High-Voltage Disconnect Switches and Operational Mechanism Failures Mataas nga Voltage Disconnect Switches ug Operational Mechanism Failures

Dyson
Dyson
Larangan: Pamantayan sa Elektresya
China

Ang mga high-voltage disconnect switches (HVDs) mao ang importante nga mga switch sa power grid, gamiton sa pag-isolate sa mga power source sama sa circuit breakers. Sa pagproposa sa "digital grids," ang patulob nga pag-advance sa teknolohiya sa high-voltage switchgear ug ang paglambigit sa China's power grid, ang HVD applications nagsugyot sa pagtumong sa kantidad ug diversity. Ang electric operating mechanism, isang vital nga komponente sa pagkontrol sa mga switching movements sa HVD, nagdagan sa exceptional nga reliability ug stability.

Ang HVDs adunay mataas nga failure rate sa mga high-voltage equipment, samtang ang operating mechanisms mao ang primary cause sa mga malfunctions. Ang common operational mechanism failures kasama ang switching refusal, operational failure, ug incomplete opening/closing. Ang runaway sa operating mechanism—sa dihang ang motor magpadayon og pag-operate—mahimong makapadala sa major power outages sa grid equipment. Sa matag caso, ang opening/closing failures (kasama ang refusal to switch, incomplete operation, ug low switching accuracy) mahimong makabati sa grid stability.

Ang panalipod nagpakita nga ang HVD failures gikan sa electric operating mechanisms dominante gikan sa secondary circuit issues, sama sa control failures gikan sa poor-quality electrical components o loose connections sa secondary circuit. Para sa widely used CJx-type electric operating mechanisms, ang internal motors protektado pinaagi sa thermal-magnetic circuit breakers ug electronic motor protection devices. Exposed outdoors long-term, kini nga mga mechanisms maintain operational postures para sa 3–6 tuig human sa commissioning, pero ang ilang electrical control components mao ang fragile ug highly susceptible sa environmental factors.

Ang prolonged operation mahimong makapalihog sa limit switches ug bolts, resulta sa incomplete switching kon undetected (e.g., ang 5° positional deviation sa Figure 1 pose grid risks). Ang travel switches, important sa switching process transitions, suffer from oxidized contacts ug shortened lifespan tungod sa environmental influences.

Summary and Research Status of High-Voltage Disconnect Switch Faults

In summary, ang primary causes sa high-voltage disconnect switch (HVD) opening/closing failures mahimong ikategoryahan sa duha ka types: electrical control circuit faults ug mechanical system faults. Kini nga paper focus sa electrical control circuit, kasama ang motor circuit failures, limit switch malfunctions, ug secondary circuit issues. Ang analysis nagpakita nga ang high switching failure rates dominante gikan sa motor ug secondary circuit faults, significantly impacting HVD operation. Thus, resolving the safety and reliability of HVD operating mechanisms is urgent.

1. Research Status of High-Voltage Disconnect Switches

Relevant researchers and engineers have conducted extensive studies on the above issues and proposed constructive solutions, summarized in two key aspects:

1.1 Research Status of Secondary Circuit Faults

Numerous studies have addressed electrical component issues in secondary circuits. Poor sealing of the operating mechanism box allows rainwater ingress, causing component corrosion, auxiliary switch/relay failure, loose button contacts, and mechanical jams—leading to switching refusal or incomplete operation. Proposed solutions include regular maintenance, moisture protection, and fault flowcharts for rapid troubleshooting.

For mechanical wear such as deformed pins, loose limit bolts, or worn screws due to motor inertia, measures like frequent inspections and timely defect elimination are recommended. Anti-oxidation materials are suggested for corroded wire joints, while voltage/resistance testing methods help diagnose secondary circuit faults—enhanced by defect logging to improve troubleshooting efficiency. Heating devices have been proposed to address humidity-induced issues like auxiliary switch misalignment and poor contact in electric operating mechanisms.

