Case Analysis of Abnormal Secondary Circuits in Voltage Transformers

07/02/2025

1. Fault Situation
In September 2023, as a front - line fault maintenance worker, I detected abnormal voltage on the 10kV Section I bus of a substation during monitoring duty and informed the operation and maintenance team. The monitoring system showed: U0 = 0 kV, Ua = 6.06 kV, Ub = 5.93 kV, Uc = 6.05 kV, Uab = 10.05 kV, Ubc = 5.94 kV
My team and I rushed to the site. We suspected the secondary air circuit breaker of the 10kV Section I bus voltage transformer was closed and found the U - phase fuse blown. After disconnecting this breaker, the 900 bus - sectioning circuit breaker auto - activated, tripping the 95A breaker on the No. 1 main transformer’s 10kV side and inter - tripping lines 911–915, then closing 900.
After restoring the secondary circuit, we checked the voltage transformer’s main body and fuse (both normal). Inspecting the secondary circuit, I found a loose A660 terminal in the cabinet. Tightening it restored normal voltage on the 10kV Section I bus.
2. Cause Analysis
The 10kV Section I bus has 6 feeders, 5 (911–915) connected to small hydropower. At full generation, the No. 1 main transformer’s 10kV side load current drops, raising bus voltage.
Operation and maintenance staff, relying on experience, disconnected the voltage transformer’s secondary air circuit breaker without analyzing impacts on protection devices. At this point, the 95A breaker’s current (≈48A) met the auto - backup’s no - voltage/current condition (secondary value: 25V, 0.02A). The auto - backup activated, tripping the 95A breaker and inter - tripping the 5 small - hydropower feeders. The root cause was failing to exit auto - backup during voltage transformer abnormal handling, causing misoperation.
3. Preventive Measures
Capacitive voltage transformers have various faults, with abnormal secondary voltage output being common. Front - line operation and maintenance staff should:
  • Strengthen department management, collect more data, and monitor alarms to detect abnormalities early.
  • Analyze danger points in voltage transformer handling, update on - site operation regulations. Before replacing fuses (or similar tasks), check the main transformer’s current and auto - backup settings. If the current is below the no - current threshold, follow procedures to exit auto - backup.
  • Regularly revise measures for “three - mistake” (mis - operation, mis - wiring, mis - setting) accidents, conduct training. Standardize emergency disposal processes to avoid improper actions.
  • Enhance on - site risk control; clearly label equipment at risk of misoperation.

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

Transformer Detection, Testing, Maintenance and Servicing
Transformer Detection, Testing, Maintenance and Servicing
Transformer testing, inspection, and maintenance are essential tasks to ensure normal operation and extend the service life of transformers. Below are some recommended steps:Visual Inspection: Regularly inspect the transformer's exterior, including the enclosure, cooling system, and oil tank. Ensure the enclosure is intact, free from corrosion, damage, or leakage.Insulation Resistance Testing: Use an insulation resistance tester to check the transformer's insulation system. Verify that the insul
Vziman
08/29/2025
What are the Common Operation Faults of Indoor Load Switches?
What are the Common Operation Faults of Indoor Load Switches?
Common operational faults of indoor load switches primarily concentrate on three core aspects: mechanical operation, electrical performance, insulation, and arc extinguishing. These issues can be broadly categorized as follows and are often related to component aging, environmental influences, or improper operation.1.Mechanical Faults The most typical issue is abnormal operation during opening and closing. This includes excessive resistance, jamming, or even refusal to operate when manually turn
08/27/2025
What should be done if the fuse element on the high-voltage side of the transformer melts?
What should be done if the fuse element on the high-voltage side of the transformer melts?
If the fuse element on the high-voltage side of the transformer blows or the circuit trips, the first step is to determine whether one phase, two phases, or all three phases are interrupted. This can be determined according to the fault symptoms as shown in the following table:When a fuse element blows, first check whether the high-voltage side fuse or the lightning arrester gap has short-circuited to ground. If no abnormalities are found during external inspection, it can be concluded that an i
08/26/2025
Usage and Maintenance of Fuses
Usage and Maintenance of Fuses
Use and MaintenanceIn low-voltage power distribution systems, fuses are protective electrical devices. Widely used for power grid and electrical equipment protection, fuses automatically cut off circuits when short circuits or overloads occur in the grid or equipment, preventing damage to electrical devices and preventing accidents from spreading.A fuse consists of an insulating base (or support), contacts, and a fuse element. The fuse element is the primary working component, acting like a spec
08/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!