Air break circuit breakers technical history in high voltage

Edwiin
01/24/2025

Air-Blast Circuit Breakers: A Historical Overview
Introduction

Air-blast circuit breakers leverage the superior dielectric strength and thermal properties of compressed air compared to atmospheric air. This technology allows for the design of high-voltage circuit breakers, utilizing an axial blast of compressed air directed at the arc to extinguish it efficiently. For over five decades, this method was the preferred technology for extra-high voltage applications until the advent of SF6 (sulfur hexafluoride) circuit breakers.

Historical Development

The concept of air-blast arc extinction originated in Europe during the 1920s. Significant advancements were made in the 1930s, leading to widespread installation of air-blast circuit breakers by the 1950s. These early models had an interrupting capability of up to 63 kA, which later increased to 90 kA by the 1970s.

Technical Limitations and Innovations

Despite their effectiveness, air-blast circuit breakers have relatively limited dielectric withstand capabilities, primarily due to the speed at which contacts can open. To enhance performance, engineers adopted multi-break designs to increase the opening speed. Consequently, for rated voltages exceeding 420 kV, initial designs required 10 or even 12 interrupters in series per pole.

Notable Example

A notable example of this technology is illustrated by a figure showing an air-blast circuit breaker with 14 interrupters per pole, designed for 765 kV operation in 1968 by ASEA (now part of ABB). This exemplifies the advanced engineering required to meet the demands of ultra-high voltage transmission systems during that era.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f