However, existing studies merely list fault points and emphasize maintenance without fundamental solutions, reflecting low attention to secondary circuits. Maintenance personnel often undervalue electrical components relative to mechanical parts, and unfamiliarity with secondary component structures/principles—combined with neglected regular inspections—are indirect failure causes.

1.2 Research Status of Switching Accuracy Issues

To address switching accuracy and mechanical inertia, scholars have improved motor control by designing brushless DC motor (BLDC) and permanent magnet synchronous motor (PMSM) operating mechanisms. A BLDC-based HVD mechanism with a DSP core and dual closed-loop control strategy has shown effective switching speed regulation. Similar methods for real-time speed monitoring ensure smooth operation and improved closing accuracy, laying a foundation for smart grid development. Notably, these designs remain in theoretical research and laboratory simulation stages, with unproven reliability in practical applications.

2 Distributed Electric Operating Mechanism Design Scheme

Based on the above analysis, the primary cause of operating mechanism failures is the poor reliability of the electrical control circuit, which is highly susceptible to environmental factors. Delayed maintenance or other issues can damage electrical components, leading to switching failures. In response, this paper proposes a distributed design for electric operating mechanisms.

2.1 Distributed Control Concept for Electric Operating Mechanisms

Distributed control divides the entire system into separate segments, each independently controlled by a main controller. This design separates the electrical control module from the motor drive module:

  • The electrical control module, composed of electronic components with numerous wiring contacts, is vulnerable to environmental influences. It is thus placed in a substation with stable room temperature.

  • The motor drive module, more resilient to environmental changes, is positioned near the high-voltage disconnect switch.

Considering the variable outdoor environment and cable susceptibility, a time-division shared cable strategy is adopted based on TRIZ's principle of multi-usage. Since motor control circuits and switching status indicator circuits do not need simultaneous activation, this approach enables signal transmission for both motor control and disconnect switch position indication using only 5 cables. This significantly reduces external environmental impacts on the electric operating mechanism. The overall control concept of the distributed electric operating mechanism is illustrated in Figure 2.

2.2 Design of Distributed Control Modules

The widely applied CJx-series electric operating mechanisms are designed with integrated electrical and mechanical components, operating outdoors year-round in a fixed configuration since commissioning. This integration is a key factor contributing to their high failure rate. The modular design disrupts this all-in-one outdoor setup by dividing the mechanism into two separate modules: an electrical control module and a mechanical drive module.

The modular design offers distinct advantages: it allows the electrical control module to be housed in a temperature-stabilized environment, significantly reducing environmental impacts on HVD switching operations; and it minimizes inter-module wiring, enabling quick replacement of faulty modules—prioritizing "replace-first, repair-later" to enhance maintenance efficiency and reduce grid downtime.

2.2.1 Electrical Control Module

The electrical control module comprises a main controller, open/close transfer switch, relays, position indication circuits, and a phase-loss protector, as outlined in the design concept of Figure 3.

The control logic functions as follows: a switching signal (open/close) from the button is sent to the controller, which regulates motor operation based on the command. When the HVD is in the open state, the open-position circuit activates, lighting the indicator. Pressing the close button triggers the controller to engage the main motor relay and close-circuit transfer relay, driving the HVD to close. Upon completion, the motor relay de-energizes, activating the close-position circuit and indicator. The phase-loss protector safeguards the motor circuit with timer functionality, disconnecting the main circuit within a specified time frame in the event of faults.

2.2.2 Motor Drive Module

The motor drive module primarily consists of an AC motor, speed reducer, friction coupling, Siemens auxiliary switch, thyristor arc-suppression circuit, limit stops, and mechanical locking device. When the main controller sends an open/close command, the motor control circuit is activated, driving the speed reducer and main shaft via the motor for switching operations. Limit stops at the top of the main shaft, in conjunction with the mechanical locking device, control the switching position accuracy. Meanwhile, the Siemens auxiliary switch works with the thyristor arc-suppression circuit to disconnect the motor control circuit, halting motor operation. A 90-degree rotational margin at the connection between the speed reducer and main shaft enables no-load starting of the motor. The appearance of the motor drive module is shown in Figure 4.

