Unsa ang Motor Protection Relay

Ang mas daghan sa 90% sa mga motor nga gigamit sa industriya mao ang induction motors, tungod kay sila murahon, robust ug dali ra maintanha. Para sa mas taas na HP (>250HP) motors, pipila mi gipili ang mataas na voltage, tungod kay makakurta kini sa operating current ug ang gidak-on sa motor.

Bakit Kita Nanginahanglan Ug Proteksyon Sa Motors?

Para maunawaan kini, kita nanginahanglan mag-alam sa cost nga adunay kasagaran sa pagkabuto sa motor, i.e.

  • Pagkawala sa produksyon (Cost of production)

  • Pagsulay sa motor (Replacement cost)

  • Cost of repair

  • Cost of man hours tungod niining emergency

Ang basic function sa protective relay mao ang pag-identify sa fault ug pag-isolate sa faulty part gikan sa healthy part sa system. Kini makapadako sa reliability sa power system.
Para sa protection of motor, kita nanginahanglan mag-identify sa iba't ibang causes sa pagkabuto ug pag-address sa sama. Ang iba't ibang causes sa pagkabuto mao ang sumala

  • Thermal stress on winding

  • Single phasing

  • Earth fault

  • Short circuit

  • Locked rotor

  • Number of hot starts

  • Bearing failure

Brief descriptions of the different failures are given below:

  • Thermal Stress on Winding –
    Kini mahimong mobuto kung ang motor nag-operate labi sa iyang rated capacity, maka-overheat kini ang winding ug insulation. Subsequently deteriorate ang winding insulation resulting in failure of motor. Kung ang
    voltage less than the designed value, maka-overheat usab ang winding at rated load ug mokabuto ang motor.

  • Single Phasing –
    Loss of one phase supplied to the motor (in case of
    3-phase motor) leads to single phasing. If we start the motor on load, then the motor will fail due to imbalance.

  • Earth Fault –
    If any part of winding comes in contact with the ground then we can say the motor is earthed. If we start the motor then it will lead to failure of motor.

  • Short Circuit –
    If there is a contact between two phases of a three phase winding or between the turns of a phase, and then this will be termed as short circuit.

  • Locked Rotor –
    If the driven equipment is in jammed condition or the motor shaft is jammed, then this is known as locked rotor. If we start the motor then it will fail.

  • Number of Hot Start –
    Each motor is designed to withstand a certain number of hot starts. Consider a motor is in running condition, if we stop the motor and immediately start the same, then this is called as a hot start. Depending upon the thermal curve of a motor we have to give certain time to bring down the temperature of winding.

  • Bearing Failure –
    If bearing fails then rubbing of rotor on stator will occur, resulting physical damage of insulation and winding. The bearing failure can be avoided by monitoring the bearing temperature. Bearing temperature detector (BTD) is used for monitoring and tripping of motor in case of abnormality.

All motor protection relays operate on the basis of current taken by the motor. Motor protection relay is used for high voltage area having the following features

  • Thermal overload protection

  • Short circuit protection

  • Single phasing protection

  • Earth fault protection

  • Locked rotor protection

  • Number of start protection

For setting of the relay we require the CT ratio and full load current of the motor. The setting of different element is listed below

  • Thermal over Load Element –
    To set this element we have to identify the % of Full load current on which the motor is running continuously.

  • Short circuit Element –
    The range available for this element is 1 to 5 times of starting current. Time delay is also available. We normally set it at 2 times of starting current with a time delay of 0.1 second.

  • Single Phasing Element –
    This element will operate, if there is an unbalance in current of three phases. It is also called as unbalance protection. The element is set for 1/3rd of starting current. If it tripped during starting, then the parameter will changed to 1/2 of starting current.

  • Earth Fault Protection –
    This element measures the neutral current of star connected CT secondary. The range available for this element is 0.02 to 2 times of CT primary current. Time delay is also available. We normally set at 0.1 times of CT primary current with a time delay of 0.2 seconds. If tripped during starting of motor, then the time setting can be raised to 0.5 sec.

