• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Trip Circuit Supervision

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Trip Circuit Supervision

There are different contacts connected in series along a trip circuit of an electrical circuit breaker. There must be some situation when the circuit breaker should not trip even a faulty current passes through its power contacts. Such situations are low gas pressure in SF6 circuit breaker, low air pressure in pneumatic operated circuit breaker etc. In this situation the trip coil of the CB must not be energized to trip the CB. So there must be NO contacts associated with gas pressure and air pressure relays, connected in series with breaker trip coil. Another scheme of trip coil is that it should not be re energized once the circuit breaker is opened. That is done by providing one NO contact of breaker auxiliary switch in series with trip coil. In addition to that the trip circuit of a CB has to pass through considerable numbers of intermediate terminal contacts in relay, control panel and circuit breaker kiosk.

So if any of the intermediate contacts is detached, the circuit breaker fails to trip. Not only that, if DC supply to the trip circuit fails, the CB will not trip. To overcome this abnormal situation, trip circuit supervision becomes very necessary. The figure below shows the simplest form of trip circuit healthy scheme. Here a series combination of one lamp, one push bottom and one resistor is connected across the protective relay contact as shown. In healthy situation all the contacts except protective relay contact are in close position. Now if push bottom (PB) is pressed, the trip circuit supervision network is completed and lamp glows indicating that the breaker is ready for tripping.

trip circuit supervisionThe above scheme is for supervision while circuit breaker is closed. This scheme is called post close supervision. There is another supervision scheme which is called pre and post close supervision.

This trip circuit supervision scheme is also quite simple. The only difference is that here in this scheme, one NC contact of same auxiliary switch is connected across the auxiliary NO contact of the trip circuit. The auxiliary NO contact is closed when CB is closed and auxiliary NC contact is closed when CB is open and vice versa. Hence, as shown in the figure below when the circuit breaker is closed the trip circuit supervision network is completed via auxiliary NO contact but when the circuit breaker is open the same supervision network is completed via NC contact. The resistor is used series with the lamp for preventing unwanted tripping of circuit breaker due to internal short circuit caused by failure of the lamp.
Trip Circuit SupervisionSo far whatever we have discussed it is only for locally controlled installation but for a distance control installation, relay system is necessary. The figure below shows the trip circuit supervision scheme wherever a remote signal is required.
Trip Circuit SupervisionWhen trip circuit is healthy and circuit breaker is closed, relay A is energized which closes the NO contact A1 and hence relay C is energized. Energized relay C keeps NC contact in open position. Now if the circuit breaker is open, relay B is energized which closes No contact B1 hence relay C is energized. As C is energized, it keeps the NC contact C1 in open position. While CB is closed, if there is any discontinuity in the trip circuit relay A is de-energized which opens contact A1 and consequently relay C is de-energized and which make the NC contact C1 in close position and hence alarm circuit is actuated. Trip circuit supervision is experienced by relay B with the circuit breaker is open in a similar manner as relay A with the circuit breaker is closed. Relays A and C are time-delayed by copper slugs to prevent spurious alarms during tripping or closing operations. The resistors are mounted separately from the relays and their values are chosen such that if any one component is inadvertently short-circuited, a tripping operation will not take place.

The alarm circuit supply should be separated from main trip supply so that the alarm can be actuated even the trip supply failed.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?When the transformer gas (Buchholz) protection device operates, a thorough inspection, careful analysis, and accurate judgment must be carried out immediately, followed by appropriate corrective actions.1. When the Gas Protection Alarm Signal is ActivatedUpon activation of the gas protection alarm, the transformer should be inspected immediately to determine the cause of operation. Check whether it was caused
Felix Spark
11/01/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
THD Overload: How Harmonics Destroy Power Equipment
THD Overload: How Harmonics Destroy Power Equipment
When Actual Grid THD Exceeds Limits (e.g., Voltage THDv > 5%, Current THDi > 10%), It Causes Organic Damage to Equipment Across the Entire Power Chain — Transmission → Distribution → Generation → Control → Consumption. The Core Mechanisms Are Additional Losses, Resonant Overcurrent, Torque Fluctuations, and Sampling Distortion. Damage Mechanisms and Manifestations Vary Significantly by Equipment Type, as Detailed Below:1. Transmission Equipment: Overheating, Aging, and Drastically Reduced
Echo
11/01/2025
What Is Discharge Load for Energy Absorption in Power Systems?
What Is Discharge Load for Energy Absorption in Power Systems?
Discharge Load for Energy Absorption: A Key Technology for Power System ControlDischarge load for energy absorption is a power system operation and control technology primarily used to address surplus electrical energy caused by load fluctuations, power source faults, or other disturbances in the grid. Its implementation involves the following key steps:1. Detection and ForecastingFirst, real-time monitoring of the power system is conducted to collect operational data, including load levels and
Echo
10/30/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.