Case Analysis of Abnormal Secondary Circuits in Voltage Transformers

Felix Spark
07/02/2025

1. Fault Situation
In September 2023, as a front - line fault maintenance worker, I detected abnormal voltage on the 10kV Section I bus of a substation during monitoring duty and informed the operation and maintenance team. The monitoring system showed: U0 = 0 kV, Ua = 6.06 kV, Ub = 5.93 kV, Uc = 6.05 kV, Uab = 10.05 kV, Ubc = 5.94 kV
My team and I rushed to the site. We suspected the secondary air circuit breaker of the 10kV Section I bus voltage transformer was closed and found the U - phase fuse blown. After disconnecting this breaker, the 900 bus - sectioning circuit breaker auto - activated, tripping the 95A breaker on the No. 1 main transformer’s 10kV side and inter - tripping lines 911–915, then closing 900.
After restoring the secondary circuit, we checked the voltage transformer’s main body and fuse (both normal). Inspecting the secondary circuit, I found a loose A660 terminal in the cabinet. Tightening it restored normal voltage on the 10kV Section I bus.
2. Cause Analysis
The 10kV Section I bus has 6 feeders, 5 (911–915) connected to small hydropower. At full generation, the No. 1 main transformer’s 10kV side load current drops, raising bus voltage.
Operation and maintenance staff, relying on experience, disconnected the voltage transformer’s secondary air circuit breaker without analyzing impacts on protection devices. At this point, the 95A breaker’s current (≈48A) met the auto - backup’s no - voltage/current condition (secondary value: 25V, 0.02A). The auto - backup activated, tripping the 95A breaker and inter - tripping the 5 small - hydropower feeders. The root cause was failing to exit auto - backup during voltage transformer abnormal handling, causing misoperation.
3. Preventive Measures
Capacitive voltage transformers have various faults, with abnormal secondary voltage output being common. Front - line operation and maintenance staff should:
  • Strengthen department management, collect more data, and monitor alarms to detect abnormalities early.
  • Analyze danger points in voltage transformer handling, update on - site operation regulations. Before replacing fuses (or similar tasks), check the main transformer’s current and auto - backup settings. If the current is below the no - current threshold, follow procedures to exit auto - backup.
  • Regularly revise measures for “three - mistake” (mis - operation, mis - wiring, mis - setting) accidents, conduct training. Standardize emergency disposal processes to avoid improper actions.
  • Enhance on - site risk control; clearly label equipment at risk of misoperation.
Felix Spark

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
1. Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In lo
Oliver Watts
07/16/2025
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage
Felix Spark
07/15/2025
What Are the Common Failures of AIS Voltage Transformers?
What Are the Common Failures of AIS Voltage Transformers?
Hey everyone! I’m Felix, a 10-year veteran in the power system industry. Today, we’re going to dive into an important topic — what are the common failures of Air Insulated Switchgear (AIS) voltage transformers? How do you identify these issues, and how can they be resolved? Let’s get started!1. Insulation DamageThe Problem You Might Encounter:One of the most frequent issues is insulation damage. This typically happens due to aging insulation materials, overvoltage surges,
Felix Spark
07/14/2025
Fault Analysis and Diagnosis on Current Transformer
Fault Analysis and Diagnosis on Current Transformer
Current transformers are numerous in substations and are key equipment to ensure the normal operation of the system. If a current transformer fails, it will cause the circuit breaker to trip and may even evolve into a power outage event, which will have an adverse impact on the safe and stable operation of the power grid. Taking an event of the main transformer differential protection operation caused by the failure of the current transformer on the low-voltage side of the main transformer in a
Felix Spark
07/14/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!