• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Pagsukod sa Capacitance gamit ang Schering Bridge nga gihimo pinaagi sa Schering Bridge

Electrical4u
Larangan: Basic Electrical Basikong Elektikal
0
China

Unsa ang Pagkuha sa Capacitance Gamit ang Schering Bridge

Teorya sa Schering Bridge

Ginagamit kini nga bridge aron sukolon ang capacitance sa capacitor, dissipation factor ug sukol sa relative permittivity. Konsidera nato ang circuit sa Schering bridge isip gihatag sa ubos:
Schering BridgeAnia, c1 mao ang unknown capacitance nga ang value kay gitukod pinaagi sa series electrical resistance r1.

c2 mao ang standard capacitor.
c4 mao ang variable capacitor.
r3 mao ang pure
resistor (i.e. non inductive in nature).
Og r4 mao ang variable non inductive resistor connected in parallel with variable
capacitor c4. Tuman-an ang supply sa bridge tali sa points a ug c. Ang detector mao ang gigamit tali sa b ug d. Gikan sa teorya sa ac bridges kita may balance condition,


Substituting the values of z1, z2, z3 and z4 in the above equation, we get

Equating the real and imaginary parts and the separating we get,

schering bridge

Konsidera nato ang phasor diagram sa uban na Shering bridge circuit ug marka ang voltage drops across ab,bc,cd and ad as e1, e3,e4 and e2 respectively. From the above Schering bridge phasor diagram, we can calculate the value of tanδ which is also called the dissipation factor.

The equation that we have derived above is quite simple and the dissipation factor can be calculated easily. Now we are going to discuss high voltage Schering Bridge in detail. As we have discussed that simple schering bridge (which uses low voltages) is used for measuring dissipation factor, capacitance and measurement of other properties of insulating materials like insulating oil etc. What is the need of high voltage schering bridge? The answer to this question is very simple, for the measurement of small capacitance we need to apply high voltage and high frequency as compare to low voltage which suffers many disadvantages. Let us discuss more features of this high voltage Schering Bridge:
schering bridge

  1. The bridge arms ab and ad consists of only capacitors as shown the bridge given below and impedances of these two arms are quite large as compared to the impedances of bc and cd. The arms bc and cd contains resistor r3 and parallel combination of capacitor c4 and resistor r4 respectively. As impedances of bc and cd are quite small therefore drop across bc and cd is small. The point c is earthed, so that the voltage across bc and dc are few volts above the point c.

  2. The high voltage supply is obtained from a transformer 50 Hz and the detector in this bridge is a vibration galvanometer.

  3. The impedances of arms ab and ad very are large therefore this circuit draws low current hence power loss is low but due to this low current we need a very sensitive detector to detect this low current.

  4. The fixed standard capacitor c2 has compressed gas which works as dielectric therefore dissipation factor can be taken as zero for compressed air. Earthed screens are placed between high and low arms of the bridge to prevent errors caused due to inter capacitance.

Let us study how Schering bridge measures relative permittivity: In order measure the relative permittivity, we need to first measure capacitance of a small capacitor with specimen as dielectric. And from this measured value of capacitance relative permittivity can calculated easily by using the very simple relation:

Where, r is relative permeability.
c is the capacitance with specimen as dielectric.
d is the spacing between the electrodes.
A is the net area of electrodes.
and ε is permittivity of free space.
There is another way to calculate relative permittivity of the specimen by changing electrode spacing. Let us consider diagram shown below
schering bridge
Here A is the area of electrode.
d is the thickness of the specimen.
t is the gap between the electrode and specimen (here this gap is filled by compressed gas or air).
cs is the capacitance of specimen.
co is capacitance due to spacing between electrode and specimen.
c is the effective combination of cs and co.

From figure above, as two capacitors are connected in series,

εo is permittivity of free space, εr is relative permittivity, when we remove specimen and the spacing readjusted to have same value of capacitance, the expression for capacitance reduces to

On equating (1) and (2), we will get the final expression for of εr as:

Statement: Respetar ang original, maayo nga mga artikulo nga wala'y bayad, kon may infraccion ayuson pag-delete.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Pangunahon nga Transformer Accidents ug Light Gas Operation Issues
1. Talaan sa Pagkamalasakit (Marso 19, 2019)Sa 16:13 sa Marso 19, 2019, ang background monitoring nagreport og light gas action sa No. 3 main transformer. Sumala sa Code for Operation of Power Transformers (DL/T572-2010), ang mga tawo sa operation and maintenance (O&M) nagsagol sa kondisyon sa No. 3 main transformer sa dapit.Konfirmasyon sa dapit: Ang WBH non-electrical protection panel sa No. 3 main transformer nagreport og Phase B light gas action sa transformer body, ug ang reset wala mae
02/05/2026
Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo