In-Depth Guide to Common Faults and Troubleshooting Methods for 10kV Vacuum Circuit Breakers

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Common Vacuum Circuit Breaker Faults and On-Site Troubleshooting by Electrical Engineers

As vacuum circuit breakers are widely used in the power industry, performance varies significantly among manufacturers. Some models offer excellent performance, require minimal maintenance, and ensure high power supply reliability. Others suffer from frequent issues, while a few have severe defects that may cause over-level tripping and large-scale blackouts. Let’s explore real-world fault handling by electrical engineers to gain practical experience and master comprehensive maintenance techniques.

1. Reduced Vacuum in Vacuum Interrupter

1.1 Fault Phenomenon
Vacuum circuit breakers interrupt current and extinguish arcs within the vacuum interrupter. However, most lack built-in qualitative or quantitative vacuum monitoring, making vacuum loss a hidden (latent) fault—far more dangerous than obvious failures.

1.2 Root Causes

  • Defects in the vacuum bottle’s material or manufacturing process, causing micro leaks.

  • Issues with the bellows material or fabrication, leading to leaks after repeated operations.

  • In separate-type VCBs (e.g., those with electromagnetic operating mechanisms), large linkage travel affects synchronization, bounce, and over-travel, accelerating vacuum degradation.

1.3 Hazards
Reduced vacuum severely impairs the breaker’s ability to interrupt fault currents, drastically shortens service life, and may lead to explosions.

1.4 Solutions

  • During scheduled outages, use a vacuum tester to perform qualitative vacuum checks and confirm adequate vacuum levels.

  • Replace the vacuum interrupter if vacuum loss is detected, and conduct travel, synchronization, and bounce tests afterward.

1.5 Preventive Measures

  • Choose vacuum breakers from reputable manufacturers with proven, mature designs.

  • Prefer integrated designs where the interrupter and operating mechanism are combined.

  • During patrols, check for external arcing on the vacuum bottle. If present, vacuum integrity is likely compromised—schedule immediate replacement.

  • During maintenance, always test synchronization, bounce, travel, and over-travel to ensure optimal performance.

2. Failure to Trip (Trip Rejection)

2.1 Fault Symptoms

  • Remote control fails to trip the breaker.

  • Manual local tripping fails.

  • Relay protection operates during faults, but the breaker fails to trip.

2.2 Root Causes

  • Open circuit in the trip control loop.

  • Open trip coil.

  • Low operating voltage.

  • Increased trip coil resistance, reducing tripping force.

  • Deformed trip rod causing mechanical binding and reduced force.

  • Severely deformed trip rod causing complete jamming.

2.3 Hazards
Trip failure during faults leads to over-level tripping, expanding the fault scope and causing widespread outages.

2.4 Solutions

  • Check for open circuits in the trip control loop.

  • Inspect the trip coil for continuity.

  • Measure trip coil resistance for abnormalities.

  • Examine the trip rod for deformation.

  • Verify normal operating voltage.

  • Replace copper trip rods with steel ones to prevent deformation.

2.5 Preventive Measures

  • Operators: If trip/close indicator lights are off, immediately check for open control circuits.

  • Maintenance staff: During outages, measure trip coil resistance and inspect trip rod condition. Replace copper rods with steel.

  • Perform low-voltage trip/close tests to ensure reliable operation.

3. Spring Mechanism – Charging Circuit Faults

3.1 Fault Symptoms

  • After closing, the breaker cannot trip (insufficient energy).

  • The storage motor runs continuously, risking overheating and burnout.

3.2 Root Causes

  • Limit switch installed too low: Cuts motor power before spring is fully charged → insufficient energy for tripping.

  • Limit switch installed too high: Motor stays energized after full charge.

  • Faulty limit switch → motor fails to stop.

3.3 Hazards

  • Incomplete charging may cause trip failure during faults, leading to over-level tripping.

  • Motor burnout renders the breaker inoperable.

3.4 Solutions

  • Adjust limit switch position for accurate motor cutoff.

  • Replace damaged limit switches immediately.

3.5 Preventive Measures

  • Operators: Monitor the "spring charged" indicator during operation.

  • Maintenance: After servicing, perform two local trip/close operations to verify proper function.

4. Poor Synchronization & Excessive Contact Bounce

4.1 Fault Phenomenon
This is a hidden fault—only detectable via mechanical characteristic tests (e.g., timing analyzers).

4.2 Root Causes

  • Poor mechanical quality of the breaker body; repeated operations cause misalignment and high bounce.

  • In separate-type breakers, long linkage rods cause uneven force transmission, increasing phase-to-phase timing differences and bounce.

4.3 Hazards
High bounce or poor synchronization severely impacts fault current interruption, shortens lifespan, and may cause explosions. Due to its hidden nature, this fault is especially dangerous.

4.4 Solutions

  • Adjust the length of the three-phase insulating pull rods to bring synchronization and bounce within acceptable limits (while maintaining proper travel and over-travel).

  • If adjustment fails, replace the faulty phase’s vacuum interrupter and re-adjust.

4.5 Preventive Measures

  • Replace aging separate-type breakers with integrated (monobloc) designs to reduce failure risks.

  • During maintenance, always perform mechanical characteristic tests to detect and resolve issues early.

Final Note: Environmental Protection

Never overlook environmental impacts. Ensure clean, dry, vibration-free, and temperature-controlled conditions to guarantee safe and reliable operation of vacuum circuit breakers.

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.