• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Neutral point grounding operation mode for 110kV~220kV power grid transformers

Vziman
Field: Manufacturing
China
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.
 
For 220kV and 110kV transformers in new construction and technical renovation projects, their neutral point grounding modes shall strictly comply with the following requirements:

1. Autotransformers

The neutral point of an autotransformer must be directly grounded or grounded via a small reactance.

2. Thin-insulation Transformers (Unmodified)

The neutral point of an unmodified thin-insulation transformer should preferably be operated in a directly grounded manner.

3. 220kV Transformers

  • If the insulation class of the 110kV side neutral point of a 220kV transformer is 35kV, the neutral points of both the 220kV side and 110kV side shall be operated in a directly grounded manner.
  • The grounding modes of the neutral points on the 220kV and 110kV sides of the transformer should preferably be the same, and the neutral point grounding disconnecting switch should preferably be equipped with remote operation functionality.
  • In a 220kV substation/power plant, one transformer should preferably be operated with its neutral point directly grounded. For 220kV substations/power plants with two or more transformers, when the 220kV or 110kV side busbars are split on either or both sides, one transformer with a directly grounded neutral point shall be maintained on each busbar section.

4. 110kV Transformers

  • If the insulation class of the 110kV neutral point of a 110kV transformer is 66kV, the neutral point may not be operated in a directly grounded manner.
  • For transformers where the insulation class of the 110kV neutral point is 44kV or lower, the neutral point should preferably be operated in a directly grounded manner.
  • In a power plant or a substation with a power source on the medium/low-voltage side, one transformer should preferably be maintained with its neutral point directly grounded within the plant/substation.
  • The neutral point of a terminal transformer without a local power supply should not be operated in a directly grounded manner.
Give a tip and encourage the author!

Recommended

Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Design Principles for Pole-Mounted Distribution Transformers
Design Principles for Pole-Mounted Distribution Transformers(1) Location and Layout PrinciplesPole-mounted transformer platforms should be located near the load center or close to critical loads, following the principle of “small capacity, multiple locations” to facilitate equipment replacement and maintenance. For residential power supply, three-phase transformers may be installed nearby based on current demand and future growth projections.(2) Capacity Selection for Three-Phase Pole-Mounted Tr
12/25/2025
Transformer Noise Control Solutions for Different Installations
1.Noise Mitigation for Ground-Level Independent Transformer RoomsMitigation Strategy:First, conduct a power-off inspection and maintenance of the transformer, including replacing aged insulating oil, checking and tightening all fasteners, and cleaning dust from the unit.Second, reinforce the transformer foundation or install vibration isolation devices—such as rubber pads or spring isolators—selected based on the severity of vibration.Finally, strengthen sound insulation at weak points of the ro
12/25/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.