• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Cineáltaí Briseadh Ciorcail Ardion & Treoir Fadhbanna

Felix Spark
Felix Spark
Réimse: Meathú agus Bainneanas
China

High-Voltage Circuit Breakers: Classification and Fault Diagnosis

Is mótarúilte iad briseoirí circe high-voltage sa chóras fuinnimh. Téann siad ar scor go tapa nuair a tharla deifir, ag cosaint ar tháirgeadh ó lódanna breise nó córais shorcha. Mar gheall ar oibriú fada éigríochta agus cúrsaí eile, d'fhéadfadh briseoirí circe fós a bheith faoi dhéanamh a bhfuil riachtanas orthu a diagnóis agus a dhiúltú.

I. Raghaidh Briseoirí Circe High-Voltage

1. De réir Suíomh Iastail:

  • Indoor-type: Iastal i seomraí comhbhrabhsála dúnta.

  • Outdoor-type: Dírithe do iastail amach, le boscaí éigeantacha.

2. De réir Meán Scora Airc:

  • Oil Circuit Breaker
    Úsáideann sé olion insüláideach mar mhéan scora airc.

    • Bulk Oil Circuit Breaker (Multi-oil): Seirbhíonn an olion mar mhéan scora airc agus insüláide idir na cuid beatha agus an bosca talún.

    • Minimum Oil Circuit Breaker (Less-oil): Úsáidtear an olion amháin do scora airc agus insüláide contáct; insüláide amach (mar shampla, porseáin) insüláide na cuid beatha ón talún.

  • Vacuum Circuit Breaker:Scorann airc in aerchúscáil airde, ag úsáid láidreacht dielectric an aerchúscáil. Forbríonn sé go forleathan i ngniomhaíochtaí meán-voltage mar gheall ar shaol fhada agus coimeád íseal.

  • Sulfur Hexafluoride (SF₆) Circuit Breaker:Úsáideann sé ga SF₆—athchúisitear as a phróiseolaíocht scora airc agus insüláide den scoth—mar mhéan scora. Is príomha é i gcórais trasnála high-voltage as ucht iontaofacht agus dearadh comhuaine.

  • Compressed Air Circuit Breaker:Úsáideann sé aer choimeádtha chun an t-arc a scoráil agus insüláide a thabhairt tar éis an scora. Níl sé chomh coitianta inniu mar gheall ar chomhshó aonrach agus coimeád.

  • Magnetic Blow-Out Circuit Breaker:Úsáideann sé fórsa electromagnecteach chun an t-arc a dhéanamh dul isteach i slite cogaí áirithe áit a rachann sé go fuar agus díonach. Tíospríonn sé go forleathan i ngniomhaíochtaí DC nó AC speisialta.

II. Deifir Chomhchoite agus Díúltú Briseoirí Circe High-Voltage

1. Theip ar Dhúntas (Refusal to Close)

D'fhéadfadh seo bheith mar thoradh ar cheisteanna meicniúla, deifir i gciorcuit stiúir, nó míghníomhaíochta. Seiceáil ciorcuit stiúir leictreach agus comhábhair meicniúla.

Deifir leictreacha:

(1) Lampa léitheoireachta gan oibriú nó neamhrialta

  • Seiceáil má dílíontar voltagh cumhachta stiúir le luach réamhdhite.

    • Má níos éiríonn an solas dearg nuair atá an spionnóg i "close" position, is dócha gur  open closing circuit no blown fuse.

    • Má díríonn an solas glas (trip position) ach níos éiríonn an solas dearg (close position), seiceáil red lamp integrity.

    • Má díríonn an solas glas agus éiríonn arís: is féidir low voltage no mechanical failure in operating mechanism.

    • Má éireann an solas dearg ar feadh tréimhse ghearr ansin díríonn agus éiríonn an solas glas: dúnadh an briseoir go moillmhar ach theip air a lúcháil— mechanical fault no excessively high control voltage ag déanamh theip tionchar.

(2) Closing contactor does not operate

  • Má tá an solas glas as: seiceáil control bus fuses (positive/negative).