2.3 Solution for Disconnect Switch Closing Accuracy

The closing action is a crucial step for high-voltage switchgear. Inadequate closing accuracy can affect the stable operation of the entire power system. To further enhance the opening and closing accuracy of the electric operating mechanism, this design employs a mechanical locking device, in conjunction with a Siemens auxiliary switch and a friction coupler, to improve the accuracy to a certain extent.

2.3.1 Siemens Auxiliary Switch and Thyristor Arc - Suppression Circuit

The auxiliary switch is connected to the main motor circuit to control the on - off of the motor circuit. The auxiliary switch is not prone to rust due to external environmental influences, and its internal friction mechanism prevents accidental closures. The contacts use a spring - loaded pin and a hard sheath to ensure stable and reliable connections. The specific structure is shown in Figure 6.

Design Principle of Thyristor Arc - Suppression Circuit: During the disconnection of the auxiliary switch, an arc is generated. To prevent the arc from being too large and damaging the switch, a thyristor arc - suppression circuit is connected in parallel with the auxiliary switch to absorb the arc. The specific circuit design is shown in Figure 7, where contacts 1, 2, 3, and 4 are all auxiliary switch contacts. (Contacts 1 and 2 are used to control the on - off of the thyristor arc - suppression circuit, and contacts 3 and 4 are used to control the on - off of the main motor circuit. It is set that contacts 1 and 2 disconnect after contacts 3 and 4 to achieve the purpose of arc suppression).

2.3.2 Function of the Friction Coupler

The friction coupler safeguards the motor under any abnormal operating conditions. Once the high - voltage disconnect switch is in place after closing, the main motor circuit is rapidly disconnected. However, due to mechanical rotational inertia, the motor cannot stop immediately. At this moment, the friction coupler acts as a force - relieving component. It enables the friction gear to idle, dissipating the motor's mechanical inertia and ensuring the precise positioning of the high - voltage disconnect switch during opening and closing operations. Additionally, by adjusting the tightness of the spring, the friction torque can be modified to suit the opening and closing operations of various disconnect switches. The friction coupler is shown in Figure 8.

Advantages of the Designed Scheme over CJx - type Electric Operating Mechanisms

The proposed design eliminates electrical components like travel switches and limit switches, reducing instability factors and enhancing the reliability of the electric operating mechanism. It also removes the terminal block with numerous contacts, simplifying the wiring circuit. With a modular design, only five cables connect the two modules, greatly improving fault - repair efficiency. Additionally, it can form multiple protection layers with thermomagnetic circuit breakers and existing electronic motor protection devices. Even if the electrical control circuit malfunctions, the mechanical locking device and friction coupler ensure motor safety. The friction coupler counteracts the force from motor mechanical inertia, and the mechanical locking device prevents the limit stop from "rebounding", ensuring accurate opening and closing of the high - voltage disconnect switch and protecting its integrity. Moreover, the motor's no - load starting minimizes the starting current, avoiding equipment shock and extending the operating mechanism's service life.

3 Experimental Verification

Adhering to relevant standards such as "High - Voltage AC Disconnect Switches and Earthing Switches" and "Common Technical Requirements for High - Voltage AC Switchgear and Controlgear", the combination of a mechanical locking device and a friction coupler further improves the opening and closing accuracy of the disconnect switch. Compared with the CJx series electric operating mechanisms, it offers higher reliability and safety. Error detection, through multiple opening and closing tests and angular deviation measurements between the limit stop and limit screw, shows that they are closely aligned, with an actual machining error within 1°, fully meeting the technological standards. The actual position is shown in Figure 9.

