• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Kaddamar da Zama da Gyara Fage-gyare na Ƙarfin Yawanci?

James
James
فیلڈ: Gwamnatiyar Kuliya
China

Tattalin da Taurari da Kammalawa na Kirkiya Masu Hukuma

1. Muhimmanci Don Tattalin Da Kammalawa

  • Duk fadada da tushen da za a tattala da kammala suka zama da shawarwari da ake gaskiya ta hanyar.

  • Abubuwa da halayansu da za a yi wa tattalin da kammalawa suka fi sani da ke daidai masu amfani da su. Abubuwan da za su iya tabbatar da su suna da alamar box-end, ring, ko socket wrenches. Ba za a yi amfani da adjustable (open-end) wrenches wajen tabbatar da abubuwan da ke kusa da birnin hukuma ba.

  • Za a yi tattalin da kammalawa a cikin yanayin da aka bayyana. Abun abubuwan da za su iya tabbatar da su suna da alamun da aka bayyana. Ya kamata ya fi dacewar da tsawon kirkiyoyin da ke fixe terminalin contact stationa ta birnin hukuma.

  • Ba a kammala da tattalin da kammalawa, ba za a duba da yanayin da aka bayyana pole-to-pole distance da kuma yanayin terminal output da ke yanzu da karamin kasa.

  • Duk abubuwan da za su iya haɗa da kammalawa suka duba da yanayin da aka bayyana. Za a yi amfani da greasin don magance ma'adanu.

  • Ba a kammala da tattalin da kammalawa, ba za a duba da yanayin da aka bayyana. Za a shirya abubuwan da za su iya haɗa da kammalawa su da painti mai lafiya don nuna wurin. Za a yi amfani da petroleum jelly don terminal output, sannan za a wrap su da paper mai lafiya don magance.

2. Yanayin Kammalawa

A nan za a yi misali da ZN39-type vacuum circuit breaker, kammalawan da aka yi ana iya duba da uku: mafi yamma, mafi girma, da kuma mafi yamma.

Yanayin Kammalawa na Mafi Yamma:
Positioning frame → Support insulators → Horizontal insulators → Support bracket → Lower busbar → Arc extinguishing chamber and parallel insulating rods → Upper busbar → Conductive clamp with flexible connection → Contact spring seat and sleeve → Triangular crank arm.

Yanayin Kammalawa na Mafi Girma:
Main shaft and bearing housing → Oil damper → Insulating push rod.

Yanayin Kammalawa na Mafi Yamma:
Operating mechanism → Opening spring → Counter, open/close indicator, grounding mark.

Integration of the Three Sections:

  • Connect the front and upper sections: link the adjustable joint of the insulating push rod to the triangular crank arm with a pin.

  • Connect the rear and upper sections: link the adjustable drive rod of the operating mechanism to the main shaft crank arm with a pin.

Yanayin kammalawa ana iya duba da yanayin da aka bayyana, da kuma ana iya samun.

Vacuum circuit breaker..jpg

3. Tattalin da Kammalawa na Siffofin Mechanic

3.1 Tattalin da Kammalawa Na Biyu

Tattalin da kammalawa na biyu ana iya samun da kammalawa na gap (opening distance) da kammalawa na travel (overtravel) ta duk pole ba a kan kammalawa na biyu.

Close the breaker manually slowly to verify correct installation and connection of all components. Avoid setting excessive contact travel, as this may compress the closing spring fully (spring binding), potentially damaging components. To prevent this, initially set the adjustable joint of the insulating push rod shorter (screwed in). After confirming smooth manual operation, proceed to measure and adjust the opening distance and contact travel.

3.2 Tattalin da Kammalawa Na Gap da Travel

Kirkiyoyin masu hukuma ana iya samun da kammalawa na biyu a cikin kammalawa na gap (opening distance) da kammalawa na travel (overtravel).

  • Type I: Coaxial Structure - Moving contact cup axis coincides with the closing spring axis.

  • Type II: Offset (Non-coaxial) Structure - Moving contact rod axis is separate from the closing spring axis, with the spring mounted on the insulating push rod shaft, nearly perpendicular to the contact rod.

The calculation and adjustment methods differ slightly between these two types.

Mechanical characteristic tables for various vacuum circuit breakers specify nominal values for opening distance and contact travel. After manually performing open and close operations and measuring actual values, adjust as follows to meet technical specifications.

(1) Adjustment for Coaxial Structures

  • Step 1: Adjust Total Travel
    Total travel = Opening distance + Contact travel.
    If total travel is less than the sum of nominal values, the main shaft rotation is insufficient. Lengthen the adjustable connecting rod between the operating mechanism and main shaft crank arm. If too long, shorten the rod. This ensures total travel meets requirements.

