Casus Analyse Abnormalis Circuitus Secundarii in Transformatoribus Voltatis

Felix Spark
Campus: Defectus et Manutentio
China

1. Situatio Defectus

In mensis Septembris anno 2023, ut operarius frontalis in defectionibus reparationum, detexi tensionem anormalem in sectione I bus 10kV substationis dum vigilabam et notificavi team operationis et maintenance. Systema monitorii ostendit: U0 = 0 kV, Ua = 6.06 kV, Ub = 5.93 kV, Uc = 6.05 kV, Uab = 10.05 kV, Ubc = 5.94 kV

Ego et meus team properavimus ad locum. Suspectavimus circuitum interruptoris aeris secundarii transformatoris tensio-metri sectionis I bus 10kV clausum esse et fusum U-phasium fractum invenimus. Post disjunctionem huius interruptoris, circuitus interruptoris bus-sectionis 900 auto-activatus est, tripulans interruptorem 95A lateris 10kV primi transformatoris principali et inter-tripulans lineas 911–915, deinde claudens 900.

Post restituendo circuitum secundarium, inspectavimus corpus transformatoris tensio-metri et fusum (utrumque normale). Inspectando circuitum secundarium, inveni terminalem A660 laxum in armario. Stringendo eum restituitur tensio normalis in sectione I bus 10kV.

2. Analyse Causae

Section I bus 10kV habet 6 alimenta, 5 (911–915) connecta ad hydroelectricas minores. In plena generatione, currentus oneris lateris 10kV primi transformatoris principali descendit, elevans tensionem bus.

Operatores et maintenancii, confidentes in experientia, disjuncti sunt interruptorem aeris secundarii transformatoris tensio-metri sine analysi impactus in dispositivos protectionis. Tunc, cum currentus interruptoris 95A (≈48A) satisfacit conditioni sine-tensione/sine-currente backup automatici (valore secundario: 25V, 0.02A), activavit se backup automaticus, tripulans interruptorem 95A et inter-tripulans 5 alimenta hydroelectricarum minorum. Causa radicalis fuit non-exitus backup automatici durante tractatione abnormalis transformatoris tensio-metri, causans misoperationem.

3. Praesidia Preventiva

Transformatores tensio-metri capaciti variis habent defectibus, output tensionis secundariae anormalis interdum occurrens. Operatores et maintenancii frontales debent:

  • Strengthen department management, collect more data, and monitor alarms to detect abnormalities early.

  • Analyze danger points in voltage transformer handling, update on - site operation regulations. Before replacing fuses (or similar tasks), check the main transformer’s current and auto - backup settings. If the current is below the no - current threshold, follow procedures to exit auto - backup.

  • Regularly revise measures for “three - mistake” (mis - operation, mis - wiring, mis - setting) accidents, conduct training. Standardize emergency disposal processes to avoid improper actions.

  • Enhance on - site risk control; clearly label equipment at risk of misoperation.

Donum da et auctorem hortare

Suggestus

Caso studii et Recommendationes de Testu PD in Situ et Testu Inductivo Tolerantiae pro Transformatoribus 750kV
I. IntroductioDemonstratio projectus transmissionis et substationis 750kV inter Guanting et Lanzhou East in China officialem in operationem positum est die 26 septembris 2005. Hoc projectum duas substationes—Lanzhou East et Guanting (quae singula quatuor transformatores 750kV habent, tres quorum in operatione bancam triphasica formant, una in reserve)—et unam lineam transmissionis includit. Transformatores 750kV in hoc projecto in China independentiter developsi et manufacturati sunt. In testibu
10/31/2025
Fuga Hydraulica & Fuga Gas SF6 in Interruptoribus Circuitus
Fuga in Mechanismis Hydraulica OperativisIn mechanismis hydraulica, fuga potest causare frequentiam pumpae in brevi tempore vel tempus repressurizationis nimium longum. Fuga olei interna gravis in valvulis potest ad deficiens pressionis perducere. Si oleum hydraulicum in partem nitrogenii cylindri accumulantis intrat, potest ad pressionis augmentum anormale ducere, quod operationem securam circuitobrachiorum SF6 affectat.Praeter casus defectus aut abnormalitatis apparatorum deprehensionis pressi
10/25/2025
Cur Non Possit VT Comprimi & CT Aperi? Explicatum
Omnes scimus quod transformator tensionis (VT) numquam debet operari in circuitu clauso, dum transformator currentis (CT) numquam debet operari in circuitu aperto. Clausura circuitus VT vel apertura circuitus CT danificabit transformatorem aut creabit conditiones periculosas.Theoretice, et VTs et CTs sunt transformatores; differentia iacet in parametri quos mensurare sunt designati. Quam ob rem, quamvis sint fundamenta eiusdem generis instrumenti, unus prohibetur ab operatione in circuitu clauso
10/22/2025
Cur Sint Transformatores Voltus Exurere? Inveni Causas Reales
In circuitibus electricitatis, transformatores tensionis (VTs) saepe laeduntur aut exuruntur. Si causa radicalis non invenitur et tantum transformer reponitur, novus unitas potest cito iterum deficere, interpellans distributionem electricitatis ad usus. Propterea, sequentes inspectiones debent fieri ut causam defectus VT determinent: Si transformer tensionis rupit et residuum olei invenitur in laminis ferro-silicio, damnum fuit verisimile propter ferroresonantiam. Haec accidit quando voltages in
10/22/2025
Inquiry
+86
Click to upload file
Descarica
Obtine Applicatio Commerciale IEE-Business
Utiliza app IEE-Business ad inveniendum apparatus obtinendumque solutiones coniungendum cum peritis et participandum in collaboratione industriale ubique et semper propter totam supportionem tuorum projectorum electricitatis et negotiorum