 

 

4 Conclusion
As one of the key equipment in the power grid, the reliability and safety of the operating mechanism of high - voltage disconnect switches are of utmost importance. This paper takes the electric operating mechanism as the research object, conducts a detailed design and analysis of its distributed control method, and verifies it through experiments, achieving the expected results.Based on the concept of distributed control, the motor is driven by the main controller to safely and accurately control the opening and closing operations of high - voltage disconnect switches.
With a modular design approach, the electric operating mechanism is mainly divided into an electrical control module and a motor drive module, reducing the complexity of wiring and improving the maintenance speed.A mechanical locking device is set up. Combined with the special structures of the Siemens auxiliary switch and the friction coupler, the opening and closing accuracy of the disconnect switch has been improved.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Minimum nga Operasyonal nga Voltaje para sa Vacuum Circuit Breakers
Minimum nga Operasyonal nga Voltaje para sa Vacuum Circuit Breakers
Minimum Operating Voltage for Trip and Close Operations in Vacuum Circuit Breakers1. IntroductionKung makita nimo ang termino "vacuum circuit breaker," mahimong dili familiar kini. Apan kon mogwarta ta og "circuit breaker" o "power switch," daghan sa mga tawo ang mosabot kini. Sa katunayan, ang vacuum circuit breakers mao ang importante nga komponente sa modernong sistema sa kuryente, responsable sa pagprotekta sa mga kuryente gikan sa pinsala. Karon, atong i-explore ang importante nga konsepto
Dyson
10/18/2025
Effektibo nga Optymizasyon sa Wind-PV Hybrid System nga may Storage
Effektibo nga Optymizasyon sa Wind-PV Hybrid System nga may Storage
1. Pag-analisa sa mga Katangian sa Generasyon sa Kuryente gikan sa Hangin ug Solar PhotovoltaicAng pag-analisa sa mga katangian sa generasyon sa kuryente gikan sa hangin ug solar photovoltaic (PV) mahimong pundok sa pagdisenyo og komplementaryong sistema. Ang estadistikal nga analisis sa taas nga datos sa hangin ug solar irradiance para sa isyuha nga rehiyon nagpakita nga ang mga resources sa hangin adunay seasonal nga pagkakaiba, uban sa mas taas nga bilis sa hangin sa yelo ug tagsibol ug mas b
Dyson
10/15/2025
Sistema nga Iot nga Gigikanan sa Hybrid nga Wind-Solar Power para sa Real-Time nga Monitoring sa Tubo sa Tubig
Sistema nga Iot nga Gigikanan sa Hybrid nga Wind-Solar Power para sa Real-Time nga Monitoring sa Tubo sa Tubig
I. Kasinatian ug Nagkalabay nga ProblemaKaron, ang mga kompanya sa paghatag og tubig adunay makapadlan nga mga network sa pipeline nga gihatag sa ilalum sa yuta sa urban ug rural nga mga dapit. Ang real-time monitoring sa data sa operasyon sa pipeline mahimong importante alang sa efektibong komando ug kontrol sa produksyon ug distribusyon sa tubig. Isip resulta, kinahanglan nga imbuhan ang daghang mga estasyon sa monitoring sa data sa pipelan. Subalang, dili kadalasan ang adunay matul-an ug hand
Dyson
10/14/2025
Paunsa ang usa ka sistema sa gudang nga may basehan sa AGV
Paunsa ang usa ka sistema sa gudang nga may basehan sa AGV
Sistema nga Intelligente sa Warehouse Logistics Batasan sa AGVHuman sa matangis na pag-abot sa industriya sa logistics, nagdako ang kahigayonan sa yuta, ug tumaas ang gasto sa trabaho, ang mga warehouse—nga nagserbiha isip key logistics hubs—nagpakita og significant challenges. Tungod kay ang mga warehouse naging mas dako, ang frequency sa operasyon nataas, ang komplikado sa impormasyon nataas, ug ang order-picking tasks naging mas mahirap, ang pag-achieve og low error rates ug reduced labor cos
Dyson
10/08/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo