Pagsusi sa usa ka Pagkunhod sa VS1 Vacuum Circuit Breaker

Felix Spark
Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

Paghahatag sa VS1 Indoor High - Voltage Vacuum Circuit Breaker Fault Analysis ug Improvement Measures

Ang VS1 indoor high - voltage vacuum circuit breaker mao ang usa ka indoor switching device nga gigamit sa 12 kV power systems. Tungod sa iyang excellent performance, lisud kini gamiton sa mga lugar nga nanginahanglan og paborito nga pagoperasyon sa rated working current o multiple interruptions sa short - circuit current. Ang operating mechanism sa VS1 indoor high - voltage vacuum circuit breaker integrated sa circuit breaker body.

Kini mahimong gamiton dili lamang aron makabuo og trolley unit uban ang special propulsion mechanism apan usab isip fixed - installation unit. Gihapon, ang fixed - type circuit breaker mahimo nga mapataas ang reliability sa mechanical interlock. Kini nga paper nag - analyze sa usa ka burning - out fault sa VS1 vacuum circuit breaker ug nagproposa og improvement measures sa material selection, installation, operation, ug maintenance para sa reference.

1. Sitwasyon sa Fault

Sa Abril 2024, ang No. 224 circuit breaker (VS1 vacuum circuit breaker) sa X - capacitor bank sa 220 kV substation naputok tungod sa fault. Human sa inspeksyon sa on - site operating personnel, natukod nga ang moving ug static contacts ug ang contact arms sa phase W sa circuit breaker adunay severe burned out ug dili na mahimo mog balik sa operasyon. Gi report ang sitwasyon immediate. Human sa pagdako sa maintenance personnel sa site, pinaagi sa approval sa dispatching department, gisulay ang No. 224 circuit breaker ug ang 10 kV busbar.

Sa 13:00 sa parehas nga adlaw, gipildi ang accident emergency repair order alang sa defect handling. Ang maintenance personnel giinspeksyon ang relevant parts sa accident switch sa on - site ug natukod nga ang moving ug static contacts sa phase W sa No. 224 circuit breaker ug ang contact box sa cabinet adunay severe burned out.

2. Paghunahuna sa Cause sa Fault

Ang No. 224 circuit breaker sa X - capacitor bank adunay modelo nga VS1 - 12/T1250 - 25 ug gipatuman sa June 3, 2005. Human sa comprehensive inspection, gihatagan ang sumala sa actual on - site situation:

  • Primary Cause: Ang aging sa spring sa plum - blossom moving contact sa circuit breaker body mao ang primary cause sa karon nga accident. Sa panahon sa on - site maintenance process, natukod sa maintenance personnel nga ang pinakamao burned - out component mao ang spring sa plum - blossom moving contact. Ang on - site situation mao nga daghan sa spring sa moving contact sa phase W wala na ug melted, ug ang spring sa moving contact sa phase V miaging annealing. Sa paghatag og katugasan sa old ug new contacts, makita nga tungod sa long operation time sa No. 224 circuit breaker, ang spring sa old contact adunay severe aging, resulta sa decrease sa contact pressure sa moving contact ug increase sa contact resistance, prone sa overheating. Sa samang panahon, tungod sa high requirements sa breaking capacity sa large currents ug frequent switching sa capacitor, sa panahon sa breaking process, lisud kini magresulta sa poor contact sa moving ug static contacts, kasagaran niini magresulta sa aging sa spring ug virtual - connection discharge, resulta sa burning - out sa contacts.

  • Secondary Cause: Ang long - term operation sa circuit breaker body ug ang oscillatory displacement sa car body mao ang secondary cause sa karon nga accident. Ang No. 224 circuit breaker adunay long - term operation o hot standby. Sa panahon sa switching process sa capacitor bank, ang circuit breaker body magvibrate, resulta sa slight shift sa car body, nga magresulta sa shift sa contact sa three - phase moving ug static contacts. Sa panahon sa rack - in ug rack - out operations sa on - site, natukod nga adunay certain gap sa car body ug cabinet track. Sa long - term switching operation sa circuit breaker, ang trolley mahimo nga magshift (sa paghatag og katugasan sa burned - out phase W sa uban pa nga non - faulty phases, makita kini). Basehan niini, sa panahon sa accident, ang contact size sa moving ug static contacts sa phase U normal, ang contact sa moving ug static contacts sa phase V lisud kaayo, ug ang phase W adunay virtual connection o unqualified contact size.

3. Paghandle sa Fault Situation

Ang maintenance personnel gipalit ang moving ug static contacts sa phase W sa No. 224 circuit breaker ug ang contact box sa cabinet sa on - site. Human sa pagkumpleto, gibuhat nila ang mechanical characteristic tests ug contact resistance measurements sa No. 224 circuit breaker. Sa samang panahon, gibuhat nila ang withstand voltage tests sa 10 kV busbar ug No. 224 circuit breaker. Tanang tests qualified, meeting the requirements for commissioning. Ang power supply gibalik sa 17:00 sa parehas nga adlaw.

4. Improvement Measures

  • Material Selection: Strictly control the material selection of all components of the incoming - network vacuum circuit breaker. For the selection of the material and mechanical dimensions of components such as plum - blossom contacts, operating mechanisms, and secondary plugs, strictly follow the product technical requirements to improve the reliability of the equipment.

  • Installation Process: Strengthen the installation process of the trolley and the cabinet of the vacuum circuit breaker. The trolley and the circuit breaker must be installed firmly and reliably. The trolley should move in and out of the cabinet flexibly without jamming. When the trolley is in the operating, maintenance, or standby position, it should be firmly fixed. At the same time, the contact pressure and insertion depth of its moving and static contacts should meet the product technical requirements. It is strictly prohibited to have insufficient contact pressure or oscillatory displacement.

  • Equipment Inspection: Strengthen the inspection of equipment. Strengthen the overall inspection of the 10 kV capacitor bank circuit breakers with VS1 vacuum circuit breakers in the cabinet. Conduct regular inspections according to the number of switching operations to ensure that the contact pressure of the moving and static contacts meets the requirements for the safe and stable operation of the equipment.

Maghatag og tip ug pagsalig sa author
Gipareserbado
10kV RMU Common Faults & Solutions Guide

Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
10kV RMU Common Faults & Solutions Guide Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
Mga Isyu sa Pag-apply ug mga Pamaagi sa Pag-handle para sa 10kV Ring Main Units (RMUs)Ang 10kV ring main unit (RMU) usa ka kasagaran nga pananglitan sa elektrikal nga distribusyon sa urban nga mga network sa kuryente, gamiton sa paghatag ug distribusyon sa medium-voltage nga kuryente. Sa aktwal nga operasyon, mahimong madungog ang uban pang mga isyu. Ania ang mga kasagaran nga problema ug ang naka-corresponding nga mga pamaagi sa pag-handle.I. Mga Electrical Faults Internal Short Circuit o Pobre
Echo
10/20/2025
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
High-Voltage Circuit Breakers: Classification and Fault DiagnosisAng mga high-voltage circuit breakers mao ang mga kritikal nga protective devices sa mga power systems. Sila nag-intererrupt sa current ngadto sa pag-occur og fault, nang maprevent ang pag-damage sa equipment gikan sa overloads o short circuits. Sa wala pa, tungod sa long-term operation ug uban pang factors, ang mga circuit breakers mahimong mag-develop og faults nga angay nga i-diagnose ug troubleshoot niadtong maayo nga panahon.I
Felix Spark
10/20/2025
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions for Transformer Installation and Operation! Dili ang pag-install sa transformer nang labi ka layo—ayaw ihatag kini sa mga remote nga bukid o wilderness. Ang labi ka dako nga distansya wala lang magwasto sa cables apan adunay mas daghan pa nga line losses, ug mahadlok usab ang pag-manage ug maintenance. Dili ang pagpili sa capacity sa transformer nang random. Importante nga ang tama nga capacity. Kon ang capacity mubo, ang transformer mahimong mag-overload ug madaling mapuslan—ang
James
10/20/2025
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Ang mga Prosidyur sa Pagmamaintain sa Dry-Type Transformers Ibutang ang standby transformer sa operasyon, buksan ang circuit breaker sa low-voltage side sa transformer nga gi-maintain, tangtangon ang control power fuse, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Buksan ang high-voltage side circuit breaker sa transformer nga gi-maintain, isara ang grounding switch, fully discharge ang transformer, lock ang high-voltage cabinet, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Para sa