• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Bus-Bar Protection

Edwiin
Field: Power switch
China

When a fault occurs on the bus bars, the entire power supply is interrupted, and all the non - faulty feeders are disconnected. The majority of bus bar faults are single - phase and often temporary in nature. Bus zone faults can occur due to various factors, such as the failure of support insulators, malfunctions in circuit breakers, or foreign objects accidentally falling across the bus bars. To clear a bus fault, all circuits connected to the faulty section must be opened.

The most commonly used bus zone protection schemes include:

  • Backup protection

  • Differential Overcurrent Protection

  • Circulating current protection

  • Voltage Overvoltage Protection

  • Frame leakage protection

Backup Protection for Bus - Bars

Backup protection represents a straightforward approach to safeguarding bus bars against faults. Faults on the bus bar often originate from the supplying system, making backup protection for the supply system essential. The diagram below illustrates a basic setup for bus - bar protection. Here, bus A is protected by the distance protection mechanism of bus B. In the event of a fault on bus A, the protective device on bus B will activate, with the relay operating within 0.4 seconds.

When a fault occurs on the bus bars, the entire power supply is interrupted, and all the non - faulty feeders are disconnected. The majority of bus bar faults are single - phase and often temporary in nature. Bus zone faults can occur due to various factors, such as the failure of support insulators, malfunctions in circuit breakers, or foreign objects accidentally falling across the bus bars. To clear a bus fault, all circuits connected to the faulty section must be opened.

The most commonly used bus zone protection schemes include:

  • Backup protection

  • Differential Overcurrent Protection

  • Circulating current protection

  • Voltage Overvoltage Protection

  • Frame leakage protection

Backup Protection for Bus - Bars

Backup protection represents a straightforward approach to safeguarding bus bars against faults. Faults on the bus bar often originate from the supplying system, making backup protection for the supply system essential. The diagram below illustrates a basic setup for bus - bar protection. Here, bus A is protected by the distance protection mechanism of bus B. In the event of a fault on bus A, the protective device on bus B will activate, with the relay operating within 0.4 seconds.

Circulating Current Protection and Voltage Differential Protection Relay

Circulating Current Protection

In the circulating current protection scheme, the summation current of the current transformers (CTs) flows through the operating coil of the relay. When current passes through the relay coils, it indicates the presence of short - circuit current in the CTs' secondaries. Consequently, the relay sends a signal to the circuit breakers, prompting them to open their contacts and isolate the faulty section of the electrical system.

However, a significant drawback of this protection scheme is that iron - cored current transformers can cause the relay to malfunction during external faults. The magnetic characteristics of iron - cored CTs may lead to unequal current transformation ratios under abnormal conditions, resulting in false tripping of the relay.

Voltage Differential Protection Relay

The voltage differential protection relay scheme employs coreless CTs, which offer improved linearity compared to their iron - cored counterparts. Linear couplers are utilized to increase the number of turns on the secondary sides of these CTs, enhancing the sensitivity and accuracy of the protection system.

In this setup, the secondary relays are connected in series via pilot wires. Additionally, the relay coil is also connected in series with the second terminal of the relevant circuit. This configuration allows for a more precise comparison of electrical quantities, enabling the protection system to accurately detect and respond to internal faults while remaining immune to the effects that cause false operations in traditional iron - cored CT - based schemes.

In a fault - free electrical system or when an external fault occurs, the algebraic sum of the secondary currents of the current transformers (CTs) equals zero. This balance is due to the normal flow of current through the system's healthy components, with the CTs accurately reflecting the current distribution. However, when an internal fault develops within the protected zone, the normal current flow is disrupted. Fault current then passes through the differential relay, disrupting the previously balanced current state.

Upon detecting this abnormal current flow, the differential relay activates. It promptly issues a command to the associated circuit breakers, instructing them to open their contacts. By quickly isolating the faulty section of the system, the differential protection mechanism effectively prevents further damage to equipment and ensures the stability of the overall electrical system. This rapid response helps minimize downtime and potential hazards, safeguarding the integrity of the power grid.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.