troubleshooting of High-Voltage Circuit Breakers

1. Failure to Close (Refusal to Close)

Kini mahimong gikan sa mechanical issues, control circuit faults, o operational errors. Check both electrical control circuits and mechanical components.

Electrical faults include:

(1) Indicator light not working or abnormal

  • Check if control power voltage matches rated value.

    • If red light does not illuminate when switch is in "close" position, likely causes: open closing circuit or blown fuse.

    • If green light (trip position) turns off but red light (close position) fails to illuminate, check red lamp integrity.

    • If green light extinguishes and relights: possible low voltage or mechanical failure in operating mechanism.

    • If red light flashes briefly then goes out and green light flashes: breaker momentarily closed but failed to latch—likely mechanical fault or excessively high control voltage causing impact failure.

(2) Closing contactor does not operate

  • If green light is off: check control bus fuses (positive/negative).

  • If green light is on: use test pen or multimeter to inspect control switch, anti-pumping relay, auxiliary contacts, and check for coil open circuit or secondary wiring break.

(3) Closing contactor operates but breaker does not move

  • Possible causes: poor contactor contact, arc chute jamming, open closing coil, or blown AC fuse in closing rectifier.

(4) Closing contactor operates, breaker moves but fails to close fully
Possible reasons:

  • Mechanical failure in operating mechanism

  • Low DC bus voltage

  • Secondary wiring mix-up accidentally energizing trip circuit

  • Improper operation (e.g., operator releasing control switch too early)

2. Failure to Trip (Refusal to Trip)

Mas dangerous kay sa failure to close, tungod sa mahimong makapuyo sa upstream breaker tripping (cascade tripping), expanding outage scope.

(1) Causes of failed electric trip

  • Red light not lit: indicates open trip circuit.

    • Check: lamp integrity, fuse, control switch contacts, breaker auxiliary contacts.

    • Check: anti-pumping relay coil, trip circuit continuity.

  • Trip coil operates weakly: may be due to high coil pickup voltage, low operating voltage, stuck trip plunger, or coil fault.

  • Trip plunger moves but breaker does not trip: likely mechanical jamming or detached drive linkage pin.

(2) Handling refusal to trip

  • Manual trip fails: Immediately report to dispatch.

    • If bypass switch available: transfer load to bypass, open bus-side disconnectors of faulty breaker, then trip bypass breaker to de-energize the circuit.

  • Upstream breaker trips due to cascade fault:

    • With power off, open disconnectors on both sides of the faulty breaker.

    • Manually open all feeders on the affected bus.

    • Report to dispatch for system restoration.

3. Unintended Opening or Closing (False Operation)

(1) Unintended Tripping (False Trip)
Occurs when breaker trips without protection activation or operator action. Possible causes:

  • Two-point DC grounding in control circuit—check and eliminate ground fault before reclosing.

  • Faulty interlock mechanism—isolate breaker (open source-side disconnector) and test close once.

  • If evidence suggests internal fault despite no relay activation, investigate accordingly.

(2) Unintended Closing (False Close)
A de-energized breaker closes without command. Causes:

  • Two-point DC grounding energizing closing circuit.

  • Stuck auto-reclose relay contact.

  • Low pickup voltage + high coil resistance, causing false closure during DC transient pulses.

4. Overheating of Circuit Breaker

Main symptoms: overheated tank (especially in minimum-oil breakers), heated frame.

  • Cause: Poor contact or oxidation in conductive parts.

  • Risks: Insulation damage, cracked porcelain, smoking, oil spraying, or even explosion.

  • Action: Strengthen patrols, detect early, and address promptly.

5. Other Common Faults

(1) Oil Circuit Breaker Fire
Fire may result from dirty or damp bushings causing ground flashover, or internal arcing.

  • If fire just started: Immediately remotely trip the breaker.

  • If fire is severe: Use upstream breaker to isolate the circuit, then open disconnectors on both sides to fully isolate the unit. Extinguish with dry-type fire extinguisher (e.g., CO₂ or powder).

(2) Trip/Close Coil Smoking
Trip/close coils are designed for short-time duty. Prolonged energizing causes overheating and burnout.

