The 10kV outdoor circuit breaker burned out and the energy storage motor malfunctioned

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Fault Description

In a certain place, the ZWG - 12 type outdoor vacuum circuit breaker is used for the 10kV circuit breaker. On September 29, 2015, when the circuit breaker in the 172 Zhakou Line interval was to be closed remotely, it was found that the remote closing operation failed. When the operating personnel arrived at the site and inspected, they found scattered iron filings on the ground directly beneath the circuit breaker. After manually energizing the circuit breaker, they operated it and found that the manual opening and closing functions were intact, but the circuit breaker could not complete the electric energy - storage operation. The equipment operation and maintenance personnel promptly reported the defect to the maintenance department. After the maintenance personnel opened the cover plate of the circuit breaker, they found a small pile of iron filings accumulated at the bottom of the circuit breaker mechanism box, and the energy - storage gear of the switch mechanism was severely worn.

 

Cause Analysis

Based on the fault phenomenon that the motor couldn't perform electric energy storage, the maintenance personnel initially suspected a fault in the motor power supply. However, through measurement, this assumption was ruled out. Considering the worn - out energy - storage mechanism at the scene, the maintenance personnel determined that the energy - storage motor had burned out. The measured resistance of the motor winding circuit at the scene was 247 MΩ, confirming the motor burnout.

Regarding the reasons for the motor burnout, generally, there are two possible situations: mechanical faults and electrical faults. A mechanical fault mainly refers to the jamming of the circuit breaker's energy - storage mechanism. This causes the motor to stall during the energy - storage process, leading to motor burnout. In the power system, some circuit breakers are rarely subjected to power - outage operations due to high - level loads. As a result, the mechanisms remain stationary for a long time. Rust and dust accumulation can cause severe jamming of the mechanism. When it reaches a certain degree, the output torque of the energy - storage motor cannot overcome the mechanism's resistance, resulting in motor burnout.

An electrical fault mainly occurs in the motor circuit. When the energy storage is completed, the micro - switch connected in series in the energy - storage circuit fails to disconnect in time. The motor keeps running, but due to the obstruction of the energy - storage holding pawl, the motor stalls and burns out due to overheating.

Fault Handling

The maintenance personnel first removed the motor from the standby interval circuit breaker and replaced the burned - out motor. Subsequently, they manually energized the spring. After the energy - storage process, they measured the micro - switch, and the measurement showed that the micro - switch contacts were in the open state, indicating normal function. When performing the opening and closing operations, they found that there was no jamming in the circuit breaker's energy - storage mechanism.

The maintenance personnel then closed the circuit breaker and carried out electric energy storage. During the energy - storage process, they found that the spring completed energy storage, but the motor kept running. To prevent the motor from burning out again, the maintenance personnel immediately opened the circuit breaker. With the spring energized, they repeatedly tested the on - off state of the micro - switch. The test results showed that regardless of the state of the micro - switch, the motor circuit remained connected. Further inspection of the circuit ruled out the possibility of a parasitic circuit.

When performing electric energy storage again, the maintenance personnel gently pressed the micro - switch with a screwdriver, and the motor stopped running. Based on this, they determined that the micro - switch was damaged. The maintenance personnel replaced it with a new original - factory micro - switch. When the motor was used for energy storage for the first time after the replacement, the motor kept running again when the spring completed energy storage. The maintenance personnel loosened the two fixing screws of the micro - switch, moved the limit switch as close as possible to the gear that presses it, and then fixed it. After that, the electric energy - storage operation returned to normal.

Combining the handling process, the maintenance personnel reached the following fault conclusion: When the spring completed energy storage, due to the small installation margin of the micro - switch itself and the severe wear of the micro - switch compression head, the stroke of the energy - storage mechanism compressing the micro - switch was reduced. The micro - switch was in a critical "virtual open" state. When the circuit breaker was closed, the 220 V AC current broke down the air between the virtual open points of the contacts, connecting the energy - storage circuit, and the motor kept running. When using the resistance gear of a multimeter to measure after opening the circuit breaker, the battery voltage of the multimeter was relatively low and not enough to break down the gap. Therefore, the measurement showed that the micro - switch was in the open state.

 Countermeasures and Suggestions

For this type of fault, it is recommended to strengthen the inspection of this type of outdoor circuit breaker and replace the severely worn micro - switches as soon as possible to avoid motor - burnout accidents. Currently, the design of outdoor circuit breakers lacks a mechanism to connect the energy - storage timeout signal, and there is a lack of monitoring for abnormal energy - storage situations. It is suggested that when conditions permit, the energy - storage timeout signal should be connected to the background alarm system.

Give a tip and encourage the author!
Recommended
A Guide to the Latest Transformer Testing Technologies
A Guide to the Latest Transformer Testing Technologies
Transformers come in many types, primarily oil-immersed and dry-type. Their fault manifestations are diverse, but most failures are concentrated in the windings, core, connecting components, and oil contamination. For example, winding insulation damage, open circuits, short circuits, and inter-turn short circuits at connection points. Common external symptoms of transformer faults include severe overheating, excessive temperature rise, abnormal noise, and three-phase imbalance.Routine transforme
Oliver Watts
10/20/2025
Inspection of transformers can be performed without any detection tools.
Inspection of transformers can be performed without any detection tools.
Transformers are electrical devices that change voltage and current based on the principle of electromagnetic induction. In power transmission and distribution systems, transformers are essential for stepping up or stepping down voltages to reduce energy losses during transmission. For example, industrial facilities typically receive power at 10 kV, which is then stepped down to low voltage via transformers for on-site use. Today, let’s learn about several common transformer inspection methods.1
Oliver Watts
10/20/2025
Vacuum Circuit Breakers for Capacitor Bank Switching
Vacuum Circuit Breakers for Capacitor Bank Switching
Reactive Power Compensation and Capacitor Switching in Power SystemsReactive power compensation is an effective means to increase system operating voltage, reduce network losses, and improve system stability.Conventional Loads in Power Systems (Impedance Types): Resistance Inductive reactance Capacitive reactanceInrush Current During Capacitor EnergizationIn power system operation, capacitors are switched in to improve power factor. At the moment of closing, a large inrush current is generated.
Oliver Watts
10/18/2025
Vacuum Circuit Breaker Withstand Voltage Test Guide
Vacuum Circuit Breaker Withstand Voltage Test Guide
Insulation Withstand Voltage Test Standards for Vacuum Circuit BreakersThe main purpose of the insulation withstand voltage test for vacuum circuit breakers is to verify whether the insulation performance of the equipment under high voltage is qualified, and to prevent breakdown or flashover accidents during operation. The test process must be strictly carried out in accordance with power industry standards to ensure equipment safety and power supply reliability.Test ObjectsThe test objects incl
Garca
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.