What are the common faults of load switches?

Felix Spark
Field: Failure and maintenance
China
As an on-site maintenance technician, I frequently deal with electrical, mechanical, and insulation faults in load switches. The following outlines fault manifestations, causes, and solutions:
I. Electrical Fault Handling
(1) Contact Heating
Contact heating is mainly caused by poor contact, insufficient pressure, or three-phase asynchrony. When the contact resistance exceeds 1.5 times the initial value, the temperature rise will exceed the standard in a 40℃ environment. For example, the FW4-10 switch only has an electrical life of 5 times when breaking an 800A current.
Solutions:
  • Clean silver contacts with 25%-28% ammonia water, then apply neutral Vaseline.
  • Adjust main contact pressure to ≥150N.
  • Calibrate opening/closing synchronism to ≤3.3ms/≤5ms.

(2) Fuse Blowing
Fuse blowing results from short circuits, overloads, or improper selection (e.g., RN1-10 fuses rated 2-5000A). Replace fuses after identifying the cause, and ensure the load switch can handle currents within the "transfer current" range.
(3) Abnormal Arcing
Arcing issues stem from failed arc extinguishers or degraded contact materials. Regularly inspect the arc chamber and cylinder seals in pneumatic switches, and avoid frequent high-current operations per GB/T 3804.
II. Mechanical Fault Handling
(1) Operating Mechanism Jamming
Jamming occurs due to component aging, insufficient lubrication, etc. Detect jamming via motor current analysis, then:
  • Check connecting rod torque (M10 bolt 8.8 grade → 20±2N·m).
  • Apply molybdenum disulfide grease (drop point ≥300℃).
  • Replace fatigued springs and adjust the spindle angle/crank arm.
(2) Contact Wear
Wear is caused by frequent operations and arcing. Replace CuW80 contacts if wear exceeds 3mm. Monitor wear regularly and maintain synchronism (opening ≤3.3ms, closing ≤5ms) to balance three-phase currents.
 
(3) Interlock Failure
Interlock failure, often from mechanical wear, poses safety risks. Regularly inspect interlock structures and test functions, replacing components as needed.
III. Insulation Fault Handling
(1) Insulation Moisture
Moisture ingress occurs in high-humidity environments (e.g., coastal areas). Use EPDM seals and:
  • Dry and apply nano moisture-proof coatings.
  • Replace insulation parts or oil (ensure breakdown voltage ≥25kV for oil-immersed switches).
(2) Insulation Aging
Aging accelerates at high temperatures (10℃ rise shortens life by 50%-70%). Monitor via tanδ, insulation resistance, and partial discharge (PD ≤10pC). Replace aged parts and use CT scans for epoxy components.
(3) Insulation Resistance Drop
Test with a 2500V megohmmeter (≥1000MΩ). Investigate drops via oil analysis and replace/repair faulty parts.
Give a tip and encourage the author!
Recommended
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
I. Introduction to Cable Grounding Loop CurrentCables rated 110 kV and above use a single-core structure. The alternating magnetic field generated by the operating current induces a voltage on the metallic sheath. If the sheath forms a closed circuit through the earth, a grounding loop current will flow on the metallic sheath. Excessive grounding loop current (loop current exceeding 50 A, more than 20% of the load current, or a ratio of maximum-to-minimum phase current greater than 3) not only a
Felix Spark
09/03/2025
Repair of high-voltage cable metallic sheaths
I. Functions of Metallic Sheaths and Necessity of RepairThe metallic sheath of high-voltage cables is a metal shielding structure laid outside the insulation layer, including types such as lead sheaths, aluminum sheaths, and steel wire armor. Its core functions include mechanical protection (resisting external impact and compression), electrochemical corrosion protection (isolating moisture and soil pollutants), electromagnetic shielding (reducing electromagnetic interference to the environment)
Felix Spark
09/03/2025
Working Principle and Arc Extinction Mechanism of Magnetic Blowout Device in DC Circuit Breakers
The arc extinguishing system of a DC circuit breaker is crucial for the safe operation of equipment, as the arc generated during current interruption can damage contacts and compromise insulation.In AC systems, the current naturally passes through zero twice per cycle, and AC circuit breakers take full advantage of these zero-crossing points to extinguish the arc.However, DC systems lack natural current zero crossings, making arc extinction significantly more difficult for DC circuit breakers. T
Felix Spark
09/02/2025
Analysis of Common Operational Fault Causes in Smart Electricity Meters
With the continuous development of smart grids, smart electricity meters are being increasingly widely applied, and various types of operational faults in smart meters are frequently encountered in energy measurement work. This paper analyzes the causes of smart meter failures and proposes corresponding solutions, using several actual operational fault cases as examples.1. Black ScreenA black screen refers to a powered meter with no display, which is the most commonly occurring fault in field-op
Felix Spark
09/01/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.