  • Má tá an solas glas ar: úsáid peann tástála nó multimeter chun control switch, anti-pumping relay, auxiliary contacts, agus seiceáil ar coil open circuit no secondary wiring break.

(3) Closing contactor operates but breaker does not move

  • Féidearthachtaí: poor contactor contact, arc chute jamming, open closing coil, or blown AC fuse in closing rectifier.

(4) Closing contactor operates, breaker moves but fails to close fully
Féidearthachtaí:

  • Mechanical failure in operating mechanism

  • Low DC bus voltage

  • Secondary wiring mix-up accidentally energizing trip circuit

  • Improper operation (e.g., operator releasing control switch too early)

2. Theip ar Thriop (Refusal to Trip)

Is mór an ngéarraidh ná theip ar dhúnadh, mar gheall ar gur féidir leis an triop tríobháil a dhéanamh (cascade tripping), ag leathnú scóip easpa.

(1) Cúrsaí theipe leictreach

  • Red light not lit: indicates open trip circuit.

    • Seiceáil: lamp integrity, fuse, control switch contacts, breaker auxiliary contacts.

    • Seiceáil: anti-pumping relay coil, trip circuit continuity.

  • Trip coil operates weakly: may be due to high coil pickup voltage, low operating voltage, stuck trip plunger, or coil fault.

  • Trip plunger moves but breaker does not trip: likely mechanical jamming or detached drive linkage pin.

(2) Handling refusal to trip

  • Manual trip fails: Immediately report to dispatch.

    • If bypass switch available: transfer load to bypass, open bus-side disconnectors of faulty breaker, then trip bypass breaker to de-energize the circuit.

  • Upstream breaker trips due to cascade fault:

    • With power off, open disconnectors on both sides of the faulty breaker.

    • Manually open all feeders on the affected bus.

    • Report to dispatch for system restoration.

3. Unintended Opening or Closing (False Operation)

(1) Unintended Tripping (False Trip)
Occurs when breaker trips without protection activation or operator action. Possible causes:

  • Two-point DC grounding in control circuit—check and eliminate ground fault before reclosing.

  • Faulty interlock mechanism—isolate breaker (open source-side disconnector) and test close once.

  • If evidence suggests internal fault despite no relay activation, investigate accordingly.

(2) Unintended Closing (False Close)
A de-energized breaker closes without command. Causes:

  • Two-point DC grounding energizing closing circuit.

  • Stuck auto-reclose relay contact.

  • Low pickup voltage + high coil resistance, causing false closure during DC transient pulses.

4. Overheating of Circuit Breaker

Main symptoms: overheated tank (especially in minimum-oil breakers), heated frame.

  • Cause: Poor contact or oxidation in conductive parts.

  • Risks: Insulation damage, cracked porcelain, smoking, oil spraying, or even explosion.

  • Action: Strengthen patrols, detect early, and address promptly.

5. Other Common Faults

(1) Oil Circuit Breaker Fire
Fire may result from dirty or damp bushings causing ground flashover, or internal arcing.

  • If fire just started: Immediately remotely trip the breaker.

  • If fire is severe: Use upstream breaker to isolate the circuit, then open disconnectors on both sides to fully isolate the unit. Extinguish with dry-type fire extinguisher (e.g., CO₂ or powder).

(2) Trip/Close Coil Smoking
Trip/close coils are designed for short-time duty. Prolonged energizing causes overheating and burnout.

  • Action: Immediately report to dispatch and request replacement.

  • If closing fuse blows during operation, replace only with specified rating—never use oversized fuse to prevent coil damage.

(3) Emergency Manual Trip Required
Immediately take oil circuit breaker out of service if any of the following occur:

  • Severe porcelain insulator cracking, flashover, or explosion

  • Melting or disconnection of conducting parts

  • Loud internal arcing sounds

  • Severe oil deficiency

Summary

This guide provides a comprehensive overview of high-voltage circuit breaker types, common operational faults, and corrective actions. Proper classification, regular inspection, and prompt troubleshooting are essential for ensuring system reliability, personnel safety, and equipment longevity.

