What are the common faults of load switches?

Felix Spark
06/28/2025

As an on-site maintenance technician, I frequently deal with electrical, mechanical, and insulation faults in load switches. The following outlines fault manifestations, causes, and solutions:
I. Electrical Fault Handling
(1) Contact Heating
Contact heating is mainly caused by poor contact, insufficient pressure, or three-phase asynchrony. When the contact resistance exceeds 1.5 times the initial value, the temperature rise will exceed the standard in a 40℃ environment. For example, the FW4-10 switch only has an electrical life of 5 times when breaking an 800A current.
Solutions:
  • Clean silver contacts with 25%-28% ammonia water, then apply neutral Vaseline.
  • Adjust main contact pressure to ≥150N.
  • Calibrate opening/closing synchronism to ≤3.3ms/≤5ms.

(2) Fuse Blowing
Fuse blowing results from short circuits, overloads, or improper selection (e.g., RN1-10 fuses rated 2-5000A). Replace fuses after identifying the cause, and ensure the load switch can handle currents within the "transfer current" range.
(3) Abnormal Arcing
Arcing issues stem from failed arc extinguishers or degraded contact materials. Regularly inspect the arc chamber and cylinder seals in pneumatic switches, and avoid frequent high-current operations per GB/T 3804.
II. Mechanical Fault Handling
(1) Operating Mechanism Jamming
Jamming occurs due to component aging, insufficient lubrication, etc. Detect jamming via motor current analysis, then:
  • Check connecting rod torque (M10 bolt 8.8 grade → 20±2N·m).
  • Apply molybdenum disulfide grease (drop point ≥300℃).
  • Replace fatigued springs and adjust the spindle angle/crank arm.
(2) Contact Wear
Wear is caused by frequent operations and arcing. Replace CuW80 contacts if wear exceeds 3mm. Monitor wear regularly and maintain synchronism (opening ≤3.3ms, closing ≤5ms) to balance three-phase currents.
 
(3) Interlock Failure
Interlock failure, often from mechanical wear, poses safety risks. Regularly inspect interlock structures and test functions, replacing components as needed.
III. Insulation Fault Handling
(1) Insulation Moisture
Moisture ingress occurs in high-humidity environments (e.g., coastal areas). Use EPDM seals and:
  • Dry and apply nano moisture-proof coatings.
  • Replace insulation parts or oil (ensure breakdown voltage ≥25kV for oil-immersed switches).
(2) Insulation Aging
Aging accelerates at high temperatures (10℃ rise shortens life by 50%-70%). Monitor via tanδ, insulation resistance, and partial discharge (PD ≤10pC). Replace aged parts and use CT scans for epoxy components.
(3) Insulation Resistance Drop
Test with a 2500V megohmmeter (≥1000MΩ). Investigate drops via oil analysis and replace/repair faulty parts.
Felix Spark

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
1 IntroductionLow - voltage current transformers for metering, with a through - core type epoxy resin structure, are widely used in distribution transformer areas and for small - to - medium - sized industrial and commercial electricity consumption. As a range expander for electric energy metering, their performance directly relates to electricity consumption safety and the accuracy of users' trade calculations. Studying long - term immersion's impact on these transformers is practically signifi
Felix Spark
07/17/2025
What are the common faults that occur when low-voltage current transformers are combined with other power equipment?
What are the common faults that occur when low-voltage current transformers are combined with other power equipment?
Low-voltage current transformers, as indispensable measurement and protection devices in power systems, often encounter various faults when used in combination with other power equipment due to environmental factors, equipment linkage issues, and improper installation and maintenance. These faults not only affect the normal operation of power equipment but may also endanger personal safety. Therefore, it is necessary to gain an in-depth understanding of fault types, judgment methods, and prevent
Felix Spark
07/17/2025
What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
1. Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In lo
Oliver Watts
07/16/2025
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage
Felix Spark
07/15/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!