Differential Protection of Generator or Alternator

03/26/2024

What Is Differential Protection

Any internal fault inside the stator winding is cleared by mainly differential protection scheme of the generator or alternator.
The
differential protection is provided in the generator by using longitudinal differential relay.
generator differential protection
Generally instantaneous attracted armature type relays are used for this purpose because all they have high speed operation and also they are free from being affected by any AC transient of the power circuit.

There are two sets of current transformers, one CT is connected to the line side of the generator and other is connected to the neutral side of the generator in each phase. It is needless to say that the characteristics of all current transformers installed against each phase must be matched. If there is any major mismatched in the current transformer’s characteristics of both sides of the generator, there may be high chance of malfunctioning of differential relay during the fault external to the stator winding and also may be during normal operating conditions of the generator. To ensure that the relay does not operate for the faults external to the operated zone of the protection scheme, a stabilizing resistor is fitted in series with the relay operating oil. It also ensures that if one set of CT has been saturated, there will be no possibility of malfunctioning of the differential relay.

generator differential protection
It is always preferable to use dedicated current transformers for differential protection purpose because common current transformers may cause unequal secondary loading for other functionalities imposed on them. It is also always preferable to use all current transformers for differential protection of generators or alternators should be of same characteristics. But practically there may be some difference in characteristics of the current transformers installed at line side to those installed in neutral side of the generator.

These mismatches cause spill current to flow through the relay operating coil. To avoid the effect of spill current, percentage biasing is introduced in differential relay.
differential protection of generator with percentage biasing
The percentage biased differential relay comprises two restraint coils and one operating coil per phase. In the relay, the torque produced by operating coil tends to close the relay contacts for instantaneous tripping of circuit breakers but at the same time the torque produced by the restraint coils prevents to close the relay contacts as restraint coils torque is directed opposite of the operating coil torque. Hence during through fault the differential relay would not be operated because the setting of the relay is increased by restraint coils and also it prevents malfunctioning of relay due to spill current. But during internal fault in the winding of the stator, the torque produced by restraint coils is ineffective and the relay closes its contact when setting current flows through the operating coil.
Differential current pickup setting/bias setting of the relay is adopted based on the maximum percentage of allowable mismatch adding some safety margin.
The spill current level for the relay is to just operate it; is experienced as a percentage of the through fault current causing it. This percentage is defined as bias setting of the relay.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su
08/29/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!