Design of Remote Closing Device for Indoor Handcart High-Voltage Vacuum Circuit Breaker

Dyson
Dyson
Field: Electrical Standards
China

The cabling and undergrounding of urban power grid lines have become an irreversible trend in distribution network construction. High-voltage switchgear, as the core equipment of the distribution system, has become the main object of daily operation and maintenance for maintenance personnel. During the equipment iteration process, the comprehensive replacement and commissioning of new equipment have a long cycle, and a type of old hand-cranked high-voltage switchgear is still in service.

Due to long-term operation, such switchgear is prone to arcing risks during opening and closing operations. In practical maintenance scenarios, when electric operation fails, manual closing by personnel is required, exposing them directly to safety threats from arcing. Therefore, developing a remote closing device to replace manual operation as an auxiliary safety measure during the equipment update transition is urgent.

Focusing on this issue, as a project participant, this paper designs a remote closing operation device by analyzing the operational characteristics of old hand-cranked circuit breakers to avoid safety risks during manual operations.

Traditional Closing Method of Hand-Cranked Circuit Breakers

In the operation panel and crank structure of hand-cranked circuit breakers (as shown in Figure 1), the manual closing rotating rod is located on the left side of the panel with a regular hexagonal cross-section. The operation handle is Z-shaped, connected to the rotating rod via a regular hexagonal sleeve at the lower end for pluggable connection. During operation, after inserting the handle into the rotating rod, turning the upper end clockwise about 24 circles completes the circuit breaker closing action.

Torque Calculation Basis and Design Criteria

Based on the structural characteristics of the linkage operating handle, the torque requirement for manual closing of the circuit breaker can be derived by determining the length of the force arm and the pulling force parameters. According to the mechanical formula 

  • L→ is the distance vector from the rotation axis of the operating handle to the force application point, with an average measured value of 14 cm;

  • F→min is the minimum vector force required to drive the rotating rod;

  • M→min is the minimum torque required to initiate rotation of the rod.

Through operational characteristic analysis, the rotational resistance of the manually operated circuit breaker reaches its peak at the 15th rotation cycle. The minimum torque data at this point can cover the entire closing process. The torque design of the remote closing device must exceed this critical value with a safety margin to accommodate torque variations among different circuit breaker models. Detailed test data will be presented in subsequent sections.

Basic Structure of the Remote Closing Device

As shown in Figure 2, the device consists of a fixed rod, moving components, electric device, and closing joint. The fixed rod is designed to be telescopic, with support plates welded on both sides. During installation, the rod is first shortened and placed vertically into the cabinet, then extended to make the support plates prop against the cabinet for horizontal fixation. The moving components are adjusted in the vertical direction to align the closing joint of the electric device with the rotating head of the handcart switch. After configuration, operators can withdraw to a safe area and send a clockwise signal via the remote transmitter to complete the closing operation.

Realization of Remote Control and Operation
Motor Selection and Parameters

In selecting the core motor module, permanent magnet DC brushless motors and brushed motors were compared. Brushless motors offer significant advantages in service life and noise level (≤55dB), but feature complex control circuits and higher costs (40% more than brushed types). Given the device's non-stringent requirements for motor control, the XD-3420 permanent magnet DC brushed motor was chosen for its simple control and low cost. Key parameters:

  • Rated voltage: 12V; Rated current: 2.42A;

  • Rated power: 30W; Calculated rated torque: 11.9N·m (1.19kgf·cm), meeting operational requirements.

 To enable maintenance personnel to operate from a safe distance, the device employs a Qichip QA-R-010 wireless remote control switch for wireless power management. The module consists of a transmitter and receiver: the receiver supports DC input from 3.6V to 24V, with red/black wires for positive/negative inputs and blue/gray wires for corresponding outputs (output voltage matches input). The two-button transmitter offers three output modes: momentary, latching, and interlocking. The project utilizes the momentary mode, where the switch module conducts only while the button is pressed, ensuring instant disconnection upon release to meet the requirements of transient control during closing operations.

On-site remote control experiment

We used a tensile tester to measure the pulling force required for manual closing of a decommissioned hand - cranked handcart switch. As shown in Table 1, when the hand - cranked closing reaches around the 15th circle, the minimum pulling force needed for hand - cranked closing reaches its maximum value. Using this pulling force, we calculated that the minimum torque required for the entire hand - cranked closing process is 1.75 N·m.

We compared the operation times of the traditional manual closing method and the remote closing device. Table 2 shows that using the remote closing device not only avoids risks but also slightly improves operation efficiency compared to pure manual operation. Without increasing time costs, it significantly reduces operators' safety risks.

To address the safety risk of maintenance personnel needing to operate old - fashioned hand - cranked circuit breakers up close in the current distribution network, we proposed and developed an auxiliary device. It allows maintenance personnel to keep a distance from the switchgear and remotely control the circuit breaker closing. We detailed the basic software and hardware components of the prototype and its usage. Torque tests show that this remote closing auxiliary device meets the closing torque requirements of hand - cranked circuit breakers. Compared with the traditional operation method, the operation time is similar. It avoids the risks of maintenance personnel operating such circuit breakers up close without increasing time costs, and the device has good engineering application value.

Give a tip and encourage the author!
Recommended
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Trip and Close Operations in Vacuum Circuit Breakers1. IntroductionWhen you hear the term "vacuum circuit breaker," it might sound unfamiliar. But if we say "circuit breaker" or "power switch," most people will know what it means. In fact, vacuum circuit breakers are key components in modern power systems, responsible for protecting circuits from damage. Today, let's explore an important concept — the minimum operating voltage for trip and close operations.Though it
Dyson
10/18/2025
Efficient Wind-PV Hybrid System Optimization with Storage
Efficient Wind-PV Hybrid System Optimization with Storage
1. Analysis of Wind and Solar Photovoltaic Power Generation CharacteristicsAnalyzing the characteristics of wind and solar photovoltaic (PV) power generation is fundamental to designing a complementary hybrid system. Statistical analysis of annual wind speed and solar irradiance data for a specific region reveals that wind resources exhibit seasonal variation, with higher wind speeds in winter and spring and lower speeds in summer and autumn. Wind power generation is proportional to the cube of
Dyson
10/15/2025
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
I. Current Status and Existing ProblemsCurrently, water supply companies have extensive networks of water pipelines laid underground across urban and rural areas. Real-time monitoring of pipeline operation data is essential for effective command and control of water production and distribution. As a result, numerous data monitoring stations must be established along the pipelines. However, stable and reliable power sources near these pipelines are rarely available. Even when power is accessible,
Dyson
10/14/2025
How to Build an AGV-Based Intelligent Warehouse System
How to Build an AGV-Based Intelligent Warehouse System
Intelligent Warehouse Logistics System Based on AGVWith the rapid development of the logistics industry, growing land scarcity, and rising labor costs, warehouses—serving as key logistics hubs—are facing significant challenges. As warehouses become larger, operational frequencies increase, information complexity grows, and order-picking tasks become more demanding, achieving low error rates and reduced labor costs while improving overall storage efficiency has become a primary goal for the wareh
Dyson
10/08/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.