• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Air Circuit Breaker Tripping? 90% Overlook This Critical Cause!

Leon
Field: Fault Diagnosis
China

In daily life and industrial operations, we often encounter circuit breakers tripping. Common causes include faulty breakers themselves or leakage/short circuits in the load. However, some tripping incidents have unexpected origins.

circuit.jpg

At a mine, an emergency backup power system consisted of a diesel generator (400V), which fed a mining transformer (10,000V–400V) to step up voltage and supply power to the underground shaft. One rainy day, the main grid power failed. To ensure safety underground, the mine immediately started the diesel generator. However, when attempting to close the breaker to energize the step-up transformer, the air circuit breaker tripped instantly. Repeated attempts resulted in the same immediate tripping. At this point, the high-voltage side switch of the transformer had not yet been closed; the only load in the circuit was the transformer itself—leading to suspicion that the transformer might be faulty.

circuit.jpg

Mine electricians inspected the transformer visually, finding no signs of arcing or burning. Using a megohmmeter, they tested insulation resistance on both high- and low-voltage sides (including cables), all results appearing normal. Due to limited equipment, no further tests could be performed.

The mine contacted me. I arrived on-site with appropriate instruments and measured the transformer’s winding DC resistance and turns ratio. All data fell within normal ranges. Combined with the electricians’ findings, I concluded the transformer itself was likely intact.

Next, I disconnected the output cables from the switching cabinet, started the diesel generator, and tested the power-up. This time, the air circuit breaker closed successfully—indicating the fault lay between the switching cabinet’s output and the transformer’s high-voltage switch.

Upon carefully inspecting the path between the cabinet and the transformer, I noticed that the transformer’s low-voltage junction box lacked a sealing gasket. The cover plate was extremely close to the low-voltage terminals—only about 3mm apart, far below the required electrical clearance and creepage distance for 380V systems (8mm and 12mm, respectively). I concluded this was the root cause of the breaker tripping.

After reinstalling the sealing gasket into the transformer’s junction box, I restarted the diesel generator. The breaker successfully closed, and power was restored.

The fault occurred because the insufficient clearance between the junction box cover and the low-voltage terminals allowed point discharge during the high inrush current at breaker closing. This caused a three-phase-to-ground short circuit, triggering the instantaneous trip of the air circuit breaker.

Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.