• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


In-Depth Guide sa Common nga Mga Suliranan ug mga Paraan sa Pagtungha Alang sa 10kV Vacuum Circuit Breakers

Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

Common Vacuum Circuit Breaker Faults and On-Site Troubleshooting by Electrical Engineers

Tungod kay ang vacuum circuit breakers gigamit kaayo sa industriya sa kuryente, ang performance mahimong magbago-bago gikan sa usa ka manufacturer ngadto sa lain. Ang pipila ka mga modelo naghatag og maayo nga performance, gibag-o lamang ang maintenance, ug nagpadayon sa mataas nga reliable nga pagsumpli sa kuryente. Ang uban nimo mao ang madalas na mga problema, ug ang pipila adunay severe nga mga defect nga mahimong mogawas sa over-level tripping ug large-scale blackouts. Hingpit kita mo-eksplora ang real-world fault handling sa electrical engineers aron makasabot sa practical experience ug masteron ang comprehensive maintenance techniques.

1. Reduced Vacuum in Vacuum Interrupter

1.1 Fault Phenomenon
Ang vacuum circuit breakers nag-interrupt sa current ug nag-extinguish sa arcs sa vacuum interrupter. Pero, ang daghang wala'y built-in qualitative o quantitative vacuum monitoring, kasagaran nagresulta sa vacuum loss nga isip hidden (latent) fault—mas dangerous kaysa obvious failures.

1.2 Root Causes

  • Defects sa material o manufacturing process sa vacuum bottle, nagresulta sa micro leaks.

  • Issues sa material o fabrication sa bellows, nagresulta sa leaks human sa repeated operations.

  • Sa separate-type VCBs (e.g., ang may electromagnetic operating mechanisms), ang large linkage travel nagapekto sa synchronization, bounce, ug over-travel, nag-accelerate sa vacuum degradation.

1.3 Hazards
Ang reduced vacuum severely impairs ang breaker’s ability sa pag-interrupt sa fault currents, drastically shortens service life, ug mahimong mogawas sa explosions.

1.4 Solutions

  • Human sa scheduled outages, gamiton ang vacuum tester aron perform og qualitative vacuum checks ug confirm adequate vacuum levels.

  • Replace ang vacuum interrupter kon natukod ang vacuum loss, ug conduct travel, synchronization, ug bounce tests afterward.

1.5 Preventive Measures

  • Pili ang vacuum breakers gikan sa reputable manufacturers nga may proven, mature designs.

  • Prefer integrated designs diin ang interrupter ug operating mechanism combined.

  • Sa patrols, check alang external arcing sa vacuum bottle. Kon present, likely compromised ang vacuum integrity—schedule immediate replacement.

  • Sa maintenance, always test synchronization, bounce, travel, ug over-travel aron ensure optimal performance.

2. Failure to Trip (Trip Rejection)

2.1 Fault Symptoms

  • Remote control fails to trip the breaker.

  • Manual local tripping fails.

  • Relay protection operates during faults, but the breaker fails to trip.

2.2 Root Causes

  • Open circuit sa trip control loop.

  • Open trip coil.

  • Low operating voltage.

  • Increased trip coil resistance, reducing tripping force.

  • Deformed trip rod causing mechanical binding ug reduced force.

  • Severely deformed trip rod causing complete jamming.

2.3 Hazards
Trip failure during faults leads to over-level tripping, expanding the fault scope ug causing widespread outages.

2.4 Solutions

  • Check for open circuits sa trip control loop.

  • Inspect the trip coil for continuity.

  • Measure trip coil resistance for abnormalities.

  • Examine the trip rod for deformation.

  • Verify normal operating voltage.

  • Replace copper trip rods with steel ones aron prevent deformation.

2.5 Preventive Measures

  • Operators: Kon trip/close indicator lights are off, immediately check for open control circuits.

  • Maintenance staff: Sa outages, measure trip coil resistance ug inspect trip rod condition. Replace copper rods with steel.

  • Perform low-voltage trip/close tests aron ensure reliable operation.

3. Spring Mechanism – Charging Circuit Faults

3.1 Fault Symptoms

  • After closing, the breaker cannot trip (insufficient energy).

  • The storage motor runs continuously, risking overheating ug burnout.

3.2 Root Causes

  • Limit switch installed too low: Cuts motor power before spring is fully charged → insufficient energy for tripping.

  • Limit switch installed too high: Motor stays energized after full charge.

  • Faulty limit switch → motor fails to stop.

3.3 Hazards

  • Incomplete charging may cause trip failure during faults, leading to over-level tripping.

  • Motor burnout renders the breaker inoperable.

3.4 Solutions

  • Adjust limit switch position for accurate motor cutoff.

  • Replace damaged limit switches immediately.

3.5 Preventive Measures

  • Operators: Monitor the "spring charged" indicator during operation.

  • Maintenance: After servicing, perform two local trip/close operations to verify proper function.

4. Poor Synchronization & Excessive Contact Bounce

4.1 Fault Phenomenon
This is a hidden fault—only detectable via mechanical characteristic tests (e.g., timing analyzers).

4.2 Root Causes

  • Poor mechanical quality of the breaker body; repeated operations cause misalignment ug high bounce.

  • In separate-type breakers, long linkage rods cause uneven force transmission, increasing phase-to-phase timing differences ug bounce.

4.3 Hazards
High bounce or poor synchronization severely impacts fault current interruption, shortens lifespan, ug may cause explosions. Due to its hidden nature, this fault is especially dangerous.

4.4 Solutions

  • Adjust the length of the three-phase insulating pull rods to bring synchronization ug bounce within acceptable limits (while maintaining proper travel ug over-travel).

  • If adjustment fails, replace the faulty phase’s vacuum interrupter ug re-adjust.

4.5 Preventive Measures

  • Replace aging separate-type breakers with integrated (monobloc) designs to reduce failure risks.

  • During maintenance, always perform mechanical characteristic tests to detect ug resolve issues early.

Final Note: Environmental Protection

Never overlook environmental impacts. Ensure clean, dry, vibration-free, ug temperature-controlled conditions to guarantee safe ug reliable operation of vacuum circuit breakers.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Pangunahon nga Transformer Accidents ug Light Gas Operation Issues
1. Talaan sa Pagkamalasakit (Marso 19, 2019)Sa 16:13 sa Marso 19, 2019, ang background monitoring nagreport og light gas action sa No. 3 main transformer. Sumala sa Code for Operation of Power Transformers (DL/T572-2010), ang mga tawo sa operation and maintenance (O&M) nagsagol sa kondisyon sa No. 3 main transformer sa dapit.Konfirmasyon sa dapit: Ang WBH non-electrical protection panel sa No. 3 main transformer nagreport og Phase B light gas action sa transformer body, ug ang reset wala mae
02/05/2026
Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo