• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Air Circuit Breaker Tripping? 90% Overlook This Critical Cause!

Leon
Leon
Field: Fault Diagnosis
China

In daily life and industrial operations, we often encounter circuit breakers tripping. Common causes include faulty breakers themselves or leakage/short circuits in the load. However, some tripping incidents have unexpected origins.

circuit.jpg

At a mine, an emergency backup power system consisted of a diesel generator (400V), which fed a mining transformer (10,000V–400V) to step up voltage and supply power to the underground shaft. One rainy day, the main grid power failed. To ensure safety underground, the mine immediately started the diesel generator. However, when attempting to close the breaker to energize the step-up transformer, the air circuit breaker tripped instantly. Repeated attempts resulted in the same immediate tripping. At this point, the high-voltage side switch of the transformer had not yet been closed; the only load in the circuit was the transformer itself—leading to suspicion that the transformer might be faulty.

circuit.jpg

Mine electricians inspected the transformer visually, finding no signs of arcing or burning. Using a megohmmeter, they tested insulation resistance on both high- and low-voltage sides (including cables), all results appearing normal. Due to limited equipment, no further tests could be performed.

The mine contacted me. I arrived on-site with appropriate instruments and measured the transformer’s winding DC resistance and turns ratio. All data fell within normal ranges. Combined with the electricians’ findings, I concluded the transformer itself was likely intact.

Next, I disconnected the output cables from the switching cabinet, started the diesel generator, and tested the power-up. This time, the air circuit breaker closed successfully—indicating the fault lay between the switching cabinet’s output and the transformer’s high-voltage switch.

Upon carefully inspecting the path between the cabinet and the transformer, I noticed that the transformer’s low-voltage junction box lacked a sealing gasket. The cover plate was extremely close to the low-voltage terminals—only about 3mm apart, far below the required electrical clearance and creepage distance for 380V systems (8mm and 12mm, respectively). I concluded this was the root cause of the breaker tripping.

After reinstalling the sealing gasket into the transformer’s junction box, I restarted the diesel generator. The breaker successfully closed, and power was restored.

The fault occurred because the insufficient clearance between the junction box cover and the low-voltage terminals allowed point discharge during the high inrush current at breaker closing. This caused a three-phase-to-ground short circuit, triggering the instantaneous trip of the air circuit breaker.

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.