  • Locked rotor protection –
    The range available for this element is 1 to 5 times of full load current. Time delay is also available. We normally set at 2 times of FLC (Full Load Current). The time delay will be more than the starting time of the motor. “Starting time means the time require by the motor to reach its full speed.”

  • Number of hot start protection –
    Here we will provide the number of start allowed in specified time duration. By this we will limit the number of hot starts given to the motor.

The schematic diagram to connect a motor protection relay is as below

Modern digital motor protection relays are having some extra features, i.e. protection against no load running of a motor and thermal protection.
In case of no load running, the relay senses the motor current. If it is less than the specified value then it will trip the motor. We can also connect the temperature probe to the relay, which will monitor the bearing and winding temperature and trip the motor if it exceeds the specified value of temperature.

Statement: Respetar ang original, maayo ang articles na worth sharing, kon adunay infringement please contact delete.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Unsa ang mga Tipo sa Reactors? Key Roles sa mga Power Systems
Unsa ang mga Tipo sa Reactors? Key Roles sa mga Power Systems
Reactor (Inductor): Pahayag ug mga UriAng reactor, gikataas usab og inductor, mao ang nag-generate og magnetic field sa kalibutan sa palibot samtang adunay kasinatong nga nag-usbong sa usa ka conductor. Busa, anang tanang conductor nga adunay kasinatong natural nga adunay inductance. Apan, ang inductance sa usa ka straight conductor gamay ra ug nag-produce og dili matibay nga magnetic field. Ang praktikal nga reactors gibuo sa pag-winding sa conductor sa usa ka solenoid shape, gikataas usab og a
James
10/23/2025
35kV Distribusyon Line Single-Phase Ground Fault Handling
35kV Distribusyon Line Single-Phase Ground Fault Handling
Distribution Lines: A Key Component of Power SystemsAng mga distribution lines usa ka importante nga komponente sa mga power systems. Sa parehas nga voltage-level busbar, gikonekta ang daghang distribution lines (para sa input o output), kung diin adunay daghang branches nga gisulayan radially ug gikonekta sa mga distribution transformers. Human sa pag-step down sa low voltage niining mga transformers, gigibit og kuryente sa daghang end users. Sa sulod niining mga distribution networks, mahimong
Encyclopedia
10/23/2025
Pagsulay Online alang sa Surge Arresters Ubos sa 110kV: Safe ug Efficient
Pagsulay Online alang sa Surge Arresters Ubos sa 110kV: Safe ug Efficient
Isa-ka nga Metodo sa Online Testing alang sa Surge Arresters sa 110kV ug Mas BajoSa mga sistema sa kuryente, ang surge arresters mao ang mga importante nga komponente nga nagprotekta sa mga equipment gikan sa overvoltage sa lightning. Alang sa mga pag-install sa 110kV ug mas bajo—tulad sa 35kV o 10kV substations—ang usa ka online testing method mahimong makapahimulos sa economic losses nga gikasabot sa power outages. Ang core niining metodo mao ang paggamit sa online monitoring technology aron m
Oliver Watts
10/23/2025
Unsa ang Teknolohiya sa MVDC? Benepisyo, Hamubo & Mga Futuro nga Tendensya
Unsa ang Teknolohiya sa MVDC? Benepisyo, Hamubo & Mga Futuro nga Tendensya
Ang teknolohiya sa medium-voltage direct current (MVDC) usa ka pangunahan nga pagbag-o sa pagpahibalo sa kuryente, gihimo aron mubag-o sa mga limitasyon sa tradisyonal nga sistema sa AC sa pipila ka aplikasyon. Tungod sa pagpahibalo sa elektrisidad pinaagi sa DC sa mga voltaje nga kasagaran nangadako gikan sa 1.5 kV hangtod sa 50 kV, gitugotan kini ang mga buluhaton sa long-distance transmission sa high-voltage DC sama sa flexibility sa low-voltage DC distribution. Sa konteksto sa pag-integro sa
Echo
10/23/2025
Mga Produktong Nakarrelasyon
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo