What are the causes of failures in low-voltage switchgear circuit breakers themselves?

Felix Spark
Field: Failure and maintenance
China

Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.

1.Failure of Operation Mechanism

Failure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and rapidly isolate power system faults, delayed or unintended operation poses a serious threat to the power grid, primarily in the following ways:

  • Expanding the scope of the fault—what was originally a single-circuit fault may escalate to affect the entire busbar, or even cause a complete substation or plant blackout;

  • Prolonging fault clearance time, which affects system stability and exacerbates damage to controlled equipment;

  • Causing unbalanced (non-full-phase) operation, which often leads to abnormal operation of protective relays and system oscillations, easily escalating into a system-wide or large-scale blackout.

The main causes of operation mechanism failure include:

  • Defects in the operating mechanism;

  • Mechanical defects in the circuit breaker itself;

  • Defects in the operation (control) system.

2.Insulation Accidents

Circuit breaker insulation accidents can be divided into internal insulation accidents and external insulation accidents. Internal insulation accidents generally cause more severe consequences than external ones.

2.1 Internal Insulation Accidents

Mainly involve bushings and current-related incidents. The primary cause is moisture ingress due to water penetration; secondary causes include oil deterioration and insufficient oil level.

2.2 External Insulation Accidents

Primarily caused by pollution flashover and lightning strikes, leading to flashover or explosion of the circuit breaker. The main reason for pollution flashover is that the creepage distance of porcelain insulators is too short for use in polluted areas; secondly, oil leakage from the circuit breaker allows dirt to accumulate easily on the porcelain skirts, triggering flashover.

Circuit breaker Failures.jpg


3. Breaking and Closing Performance Failures

Breaking and closing operations represent the most severe test for a circuit breaker. The vast majority of breaking and closing failures are primarily due to obvious mechanical defects in the circuit breaker; secondarily due to insufficient oil or oil not meeting required specifications. Some cases are also attributed to inadequate interrupting capacity of the circuit breaker. However, the former is more common, as a considerable number of failures occur even during switching of small loads or normal load currents.

4. Poor Conductivity Failures

Analysis of field accident statistics shows that poor conductivity failures are mainly caused by mechanical defects, including:

  • Poor contact—such as unclean contact surfaces, insufficient contact area, or inadequate contact pressure;

  • Detachment or jamming—for example, detachment of copper-tungsten contacts;

  • Loose screws at contact points;

  • Broken flexible connectors.

Give a tip and encourage the author!

Recommended

Rockwill Passes Single-Phase Ground Fault Test for Smart Feeder Terminal
Rockwill Electric Co., Ltd. has successfully passed the real-scenario single-phase-to-ground fault test conducted by the Wenzhou of China Electric Power Research Institute for its DA-F200-302 hood-type feeder terminal and integrated primary-secondary pole-mounted circuit breakers—ZW20-12/T630-20 and ZW68-12/T630-20—receiving an official qualified test report. This achievement marks Rockwill Electric as a leader in single-phase ground fault detection technology within distribution networks.The DA
12/25/2025
Overview of Defect Diagnosis Methods for High-Voltage AC Circuit Breakers
1. What are the characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms? How to extract these characteristic parameters from the original trip coil current signal?Answer: The characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms may include the following: Steady-state peak current: The maximum steady-state current value in the electromagnet coil waveform, representing the position where the
12/16/2025
A Brief Discussion on the Issues of Converting Reclosers into Outdoor Vacuum Circuit Breakers for Use
The rural power grid transformation plays an important role in reducing rural electricity tariffs and accelerating rural economic development. Recently, the author participated in the design of several small-scale rural power grid transformation projects or conventional substations. In rural power grid substations, conventional 10kV systems mostly adopt 10kV outdoor auto circuit vacuum reclosers.To save investment, we adopted a scheme in the transformation that removes the control unit of the 10
12/12/2025
A Brief Analysis of Automatic Circuit Recloser in Distribution Feeder Automation
An Automatic Circuit Recloser is a high-voltage switching device with built-in control (it inherently possesses fault current detection, operation sequence control, and execution functions without requiring additional relay protection or operating devices) and protective capabilities. It can automatically detect the current and voltage in its circuit, automatically interrupt fault currents according to inverse-time protection characteristics during faults, and perform multiple reclosures accordi
12/12/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.