Ang 10kV outdoor circuit breaker nagkaroon ng pagkasira ug ang energy storage motor nagsayop nga gumana

Felix Spark
Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

Deskripsyon sa Sayop

Sa usa ka lugar, ang tipo nga ZWG - 12 outdoor vacuum circuit breaker ang gisagol alang sa 10kV circuit breaker. Sa Setyembre 29, 2015, kini nga circuit breaker sa 172 Zhakou Line interval wala ma-remote close. Ang mga operator nga mibisita sa dapit nakatubod og scattered iron filings sa yuta direkta sa ilalum sa circuit breaker. Pagkahuman og manual energizing sa circuit breaker, ang operasyon nia gibantog nga ang manual opening ug closing functions kay intact, pero ang circuit breaker dili makompleto sa electric energy-storage operation. Ang mga opisyal sa pag-operate ug maintenance adunay report sa defect sa departamento sa maintenance. Pagkahuman ang mga maintenance personnel mopasabot sa cover plate sa circuit breaker, nakatubod sila og small pile og iron filings nag-accumulate sa ilalum sa mechanism box sa circuit breaker, ug ang energy-storage gear sa switch mechanism adunay severe wear.

 

Analisis sa Kasinatian

Batasan sa sayop nga ang motor wala makahimo og electric energy storage, ang mga maintenance personnel nagsuspect sa unang paagi nga may problema sa power supply sa motor. Apan pinaagi sa measurement, kini nga asumption gi-dismiss. Pinaagi sa observed worn-out energy-storage mechanism sa dapit, ang mga maintenance personnel naghatag ug desisyon nga ang energy-storage motor adunay burnout. Ang measured resistance sa motor winding circuit sa dapit adunay 247 MΩ, konfirmado ang motor burnout.

Ang mga rason sa motor burnout, kasagaran duha ang posible nga sitwasyon: mechanical faults ug electrical faults. Ang mechanical fault main refers to ang jamming sa circuit breaker's energy-storage mechanism. Kini mosulti nga ang motor mag-stall sa duration sa energy-storage process, resulta ang motor burnout. Sa power system, ang uban nga mga circuit breakers rare kaayo mogawas sa power-outage operations tungod sa high-level loads. Kaymao, ang mechanisms mag-stay stationary og dugay. Ang rust ug dust accumulation makapadako og severe jamming sa mechanism. Kapag naabot sa certain degree, ang output torque sa energy-storage motor dili makapalihok sa mechanism, resulta ang motor burnout.

Ang electrical fault main occurs sa motor circuit. Kapag natapos ang energy storage, ang micro-switch connected in series sa energy-storage circuit wala ma-disconnect on time. Ang motor magpadayon og run, apan tungod sa obstruction sa energy-storage holding pawl, ang motor mag-stall ug burnout tungod sa overheating.

Paghunahuna sa Sayop

Ang mga maintenance personnel unang nagremove sa motor gikan sa standby interval circuit breaker ug nareplace ang burned-out motor. Subsequently, sila manual energize sa spring. Pagkahuman sa energy-storage process, sila measure sa micro-switch, ug ang measurement nagpakita nga ang contacts sa micro-switch open, indicating normal function. Sa pag-operate sa opening ug closing, wala sila makatubod og jamming sa circuit breaker's energy-storage mechanism.

Pagkahuman, ang mga maintenance personnel nag-close sa circuit breaker ug naggamit og electric energy storage. Sa duration sa energy-storage, sila makatubod nga ang spring nakahimo og energy storage, apan ang motor padayon og run. Para i-prevent ang motor burnout, ang mga maintenance personnel immediate nag-open sa circuit breaker. Pinaagi sa spring energized, sila repeated test sa on-off state sa micro-switch. Ang resulta nagpakita nga regardless sa state sa micro-switch, ang motor circuit remain connected. Further inspection sa circuit ruled out ang possibility sa parasitic circuit.

Sa pag-operate sa electric energy storage usab, ang mga maintenance personnel gently press sa micro-switch pinaagi sa screwdriver, ug ang motor stop running. Based sa kini, sila determine nga ang micro-switch damaged. Ang mga maintenance personnel nareplace niini pinaagi sa new original-factory micro-switch. Sa first time use sa motor after replacement, ang motor padayon og run when the spring completed energy storage. Ang mga maintenance personnel loosen ang two fixing screws sa micro-switch, move ang limit switch as close as possible sa gear nga mopress, ug fixed. After, ang electric energy-storage operation back to normal.

