How to judge whether the temperature change of the transformer is normal or abnormal?

Vziman
Vziman
Field: Manufacturing
China

1. How to Judge Whether the Temperature Change of a Transformer is Normal or Abnormal

During operation, losses in the transformer’s core and windings are converted into heat, causing temperature rise in various parts. This heat is dissipated through radiation, conduction, and other means. When heat generation and dissipation reach equilibrium, the temperature of each part stabilizes. Iron losses remain nearly constant, while copper losses vary with load.

When inspecting a transformer, record the ambient temperature, top oil temperature, load, and oil level, and compare these values with historical data to assess whether the transformer is operating normally.

If, under the same operating conditions, the oil temperature is more than 10°C higher than usual, or if the load remains constant but the temperature continues to rise despite normal operation of the cooling system, an internal fault may be present (and the possibility of thermometer error or malfunction should be checked).

Typically, the main insulation of a transformer (winding insulation) is Class A (paper-based), with a maximum allowable operating temperature of 105°C. The winding temperature is generally 10–15°C higher than the top oil temperature. For example, if the top oil temperature is 85°C, the winding temperature may reach 95–100°C.

2. Causes of Abnormal Transformer Temperature

(1)Internal Faults Leading to Abnormal Temperature

Internal faults such as inter-turn or inter-layer short circuits, discharge from windings to nearby shielding, overheating at internal lead connections, multi-point grounding of the core causing increased eddy currents and overheating, or stray flux from zero-sequence unbalanced current forming a loop with the tank and generating heat—can all cause abnormal temperature rise. Such faults are often accompanied by operation of gas or differential protection. In severe cases, the explosion-proof pipe or pressure relief device may discharge oil. In such situations, the transformer should be taken out of service for inspection.

(2)Abnormal Temperature Due to Cooler Malfunction

Abnormal temperature may result from improper operation or failure of the cooling system, such as submersible pump shutdown, fan damage, fouling in cooling pipes, reduced cooling efficiency, or failure of radiator valves to open. Timely maintenance or flushing of the cooling system should be performed, or a backup cooler should be activated. Otherwise, the transformer load must be reduced.

(3)Temperature Indicator Errors
If the temperature indication is inaccurate or the instrument is malfunctioning, the thermometer should be replaced.

Give a tip and encourage the author!
Recommended
Complete Guide to Circuit Breaker Selection and Setting Calculation
Complete Guide to Circuit Breaker Selection and Setting Calculation
How to Select and Set Circuit Breakers1. Types of Circuit Breakers1.1 Air Circuit Breaker (ACB)Also known as a molded frame or universal circuit breaker, all components are mounted within an insulated metal frame. It is typically open-type, allowing easy replacement of contacts and parts, and can be equipped with various accessories. ACBs are commonly used as main power supply switches. Overcurrent trip units include electromagnetic, electronic, and intelligent types. They provide four-stage pro
Echo
10/28/2025
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
Basic Composition and Function of Circuit Breaker Failure ProtectionCircuit breaker failure protection refers to a protective scheme that operates when the relay protection of a faulty electrical device issues a trip command but the circuit breaker fails to operate. It uses the protection trip signal from the faulty equipment and the current measurement from the failed breaker to determine breaker failure. The protection can then isolate other relevant breakers within the same substation in a sh
Felix Spark
10/28/2025
 Electrical Room Power-On Safety Operation Guide
Electrical Room Power-On Safety Operation Guide
Power Supply Procedure for Low-Voltage Electrical RoomsI. Pre-Power-On Preparations Clean the electrical room thoroughly; remove all debris from switchgear and transformers, and secure all covers. Inspect busbars and cable connections inside transformers and switchgear; ensure all screws are tightened. Live parts must maintain adequate safety clearance from cabinet enclosures and between phases. Test all safety equipment before energizing; use only calibrated measuring instruments. Prepare fire-
Echo
10/28/2025
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
1 Key Points in Operation of High and Low Voltage Equipment1.1 High and Low Voltage EquipmentInspect insulating porcelain components for dirt, damage, or signs of electrical discharge. Check the exterior of low-voltage capacitor compensators for excessive temperature or bulging. If both conditions occur simultaneously, suspend installation work immediately. Examine wiring and terminal joints for oil leakage and conduct a thorough inspection for potential issues.Use auditory judgment to assess th
Felix Spark
10/28/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.