Case Analysis of Abnormal Secondary Circuits in Voltage Transformers

Felix Spark
Felix Spark
Field: Failure and maintenance
China

1. Fault Situation

In September 2023, as a front - line fault maintenance worker, I detected abnormal voltage on the 10kV Section I bus of a substation during monitoring duty and informed the operation and maintenance team. The monitoring system showed: U0 = 0 kV, Ua = 6.06 kV, Ub = 5.93 kV, Uc = 6.05 kV, Uab = 10.05 kV, Ubc = 5.94 kV

My team and I rushed to the site. We suspected the secondary air circuit breaker of the 10kV Section I bus voltage transformer was closed and found the U - phase fuse blown. After disconnecting this breaker, the 900 bus - sectioning circuit breaker auto - activated, tripping the 95A breaker on the No. 1 main transformer’s 10kV side and inter - tripping lines 911–915, then closing 900.

After restoring the secondary circuit, we checked the voltage transformer’s main body and fuse (both normal). Inspecting the secondary circuit, I found a loose A660 terminal in the cabinet. Tightening it restored normal voltage on the 10kV Section I bus.

2. Cause Analysis

The 10kV Section I bus has 6 feeders, 5 (911–915) connected to small hydropower. At full generation, the No. 1 main transformer’s 10kV side load current drops, raising bus voltage.

Operation and maintenance staff, relying on experience, disconnected the voltage transformer’s secondary air circuit breaker without analyzing impacts on protection devices. At this point, the 95A breaker’s current (≈48A) met the auto - backup’s no - voltage/current condition (secondary value: 25V, 0.02A). The auto - backup activated, tripping the 95A breaker and inter - tripping the 5 small - hydropower feeders. The root cause was failing to exit auto - backup during voltage transformer abnormal handling, causing misoperation.

3. Preventive Measures

Capacitive voltage transformers have various faults, with abnormal secondary voltage output being common. Front - line operation and maintenance staff should:

  • Strengthen department management, collect more data, and monitor alarms to detect abnormalities early.

  • Analyze danger points in voltage transformer handling, update on - site operation regulations. Before replacing fuses (or similar tasks), check the main transformer’s current and auto - backup settings. If the current is below the no - current threshold, follow procedures to exit auto - backup.

  • Regularly revise measures for “three - mistake” (mis - operation, mis - wiring, mis - setting) accidents, conduct training. Standardize emergency disposal processes to avoid improper actions.

  • Enhance on - site risk control; clearly label equipment at risk of misoperation.

Give a tip and encourage the author!
Recommended
Why Can't VT Be Shorted & CT Be Opened? Explained
Why Can't VT Be Shorted & CT Be Opened? Explained
We all know that a voltage transformer (VT) must never operate short-circuited, while a current transformer (CT) must never operate open-circuited. Short-circuiting a VT or opening the circuit of a CT will damage the transformer or create hazardous conditions.From a theoretical standpoint, both VTs and CTs are transformers; the difference lies in the parameters they are designed to measure. So why, despite being fundamentally the same type of device, is one prohibited from short-circuit operatio
Echo
10/22/2025
Why Are Voltage Transformers Burning Out? Find the Real Causes
Why Are Voltage Transformers Burning Out? Find the Real Causes
In power circuits, voltage transformers (VTs) are often damaged or burned out. If the root cause is not identified and only the transformer is replaced, the new unit may quickly fail again, disrupting power supply to users. Therefore, the following checks should be performed to determine the cause of VT failure: If the voltage transformer has ruptured and oil residue is found on the silicon steel laminations, the damage was likely caused by ferroresonance. This occurs when unbalanced voltages or
Felix Spark
10/22/2025
Things to Know When Operating Voltage Transformers: De-energizing and Energizing Procedures
Things to Know When Operating Voltage Transformers: De-energizing and Energizing Procedures
Q:What are the Operating Sequence Rules for the Secondary Miniature Circuit Breaker and High-Voltage Power Supply During Voltage Transformer De-energizing and Energizing?A:For busbar voltage transformers, the principle for operating the secondary miniature circuit breaker during de-energizing and energizing is as follows: De-energizing:First, open the secondary miniature circuit breaker, then disconnect the high-voltage power supply of the voltage transformer (VT). Energizing:First, energize the
Echo
10/22/2025
How to Operate & Maintain Voltage Transformers Safely?
How to Operate & Maintain Voltage Transformers Safely?
I. Normal Operation of Voltage Transformers A voltage transformer (VT) may operate long-term at its rated capacity, but under no circumstances should it exceed its maximum capacity. The secondary winding of a VT supplies high-impedance instruments, resulting in a very small secondary current, nearly equal to the magnetizing current. The voltage drops across the leakage impedances of both primary and secondary windings are therefore very small, meaning the VT operates close to no-load under norma
Edwiin
10/22/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.