Tabhair leithrinn agus coiméide an údar!
Moltaigh
Cúrsaí Grúndála Céimeanna Cabhla agus Prionsabail an Óbhais Díolaim
Cúrsaí Grúndála Céimeanna Cabhla agus Prionsabail an Óbhais Díolaim
Is stáisiún 220 kV againn atá suite go himeartha ón lárnach cathrach i réimse éigeantach, timpeall air a bhfuil páirceanna tionsclaíocha mar Lanshan, Hebin, agus Tasha Industrial Parks. Ina measc na gcústóirí mórúsacha sa réigiún—lena n-áirítear foirgnimh carbcín síicéide, ferroalloy, agus carbaid cálcium—tugtar cuntas ar thart ar 83.87% de luchtú árnbhuró. Oibríonn an stáisiún ag leibhéal voltaí 220 kV, 110 kV, agus 35 kV.Príomhthacáil an taobh ísle voltaí 35 kV tá sí ag soláthar feeders do fho
Felix Spark
10/21/2025
Treoir Fadhbanna Coitianta & Solúidí do 10kV RMU
Treoir Fadhbanna Coitianta & Solúidí do 10kV RMU
Fadhbanna Feidhmeáin agus Beartais do Aonaid Mórchiorcla 10kV (RMUs)Is feidhmeán deighineach é an aonad mórchiorcla 10kV (RMU) i ndúshlánuithe ar an ngnéasóireacht, ag baint úsáide as sé go príomha le haghaidh fógraíocht meánvoltaí. Le linn oibriú fíor, d'fhéadfadh fadhbanna éagsúla teacht chun cinn. Anseo thíos, na fadhbanna coitianta agus na beartais cuí.I. Fadhbanna Deileachta Ciorcal Coitianta Isteach nó Cabhlach MeasarthaD'fhéadfadh ciorcal coitianta isteach nó cabhlach measartha sa RMU a d
Echo
10/20/2025
10 Cúram do Tháirgeadh agus Oibriú an Trafó!
10 Cúram do Tháirgeadh agus Oibriú an Trafó!
10 Cúrsaí a Bhfuil Fágáil Amach i Leith Socrú agus Oibriú an Trasnóir! Ná socrúigh an trasnóir riamh níos faide ná mar is gá—bíodh sé cosúil leis é a chur in ait thall nó i bpáirc mhór. Is minic a chuirtear isteach ar chábail agus feabhsaíonn sé fiachais líne, ach cuireann sé go háirithe deacracht ar bhainistíocht agus cothú. Ná roghnaigh an ciorcalacht trasnóra go foréigneach. Tá sé tábhachtach an ciorcalacht ceart a roghnú. Má tá an ciorcalacht ró-bheag, d'fhéadfadh an trasnóir a bheith tríthi
James
10/20/2025
Conas a choinneáil Trasnóirí Dúnta go Sábháilte?
Conas a choinneáil Trasnóirí Dúnta go Sábháilte?
Modholaí Meaitseála do Thraisfóirmeoirí Géar Cuir an traisfóirim ghearrach isteach i bhfeidhm, oscail an briseadh chiorcail ar thaobh ísle-spéile an traisfóirmeora atá le meaitseáil, baint amach an fuinneog stiúir, agus cuardach "NÁ DÚNGAÍ" ar uilleoga an briseadh. Oscail an briseadh chiorcail ar thaobh ard-spéile an traisfóirmeora atá le meaitseáil, dúng an briseadh talamhuín, scarraíoch an traisfóirim go lán, glasaigh an armadach ard-spéile, agus cuardach "NÁ DÚNGAÍ" ar uilleoga an briseadh. D
Felix Spark
10/20/2025
Seol fiosrúchán
Íoslódáil
Faigh an tApliú IEE Business
Úsáid an t-aip IEE-Business chun eochair uirlis a aimsiú déantar réiteach a fháil nasc le saineolaithe agus glacadh páirte i gcothromhachtú tionscail ar bith áit ar bith go láidir tacú le forbairt do thionscadal forbartha agus gnó