  • Action: Immediately report to dispatch and request replacement.

  • If closing fuse blows during operation, replace only with specified rating—never use oversized fuse to prevent coil damage.

(3) Emergency Manual Trip Required
Immediately take oil circuit breaker out of service if any of the following occur:

  • Severe porcelain insulator cracking, flashover, or explosion

  • Melting or disconnection of conducting parts

  • Loud internal arcing sounds

  • Severe oil deficiency

Summary

This guide provides a comprehensive overview of high-voltage circuit breaker types, common operational faults, and corrective actions. Proper classification, regular inspection, and prompt troubleshooting are essential for ensuring system reliability, personnel safety, and equipment longevity.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Mga Punto sa Panganib sa Operasyon sa Transformer ug Ilahang Mga Sukad nga Pamaagi
Mga Punto sa Panganib sa Operasyon sa Transformer ug Ilahang Mga Sukad nga Pamaagi
Ang mga pangunahon nga panganib sa operasyon sa transformer mao kini: Ang switching overvoltages nga mahimong makita samtang ang no-load transformers nag-energizing o de-energizing, nga nagsulob sa insulation sa transformer; Ang pagtaas sa no-load voltage sa mga transformer, nga mahimong masira ang insulation sa transformer.1. Mga Preventive Measures Labi sa Switching Overvoltages Sa No-Load Transformer SwitchingAng grounding sa neutral point sa transformer primarihon gipangandoy aron maprevent
Felix Spark
12/04/2025
126 (145) kV Vacuum Circuit Breaker Installation & Adjustment Guide

Pamantayan sa Pag-install ug Pagsulay sa 126 (145) kV Vacuum Circuit Breaker
126 (145) kV Vacuum Circuit Breaker Installation & Adjustment Guide Pamantayan sa Pag-install ug Pagsulay sa 126 (145) kV Vacuum Circuit Breaker
Ang mga high-voltage vacuum circuit breakers, tungod sa ilang excellent na mga katangian sa pagpuno sa arc, kahimtang para sa regular nga pag-operate, ug long maintenance-free intervals, gipagtubag sila sa China’s power industry—espesyalmente sa urban ug rural power grid upgrades, ug sa chemical, metallurgical, railway electrification, ug mining sectors—ug nakuha sila og widespread acclaim gikan sa mga users.Ang primary advantage sa vacuum circuit breakers nahimutang sa vacuum interrupter. Apan,
James
11/20/2025
Common nga mga Isyu ug Pag-atas sa 145kV Disconnector Control Circuits
Common nga mga Isyu ug Pag-atas sa 145kV Disconnector Control Circuits
Ang 145 kV disconnector usa ka importante nga switching device sa mga sistema sa elektrisidad sa substation. Gigamit kini kasama sa mga high-voltage circuit breakers ug naglakip og importante nga papel sa operasyon sa power grid:Una, iya nang isolar ang pinaghunahon, paghiwalay sa mga equipment nga gigamiton sa maintenance gikan sa sistema sa power aron siguraduhon ang seguridad sa mga personal ug equipment;Pangaduha, iya nang pagpahimutang sa mga operasyon para bag-ohan ang modo sa operasyon sa
Felix Spark
11/20/2025
Revolutionary nga 550 kV Capacitor-Free Arc-Quenching Circuit Breaker Debuts sa China
Revolutionary nga 550 kV Capacitor-Free Arc-Quenching Circuit Breaker Debuts sa China
Lahat kini, usa ka Chinese nga manugbenta og high-voltage circuit breaker, sama sa daghang nailhan nga mga kompanya, makayabong nga gi-develop ang 550 kV capacitor-free arc-quenching chamber circuit breaker, nga naka-pass sa tanang tipo sa mga test sa unang pag-ensayo. Kini nga abilidad nagmarka og revolutionary breakthrough sa interrupting performance sa mga circuit breaker sa 550 kV voltage level, nga efektibong nagsolusyon sa long-standing “bottleneck” issue gikan sa pagpuyo sa imported capac
Baker
11/17/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo