• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Solve Single-Phase Grounding Fault Judgment for 3-Phase 4PT in Ungrounded Systems?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage transformers, this paper analyzes single - phase grounding to improve remote measurement usability for staff, offering solutions based on field experience.

1 Analysis of Normal Operation and Single - Phase Grounding Faults in Ungrounded Systems
1.1 Voltage Transformer Principle During Normal Operation

For a 10 kV bus three - phase 4PT voltage transformer (wiring: Figure 1), UA, UB, UC(phase - to - ground voltages), UL (zero - sequence voltage); UAa, UBb, UCc (primary winding phase voltages); Ua, Ub, Uc (secondary winding phase voltages), 3U0 (zero - sequence voltage). All PT ratios:(10 kV/√3)/(57.74 V).

During normal operation, the primary three - phase and zero - sequence voltages are analyzed, as shown in Equation (1). From Equation (1), the secondary voltages are obtained as Ua= 57.74 V, Ub = 57.74V, Uc = 57.74V, and 3U0 = 0V, which are consistent with the secondary voltages of the voltage transformer with a three - phase open - delta connection.

1.2 Principle Analysis of PT in Single - Phase Grounding

When a phase - A grounding fault occurs, the primary side of the voltage transformer can be equivalently represented as shown in Figure 2. Among them, the primary windings of the three - phase PT are , the zero - sequence winding impedance is , and UA', UB', UC', UL' are the phase - to - ground voltages of the three phases and the zero - sequence voltage when a phase - A grounding fault occurs, respectively.

According to the superposition theorem, it can be obtained that

According to the characteristics of the three - phase 4PT voltage transformer, the impedance of the zero - sequence winding is much larger than that of the phase winding. Then the above formula can be simplified as shown in Formula (3).

When a phase - A grounding fault occurs, the phase - to - ground voltage of phase A is 0, and the voltages of phases B and C are 10 kV. Combined with Formula (3), the phasor diagram during the single - phase grounding fault can be obtained, as shown in Figure 3.

According to the phasor diagram analysis in Figure 3, Formula (4) can be obtained. Among them, UAa', UBb', and UCc' are the primary winding voltages of the bus after the phase - A grounding fault, respectively.UAa'= UA 10kV√3, UBb'= UB 10kV√3, UCc' =UC 10kV√3, UL'=UA = 10kV √3. Converting to the secondary side after the fault, we can get Ua' = 57.74V, Ub' = 57.74V, Uc' = 57.74V, and 3U0' = 57.74V.

From the above analysis, in an ungrounded system, when a single - phase grounding fault occurs, the voltages of the three phases ABC are all 57.74 V, which is consistent with the normal operation situation. Only the zero - sequence voltage rises to the phase voltage, which brings great confusion to monitoring and operation and maintenance personnel. It is very difficult to judge that it is a single - phase grounding fault. Moreover, because the fault current is too small for the protection to start the protection tripping, it brings hidden dangers to the safe and stable operation of the power grid.

2 Rectification Measures

To solve the problem that, for the voltage transformer with the three - phase 4PT wiring mode, when a single - phase grounding fault occurs, the uploaded three - phase voltage remote measurement is consistent with the normal operation situation, which brings certain confusion to monitoring and operation and maintenance personnel. This paper proposes to keep the wiring mode of the primary side voltage winding of the three - phase 4PT voltage transformer unchanged and change the wiring of the secondary winding, as shown in Figure 4.

Based on the principle analyzed in Section 1.2, we can derive: UA' = UL' + UAa' = 0V, UB' = UL' + UBb' = 10kV, UC' = UL' + UCc' = 10kV. That is, the secondary voltages after the fault are UA' = 0V, UB' = 100 kV, UC' = 100kV, and3U0' = 57.74kV. From the data analyzed above, for the improved three - phase 4PT voltage transformer, during a single - phase grounding fault, the three - phase voltages are consistent with those of a single - phase fault in a three - phase four - wire system, and the zero - sequence voltage also rises to the phase voltage.

Monitoring and operation and maintenance personnel can quickly determine that a single - phase grounding fault has occurred in the 10 kV system. Combined with the small - current grounding line selection device, the relevant fault line can be removed as soon as possible.

3 Conclusion

This paper proposes a secondary winding wiring method for the three - phase 4PT voltage transformer, which can upload three - phase voltage remote measurements with the same characteristics as those of a single - phase grounding fault in an ungrounded system to the monitoring system. Thus, it is more conducive for monitoring and operation and maintenance personnel to make quick judgments, prevent the fault from worsening further, and ensure the safe and stable operation of the power grid.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.