Hazards Causes and Types of Transformer Core Multi point Ground Faults

Leon
Leon
Field: Fault Diagnosis
China

Hazards of Multi-point Core Ground Faults

A transformer core must not have multi-point grounding during normal operation. An alternating magnetic field around the winding induces parasitic capacitances between windings, core, and shell. Live windings couple through these capacitances, creating a core floating potential relative to ground. Uneven distances between components cause potential differences; when high enough, they spark. This intermittent discharge degrades transformer oil and solid insulation over time.

To prevent this, the core and shell are reliably connected to share the same potential. However, two or more core/metal component ground points form a closed loop, causing circulation and local overheating. This decomposes oil, reduces insulation performance, and in severe cases, burns core silicon steel sheets—leading to major main transformer accidents. Thus, main transformer cores must use single-point grounding.

Causes of Core Ground Faults

Key causes include: grounding plate short circuits from poor construction/design; multi-point grounding from accessories or external factors; metal debris left in the transformer; and burrs, rust, or welding slag due to shoddy core processing.

Types of Core Failures

Six common types:

  • Core contact with shell/clamp: e.g., unremoved transport nails, clamp limb contact with core columns, warped silicon steel sheets touching clamps, fallen cardboard between clamp feet and iron yoke, or overlong thermometer seats.

  • Overlong core bolt steel covers shorting with silicon steel sheets.

  • Tank foreign objects causing partial short circuits (e.g., a screwdriver in a 31500/110 transformer, a 120mm copper wire in a 60000/220 unit).

  • Damp/damaged insulation (sludge, moisture, degraded clamp/pad/iron box insulation) leading to high-resistance multi-point grounding.

  • Worn submersible pump bearings releasing metal powder; electromagnetic attraction forms a bridge between lower rails, pads, or tank bottom, causing multi-point grounding.

  • Inadequate operation, maintenance, and lack of scheduled checks.

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.