  • Step 2: Adjust Distribution Between Opening Distance and Contact Travel
    Adjust the threaded connection at the front end of each pole’s insulating rod.

    Minimum adjustment: half a thread pitch (by turning the joint 180°).
    This threaded joint also adjusts three-phase synchronization. Adjustments must balance travel values and phase synchronization. Repeat manual open/close cycles until both are within tolerance. Never exceed maximum allowable contact travel to avoid spring binding and component damage.

    • Lengthen connection (screw out): Opening distance ↑, Contact travel ↓

    • Shorten connection (screw in): Opening distance ↓, Contact travel ↑

(2) Adjustment for Offset (Non-coaxial) Structures

In this design, the closing spring axis and moving contact axis are not aligned, so total travel has no direct physical meaning. Adjustment methods differ:

  • Opening Distance Adjustment:
    Achieved via an "opening distance adjustment shim" mounted on the frame. The shim’s height is adjusted by adding or removing layers. The top is pressed by the main shaft’s crank arm. Changing the shim height alters the main shaft’s initial angle in the open position, thereby changing the contact opening distance through the insulating push rod.

  • Contact Travel Adjustment:
    The pre-compression height (B1) of the contact spring is fixed by the roller diameter and cannot be changed. The final compression height (B2) after closing is adjusted by:

    During adjustment, simultaneously optimize three-phase synchronization, making repeated fine adjustments until all parameters are within tolerance.

    • Lengthen rod: B2 decreases → Contact travel increases

    • Shorten rod: B2 increases → Contact travel decreases

    • Screw in (shorten rod): B2 increases → Contact travel decreases

    • Screw out (lengthen rod): B2 decreases → Contact travel increases

    • A. Adjusting the threaded joint at the end of the insulating push rod:

    • B. Adjusting the length of the connecting rod between the operating mechanism and the main shaft crank arm:

(3) Auxiliary Switch Interlock Adjustment

After manually adjusting opening distance and contact travel, the auxiliary switch interlock position must be properly set before electric operation—otherwise, electrical components may be damaged.

Adjustment Procedure:

  • Disconnect the pin between the auxiliary switch and the main shaft crank arm linkage.

  • Manually close the breaker while rotating the auxiliary switch to the point just before it trips. Adjust the length of the adjustable rod and bolt so that the pin holes align approximately.

  • Manually open the breaker and rotate the auxiliary switch to its trip point again, ensuring pin holes align.

  • Repeat the process until alignment is achieved in both open and close positions, then insert the pin.

  • Ensure the auxiliary switch contacts open slightly before the main contacts fully close or open.

4. Tattalin da Kammalawa, Fine Adjustment, and Factory Tests

4.1 Characteristic Testing

After preliminary adjustment of opening distance, contact travel, and auxiliary switch, perform electric open/close operations and measure the following mechanical characteristics:

  • Opening/closing time

  • Speed

  • Phase-to-phase synchronization (out-of-phase)

  • Closing bounce

Testing Instruments:

  • Optical oscillograph – highly accurate and visual

  • Circuit breaker analyzer – simple, fast, and sufficiently accurate for field use

(Specific test methods are not detailed here.)

4.2 Fine Adjustment of Mechanical Characteristics

After testing, perform fine adjustments on any out-of-spec parameters to achieve optimal performance.

(1) Fine Adjustment of Synchronization
Identify the phase with the greatest timing deviation. If one pole closes too early (or late), slightly increase (or decrease) its opening distance by turning the insulating rod’s adjustable joint in (for earlier closure) or out (for later closure) by about half a turn. Typically, this can reduce synchronization error to within 1 ms.

(2) Fine Adjustment of Opening/Closing Speed
Speed is influenced by multiple factors, but key adjustable elements are the opening spring tension and contact travel.

  • Closing speed too high, opening speed too low:
    Increase contact travel or tighten the opening spring.

  • Closing speed acceptable, opening speed too low:
    Increase total travel by 0.1–0.2 mm, which increases contact travel and improves opening speed.

  • Opening speed too high:
    Reduce contact travel by 0.1–0.2 mm to lower speed.

After adjustment, re-measure opening distance and contact travel to ensure they remain within specified ranges.

(3) Elimination of Closing Bounce

Closing bounce may result from:

  • Excessive closing impact rigidity, causing axial rebound of the moving contact.

  • Poor guidance of the moving contact rod, resulting in excessive wobble.

  • Excessive clearance in transmission links, especially between the contact spring and the conductive rod.

  • Poor perpendicularity between the contact surface and the central axis, causing lateral slip upon contact (appears as "bounce" on oscillograms).

Mitigation Measures:

  • Design should avoid excessive mechanical rigidity (not adjustable post-manufacture).

