• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


10 kV VCB Faults: The 4 Most Common Issues You Must Know

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Common Vacuum Circuit Breaker Faults and On-Site Troubleshooting by Electrical Engineers

As vacuum circuit breakers are widely used in the power industry, performance varies significantly among manufacturers. Some models offer excellent performance, require minimal maintenance, and ensure high power supply reliability. Others suffer from frequent issues, while a few have severe defects that may cause over-level tripping and large-scale blackouts. Let’s explore real-world fault handling by electrical engineers to gain practical experience and master comprehensive maintenance techniques.

1. Reduced Vacuum in Vacuum Interrupter

1.1 Fault Phenomenon
Vacuum circuit breakers interrupt current and extinguish arcs within the vacuum interrupter. However, most lack built-in qualitative or quantitative vacuum monitoring, making vacuum loss a hidden (latent) fault—far more dangerous than obvious failures.

1.2 Root Causes

  • Defects in the vacuum bottle’s material or manufacturing process, causing micro leaks.

  • Issues with the bellows material or fabrication, leading to leaks after repeated operations.

  • In separate-type VCBs (e.g., those with electromagnetic operating mechanisms), large linkage travel affects synchronization, bounce, and over-travel, accelerating vacuum degradation.

1.3 Hazards
Reduced vacuum severely impairs the breaker’s ability to interrupt fault currents, drastically shortens service life, and may lead to explosions.

1.4 Solutions

  • During scheduled outages, use a vacuum tester to perform qualitative vacuum checks and confirm adequate vacuum levels.

  • Replace the vacuum interrupter if vacuum loss is detected, and conduct travel, synchronization, and bounce tests afterward.

1.5 Preventive Measures

  • Choose vacuum breakers from reputable manufacturers with proven, mature designs.

  • Prefer integrated designs where the interrupter and operating mechanism are combined.

  • During patrols, check for external arcing on the vacuum bottle. If present, vacuum integrity is likely compromised—schedule immediate replacement.

  • During maintenance, always test synchronization, bounce, travel, and over-travel to ensure optimal performance.

2. Failure to Trip (Trip Rejection)

2.1 Fault Symptoms

  • Remote control fails to trip the breaker.

  • Manual local tripping fails.

  • Relay protection operates during faults, but the breaker fails to trip.

2.2 Root Causes

  • Open circuit in the trip control loop.

  • Open trip coil.

  • Low operating voltage.

  • Increased trip coil resistance, reducing tripping force.

  • Deformed trip rod causing mechanical binding and reduced force.

  • Severely deformed trip rod causing complete jamming.

2.3 Hazards
Trip failure during faults leads to over-level tripping, expanding the fault scope and causing widespread outages.

2.4 Solutions

  • Check for open circuits in the trip control loop.

  • Inspect the trip coil for continuity.

  • Measure trip coil resistance for abnormalities.

  • Examine the trip rod for deformation.

  • Verify normal operating voltage.

  • Replace copper trip rods with steel ones to prevent deformation.

2.5 Preventive Measures

  • Operators: If trip/close indicator lights are off, immediately check for open control circuits.

  • Maintenance staff: During outages, measure trip coil resistance and inspect trip rod condition. Replace copper rods with steel.

  • Perform low-voltage trip/close tests to ensure reliable operation.

3. Spring Mechanism – Charging Circuit Faults

3.1 Fault Symptoms

  • After closing, the breaker cannot trip (insufficient energy).

  • The storage motor runs continuously, risking overheating and burnout.

3.2 Root Causes

  • Limit switch installed too low: Cuts motor power before spring is fully charged → insufficient energy for tripping.

  • Limit switch installed too high: Motor stays energized after full charge.

  • Faulty limit switch → motor fails to stop.

3.3 Hazards

  • Incomplete charging may cause trip failure during faults, leading to over-level tripping.

  • Motor burnout renders the breaker inoperable.

3.4 Solutions

  • Adjust limit switch position for accurate motor cutoff.

  • Replace damaged limit switches immediately.

3.5 Preventive Measures

  • Operators: Monitor the "spring charged" indicator during operation.

  • Maintenance: After servicing, perform two local trip/close operations to verify proper function.

4. Poor Synchronization & Excessive Contact Bounce

4.1 Fault Phenomenon
This is a hidden fault—only detectable via mechanical characteristic tests (e.g., timing analyzers).

4.2 Root Causes

  • Poor mechanical quality of the breaker body; repeated operations cause misalignment and high bounce.

  • In separate-type breakers, long linkage rods cause uneven force transmission, increasing phase-to-phase timing differences and bounce.

4.3 Hazards
High bounce or poor synchronization severely impacts fault current interruption, shortens lifespan, and may cause explosions. Due to its hidden nature, this fault is especially dangerous.

4.4 Solutions

  • Adjust the length of the three-phase insulating pull rods to bring synchronization and bounce within acceptable limits (while maintaining proper travel and over-travel).

  • If adjustment fails, replace the faulty phase’s vacuum interrupter and re-adjust.

4.5 Preventive Measures

  • Replace aging separate-type breakers with integrated (monobloc) designs to reduce failure risks.

  • During maintenance, always perform mechanical characteristic tests to detect and resolve issues early.

Final Note: Environmental Protection

Never overlook environmental impacts. Ensure clean, dry, vibration-free, and temperature-controlled conditions to guarantee safe and reliable operation of vacuum circuit breakers.

Give a tip and encourage the author!
Recommended
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
A "2-in 4-out 10 kVsolid-insulated ring main unit" refers to a specific type of ring main unit (RMU). The term "2-in 4-out" indicates that this RMU has two incoming feeders and four outgoing feeders.10 kVsolid-insulated ring main unit are equipment used in medium-voltage power distribution systems, primarily installed in substations, distribution stations, and transformer stations to distribute high-voltage power to low-voltage distribution networks. They generally consist of high-voltage incomi
Garca
12/10/2025
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.