Surge Impedance Loading or SIL

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Surge Impedance Loading

Surge Impedance Loading is a very essential parameter when it comes to the study of power systems as it is used in the prediction of maximum loading capacity of transmission lines.
However before understanding SIL, we first need to have an idea of what is Surge Impedance (Zs). It can be defined in two ways one a simpler one and other a bit rigorous.
Method 1
It is a well known fact that a
long transmission lines (> 250 km) have distributed inductance and capacitance as its inherent property. When the line is charged, the capacitance component feeds reactive power to the line while the inductance component absorbs the reactive power. Now if we take the balance of the two reactive powers we arrive at the following equation

Capacitive VAR = Inductive VAR
Where,
V = Phase voltage
I = Line Current
Xc =
Capacitive reactance per phase
XL = Inductive reactance per phase
Upon simplifying
Where,
f = Frequency of the system
L = Inductance per unit length of the line
l = Length of the line
Hence we get,
This quantity having the dimensions of resistance is the Surge Impedance. It can be considered as a purely resistive load which when connected at the receiving end of the line, the reactive power generated by capacitive reactance will be completely absorbed by inductive reactance of the line.It is nothing but the Characteristic Impedance (Zc) of a lossless line.

Method 2
From the rigorous solution of a
long transmission line we get the following equation for voltage and current at any point on the line at a distance x from the receiving end
Where,
Vx and Ix = Voltage and Current at point x
VR and IR = Voltage and Current at receiving end
Zc = Characteristic Impedance
δ = Propagation Constant
Z = Series impedance per unit length per phase
Y = Shunt admittance per unit length per phase
Putting the value of δ in above equation of voltage we get

Where,
We observe that the instantaneous voltage consists of two terms each of which is a function of time and distance. Thus they represent two travelling waves. The first one is the positive exponential part representing a wave travelling towards receiving end and is hence called the incident wave. While the other part with negative exponential represents the reflected wave. At any point along the line, the voltage is the sum of both the waves. The same is true for current waves also.

Now, if suppose the load impedance (ZL) is chosen such that ZL = Zc, and we know
Thus

and hence the reflected wave vanishes. Such a line is termed as infinite line. It appears to the source that the line has no end because it receives no reflected wave.
Hence, such an impedance which renders the line as infinite line is known as surge impedance.It has a value of about 400 ohms and phase angle varying from 0 to –15 degree for overhead lines and around 40 ohms for underground cables.
The term surge impedance is however used in connection with surges on the transmission line which may be due to lightning or switching, where the line losses can be neglected such that

Now that we have understood Surge Impedance, we can easily define Surge Impedance Loading.
SIL is defined as the power delivered by a line to a purely resistive load equal in value to the surge impedance of that line. Hence we can write
The unit of SIL is Watt or MW.
When the line is terminated by surge impedance the receiving end voltage is equal to the sending end voltage and this case is called flat voltage profile. The following figure shows the voltage profile for different loading cases.
surge impedance loading or silIt should also be noted that surge impedance and hence SIL is independent of the length of the line. The value of surge impedance will be the same at all the points on the line and hence the voltage.
In case of a Compensated Line, the value of surge impedance will be modified accordingly as
Where, Kse = % of series capacitive compensation by Cse
KCsh = % of Shunt capacitive compensation by Csh
Klsh = % of shunt inductive compensation by Lsh
The equation for SIL will now use the modified Zs.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.