  • Ensure proper guidance clearance for the moving contact rod.

  • In coaxial designs, the contact spring connects directly to the conductive rod—no intermediate links, hence less bounce.

  • In offset designs, a triangular crank arm with three pins introduces three potential clearances, increasing bounce risk.

If bounce is caused by poor perpendicularity of the arc extinguishing chamber contact surface, try rotating the chamber by 90°, 180°, or 270° during assembly to find the optimal alignment. If ineffective, replace the arc extinguishing chamber.
Ensure all screws are fully tightened during adjustment to avoid vibration interference.

(4) Factory Acceptance Tests

After all mechanical characteristics meet specifications, perform 50 operation cycles (open/close and reclose) at maximum, minimum, and rated control voltage as per factory requirements.

After 50 operations, re-measure all mechanical parameters. Results should closely match initial measurements to pass.

Finally, perform:

  • Circuit resistance test

  • Power frequency withstand voltage tests on primary and secondary circuits

Only units passing all tests are approved for shipment.

Ba da kyau kuma kara mai rubutu!
Tambayar Da Yawanci
Ko kari ƙoƙarin shirya ɗaya na 10kV
Ko kari ƙoƙarin shirya ɗaya na 10kV
Wannan makaranta ta shirya misalai don koyar da zakaici na logic ta zaɓi ɗaya 10kV steel tubular poles, tana magana game da abubuwa masu yawa, kiyaye da yanayin da suka samu, da kuma abubuwan da ke buƙata waɗanda ana iya amfani da su a cikin koyar da zakaici na 10kV overhead line. Kowane wurare (kamar wasu lokaci mai gaba ko kasa mai kyau) suna buƙatar ingantaccen bayanai daban-daban don in ba da tabbacin cikakken ɗaya.Abubuwan Da Ke Buƙata Don Zaɓi Ɗaya Na Overhead Transmission LineZaɓin daidai
James
10/20/2025
Ko da zaka iya kowa aiki na tashin mafi yawa?
Ko da zaka iya kowa aiki na tashin mafi yawa?
1. Sistem Kontrol SuhuSatu dari penyebab utama kegagalan transformator adalah kerusakan isolasi, dan ancaman terbesar bagi isolasi berasal dari melebihi batas suhu yang diperbolehkan pada gulungan. Oleh karena itu, pemantauan suhu dan penerapan sistem alarm untuk transformator yang beroperasi sangat penting. Berikut ini memperkenalkan sistem kontrol suhu menggunakan TTC-300 sebagai contoh.1.1 Kipas Pendingin OtomatisTermistor dipasang di titik terpanas pada gulungan tegangan rendah untuk mendapa
James
10/18/2025
Daidaitaccen Masu Kudin Tausayi Da Duk Da Gaskiya?
Daidaitaccen Masu Kudin Tausayi Da Duk Da Gaskiya?
Daidaitaccen Da Zabe da Kudin Transformer1. Muhammanci na Daidaitaccen Da Zabe da Kudin TransformerTransformers suna da muhimmanci sosai a cikin nufin kuliya. Suna tattara masu zabe don zaɓe da ma'aikata daban-daban, wanda ke jin kuliya da aka gina a cikin kuliyan suka shafi da kuma zama mai amfani. Idan ba a daidaita da zabe ko kudi transformer ba, yana iya haɗa da abubuwa mafi yawan. Misali, idan babbanar ta fiye, transformer ba za su iya taimaka da zabe da ke magance, wanda yake iya haɗa da t
James
10/18/2025
Karamin Ƙananan Kirkiya na Zabe ta 10kV Daidai
Karamin Ƙananan Kirkiya na Zabe ta 10kV Daidai
I. Bayyana na Vakansu Circuit Breakers a Wani Yawanci1. Bayyana a Tsari (ON) Muhimmanci da zai iya kula da tsari; Zuru mai tsari ya zama ta gida daga oil damper; Spring mai fitowa yana cikin hali mai energy-stored (stretched); Take da zakaɗaukar contact rod mai vakansu mai fi shahara a cikin guide plate yana da 4–5 mm; Bellows a cikin vacuum interrupter yana iya samun (bayan wannan ba za su iya amfani da ceramic-tube interrupters); Stickers mai nuna temperature a ƙarfin da kuma tsohon ƙarfi ba s
Felix Spark
10/18/2025
Aika tambaya
Kwamfuta
Samun IEE Business Application
Yi amfani da IEE-Business app don samun abubuwan aikin, samun halayyin, haɗi da malamai, kuma kai tsauraran takaiddun kasoshin duka lokaci, duka wurin—dole bai karfin takamaltar hulɗin ku na alintakargida da kasuwanci.