Combining ang handling process, ang mga maintenance personnel reach sa following fault conclusion: When the spring completed energy storage, due to the small installation margin of the micro-switch itself and the severe wear of the micro-switch compression head, the stroke of the energy-storage mechanism compressing the micro-switch was reduced. The micro-switch was in a critical "virtual open" state. When the circuit breaker was closed, the 220 V AC current broke down the air between the virtual open points of the contacts, connecting the energy-storage circuit, and the motor kept running. When using the resistance gear of a multimeter to measure after opening the circuit breaker, the battery voltage of the multimeter was relatively low and not enough to break down the gap. Therefore, the measurement showed that the micro-switch was in the open state.

Countermeasures ug Suggestions

Para sa karon nga klase sa sayop, recommended ang strengthen sa inspection sa karon nga klase sa outdoor circuit breaker ug replace ang severely worn micro-switches as soon as possible para i-prevent ang motor-burnout accidents. Currently, ang design sa outdoor circuit breakers lack mechanism to connect the energy-storage timeout signal, ug lack monitoring sa abnormal energy-storage situations. Suggested nga if conditions permit, ang energy-storage timeout signal must be connected to the background alarm system.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Ang inspeksyon sa mga transformer mahimo ang gihapon bisan walay mga kasangkapan alang sa pagdetece.
Ang inspeksyon sa mga transformer mahimo ang gihapon bisan walay mga kasangkapan alang sa pagdetece.
Ang mga transformers mao ang mga electrical devices nga nag-usab sa voltage ug current batas sa principle sa electromagnetic induction. Sa power transmission ug distribution systems, importante kaayo ang mga transformers aron mopataas o mobaba ang mga voltages aron mapangita ang energy losses sa panahon sa transmission. Tumong, ang mga industrial facilities kasagaran mogawas og power sa 10 kV, nga usab mobaba sa low voltage pinaagi sa transformers alang sa on-site use. Karon, atong pagbatasan an
Oliver Watts
10/20/2025
Pagsulay sa Vacuum Circuit Breakers alang sa Capacitor Bank
Pagsulay sa Vacuum Circuit Breakers alang sa Capacitor Bank
Pagkompensar sa Reactive Power ug Pagpaila ngadto sa Capacitor sa mga System sa PowerAng pagkompensar sa reactive power usa ka epektibong paagi aron mapataas ang sistema nga operasyon voltage, mapabag-o ang network losses, ug mapahimulos ang stability sa sistema.Ang Konbensional nga Mga Load sa mga System sa Power (Impedance Types): Resistance Inductive reactance Capacitive reactanceInrush Current Sa Panahon sa Energization sa CapacitorSa operasyon sa sistema sa power, ang mga capacitor gi-switc
Oliver Watts
10/18/2025
Pahimong Guide sa Pagsusi sa Voltage ng Vacuum Circuit Breaker
Pahimong Guide sa Pagsusi sa Voltage ng Vacuum Circuit Breaker
Pangutana sa Voltage sa Insulation sa Vacuum Circuit BreakersAng pangunahon nga butang sa insulation voltage test sa vacuum circuit breakers mao ang pag-verify kung ang insulation performance sa equipment sa dako nga voltage maoy qualified, ug ang pag-prevent sa breakdown o flashover accidents sa panahon sa operasyon. Ang proseso sa test dili bayad mahimong gihatagan og importansya batasan sa power industry aron masiguro ang seguridad sa equipment ug reliability sa power supply.Test ObjectsAng m
Garca
10/18/2025
Paunsa ang Bango sa Vacuum sa mga Vacuum Circuit Breakers
Paunsa ang Bango sa Vacuum sa mga Vacuum Circuit Breakers
Pagsusi sa Integrity sa Vacuum sa mga Circuit Breakers: Isang Kritikal nga Medida alang sa Evaluation sa PerformanceAng pagsusi sa integrity sa vacuum usa ka pangunahon nga paagi alang sa pag-ila sa performance sa vacuum sa mga circuit breakers. Kini nga test mahimong maayo nga i-evaluate ang insulating ug arc-quenching capabilities sa breaker.Bago ang pag-test, siguraduhon nga ang circuit breaker naka-install ug naka-connect sa husto. Ang mga common nga paagi sa pagsukat sa vacuum mao ang high-
Oliver Watts
10/16/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo