Design of Remote Closing Device for Indoor Handcart High-Voltage Vacuum Circuit Breaker

Dyson
06/07/2025

The cabling and undergrounding of urban power grid lines have become an irreversible trend in distribution network construction. High-voltage switchgear, as the core equipment of the distribution system, has become the main object of daily operation and maintenance for maintenance personnel. During the equipment iteration process, the comprehensive replacement and commissioning of new equipment have a long cycle, and a type of old hand-cranked high-voltage switchgear is still in service.
Due to long-term operation, such switchgear is prone to arcing risks during opening and closing operations. In practical maintenance scenarios, when electric operation fails, manual closing by personnel is required, exposing them directly to safety threats from arcing. Therefore, developing a remote closing device to replace manual operation as an auxiliary safety measure during the equipment update transition is urgent.
Focusing on this issue, as a project participant, this paper designs a remote closing operation device by analyzing the operational characteristics of old hand-cranked circuit breakers to avoid safety risks during manual operations.
Traditional Closing Method of Hand-Cranked Circuit Breakers
In the operation panel and crank structure of hand-cranked circuit breakers (as shown in Figure 1), the manual closing rotating rod is located on the left side of the panel with a regular hexagonal cross-section. The operation handle is Z-shaped, connected to the rotating rod via a regular hexagonal sleeve at the lower end for pluggable connection. During operation, after inserting the handle into the rotating rod, turning the upper end clockwise about 24 circles completes the circuit breaker closing action.
Torque Calculation Basis and Design Criteria
Based on the structural characteristics of the linkage operating handle, the torque requirement for manual closing of the circuit breaker can be derived by determining the length of the force arm and the pulling force parameters. According to the mechanical formula 
  • L→ is the distance vector from the rotation axis of the operating handle to the force application point, with an average measured value of 14 cm;
  • F→min is the minimum vector force required to drive the rotating rod;
  • M→min is the minimum torque required to initiate rotation of the rod.
Through operational characteristic analysis, the rotational resistance of the manually operated circuit breaker reaches its peak at the 15th rotation cycle. The minimum torque data at this point can cover the entire closing process. The torque design of the remote closing device must exceed this critical value with a safety margin to accommodate torque variations among different circuit breaker models. Detailed test data will be presented in subsequent sections.
Basic Structure of the Remote Closing Device

As shown in Figure 2, the device consists of a fixed rod, moving components, electric device, and closing joint. The fixed rod is designed to be telescopic, with support plates welded on both sides. During installation, the rod is first shortened and placed vertically into the cabinet, then extended to make the support plates prop against the cabinet for horizontal fixation. The moving components are adjusted in the vertical direction to align the closing joint of the electric device with the rotating head of the handcart switch. After configuration, operators can withdraw to a safe area and send a clockwise signal via the remote transmitter to complete the closing operation.
Realization of Remote Control and Operation
Motor Selection and Parameters
In selecting the core motor module, permanent magnet DC brushless motors and brushed motors were compared. Brushless motors offer significant advantages in service life and noise level (≤55dB), but feature complex control circuits and higher costs (40% more than brushed types). Given the device's non-stringent requirements for motor control, the XD-3420 permanent magnet DC brushed motor was chosen for its simple control and low cost. Key parameters:
  • Rated voltage: 12V; Rated current: 2.42A;
  • Rated power: 30W; Calculated rated torque: 11.9N·m (1.19kgf·cm), meeting operational requirements.
 To enable maintenance personnel to operate from a safe distance, the device employs a Qichip QA-R-010 wireless remote control switch for wireless power management. The module consists of a transmitter and receiver: the receiver supports DC input from 3.6V to 24V, with red/black wires for positive/negative inputs and blue/gray wires for corresponding outputs (output voltage matches input). The two-button transmitter offers three output modes: momentary, latching, and interlocking. The project utilizes the momentary mode, where the switch module conducts only while the button is pressed, ensuring instant disconnection upon release to meet the requirements of transient control during closing operations.
On-site remote control experiment
We used a tensile tester to measure the pulling force required for manual closing of a decommissioned hand - cranked handcart switch. As shown in Table 1, when the hand - cranked closing reaches around the 15th circle, the minimum pulling force needed for hand - cranked closing reaches its maximum value. Using this pulling force, we calculated that the minimum torque required for the entire hand - cranked closing process is 1.75 N·m.
We compared the operation times of the traditional manual closing method and the remote closing device. Table 2 shows that using the remote closing device not only avoids risks but also slightly improves operation efficiency compared to pure manual operation. Without increasing time costs, it significantly reduces operators' safety risks.
To address the safety risk of maintenance personnel needing to operate old - fashioned hand - cranked circuit breakers up close in the current distribution network, we proposed and developed an auxiliary device. It allows maintenance personnel to keep a distance from the switchgear and remotely control the circuit breaker closing. We detailed the basic software and hardware components of the prototype and its usage. Torque tests show that this remote closing auxiliary device meets the closing torque requirements of hand - cranked circuit breakers. Compared with the traditional operation method, the operation time is similar. It avoids the risks of maintenance personnel operating such circuit breakers up close without increasing time costs, and the device has good engineering application value.
Dyson

Focused on the design of electrical equipment, proficient in electrical principles and relevant specifications, and skilled in using design software. From intelligent substations to various types of electrical equipment, I am adept at optimizing design solutions, integrating new technologies. With practical experience and collaborative management capabilities, I deliver outstanding electrical design achievements.

Research on Low - Voltage Anti - DC Current Transformer and Detection Device
Research on Low - Voltage Anti - DC Current Transformer and Detection Device
1. Overview of Components and IssuesTA (low-voltage current transformer) and electric energy meters are key components of low-voltage electric energy metering. The load current of such meters is no less than 60A. Electric energy meters vary in type, model, and anti-DC performance, and are connected in series in the metering device. Due to the lack of anti-DC capability, they suffer from metering errors under DC component loads, usually caused by non-linear loads. With the increasing use of DC or
Dyson
07/16/2025
Anti - Theft Device for Low - Voltage Current Transformers
Anti - Theft Device for Low - Voltage Current Transformers
1. Innovation BackgroundWith the progress of society and economic development, the electricity demand of power users is expanding increasingly. Lawbreakers, aiming to save electricity costs and pursue high profits, gradually use high - tech methods to steal electricity, causing huge economic losses to power supply enterprises. Currently, popular electricity theft methods in the market include illegally opening the wiring cover of low - voltage transformers in electric energy metering boxes, alte
Dyson
07/16/2025
What aspects should be taken into consideration during the design of AIS voltage transformers?
What aspects should be taken into consideration during the design of AIS voltage transformers?
I. Key Elements of Mechanical Structure DesignThe mechanical structure design of AIS voltage transformers ensures long - term stable operation. For 66 kV outdoor AIS voltage transformers (pillar - type structure):Pillar Material: Use epoxy resin casting + metal frame for mechanical strength, pollution/weather resistance. Special design needed for 66 kV (vs 35 kV & below). Dry - type insulation (porcelain/epoxy shell) requires sufficient bending/impact resistance for harsh outdoors.Heat Dissi
Dyson
07/15/2025
Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets
Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets
1.Gas Generation and Analysis Principle of High - Voltage ReactorsHigh - voltage reactors use oil and insulating paper for insulation. Normal operation may see local overheating or discharges (e.g., iron core/winding issues, inter - turn short circuits), causing insulation cracking and producing gases like hydrocarbons (methane, etc.), CO, CO2, H2). These gases reflect internal insulation status, enabling real - time monitoring.For closed oil - filled reactors, insulation aging and oil oxidation
Oliver Watts
07/11/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!