On-Site Testing of SF6 Gas Density Relays: Relevant Issues

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Introduction

SF6 gas is widely used as an insulating and arc-quenching medium in high-voltage and extra-high-voltage electrical equipment due to its excellent insulation, arc-extinguishing properties, and chemical stability. The insulation strength and arc-quenching capability of electrical equipment depend on the density of SF6 gas. A decrease in SF6 gas density can lead to two main hazards:

  • Reduced dielectric strength of the equipment;

  • Decreased interrupting capacity of circuit breakers.

Additionally, gas leakage often leads to moisture ingress, increasing the moisture content of SF6 gas and further degrading insulation performance. Therefore, monitoring the density of SF6 gas is essential for ensuring safe equipment operation.

An SF6 gas density relay (also known as a density monitor, controller, or density gauge) is installed on SF6 electrical equipment to reflect changes in internal gas density. It detects pressure variations to indicate density changes, issuing an alarm signal when density drops to a preset alarm level, and locking out switching operations if it further decreases to a lockout level. Given that its performance directly affects equipment safety, regular testing of its reliability and accuracy is crucial.




1. Types and Operating Principles of SF6 Gas Density Relays

1.1 Mechanical Gas Density Relays

Mechanical relays can be classified by structure into bellows-type and bourdon-tube-type, and by function into those with pressure display and without. Both types use temperature compensation to monitor gas density.

Taking the typical bellows-type as an example (see Figure 1):

  • A pre-charged chamber is filled with SF6 gas at the same pressure as the monitored chamber;

  • A metal bellows is connected to the monitored chamber;

  • When a leak occurs, the internal pressure in the bellows decreases, creating a pressure differential that compresses the bellows.This movement actuates a microswitch via a mechanical linkage,triggering  an alarm or lockout signal.

Since the pre-charged chamber is in the same environment, temperature changes affect both sides equally, enabling automatic temperature compensation.

图片4.png

Figure 1. Principle of Mechanical Gas Density Relay
(Note: 4—microswitch; 3—bimetal strip; 2—metal bellows; 1—pre-charged chamber)

1.2 Digital Gas Density Relays

These relays exploit the strong electronegativity of SF6 molecules. An alpha particle source in an ionization chamber ionizes the gas, and under an applied DC electric field, an ion current is formed. This current is proportional to the gas density. As density decreases, the output current decreases, allowing real-time monitoring.

Advantages of digital density relays include:

  • Direct digital display of pressure, equivalent pressure at  20°C, and equipment temperature;

  • Compatibility with computer systems for online monitoring;

  • Ability to plot leakage trend curves, supporting condition-based maintenance;

  • Full-scale measurement without range switching, with field-adjustable parameters;

  • Output of gas-refill alarm and under-pressure lockout contact signals.

图片5.png

Figure 2. Principle of Digital Gas Density Relay
(Note: Alpha particles in the ionization chamber ionize SF6 gas; electrons migrate to the anode, positive ions return to the emitter, generating a current that is amplified and output)

2. Necessity of On-Site Testing of Density Relays

Density relays can be tested either on-site or in a laboratory. While laboratory testing offers higher precision, it presents several drawbacks:

  • Dismantling breaks the original seal, making reassembly and sealing difficult to guarantee;

  • Precision instruments may lose calibration due to transportation shocks;

  • Tight maintenance schedules make disassembly and reassembly  time-consuming.

Therefore, on-site testing is recommended when feasible, as it is more efficient and safer.


3. Instruments Used for On-Site Testing

Since SF6 electrical equipment must not be contaminated with oil or other gases, only SF6 gas can be used as the test medium. An ideal calibration device should have:

  • An integrated SF6 gas cylinder;

  • Adjustable pressure;

  • Automatic temperature compensation and conversion.

This article introduces the JMD-1A SF6 Gas Density Relay Calibration Unit, which features:

  • Built-in SF6 cylinder and pressure regulation system;

  • Isolates the equipment’s gas circuit during testing, using its own gas supply;

  • Automatically converts measured values to standard pressure at 20°C;

  • Requires annual factory recalibration to ensure accuracy;

  • Accuracy class 0.5, meeting the requirement that “standard  instrument error shall not exceed one-third of the tested instrument’s error” (tested relays are typically below class 1.5), fully satisfying      on-site requirements.


4. Testing Content for Gas Density Relays

4.1 Testing Standards and Frequency

According to GB50150-1991 and DL/T596-1996:

  • New equipment must undergo density relay testing before commissioning;

  • In-service equipment should be tested every 1–3 years, or after major maintenance or when necessary;

  • Action values must comply with manufacturer’s technical specifications;

  • Pressure gauge indication error and hysteresis must be within allowable limits for the specified accuracy class.

4.2 Test Items

Main test items include:

  • Alarm (gas refill) activation pressure;

  • Lockout activation pressure;

  • Lockout return pressure;

  • Alarm return pressure;

  • If equipped with a pressure gauge, its indication must also be      tested.

Pressure gauge testing requirements:

  • At least 5 test points evenly distributed across the range;

  • Two full cycles of pressurization and depressurization;

  • Pressure applied slowly and steadily, with readings taken at  each point;

  • The maximum indication error from the two cycles is taken as the final result.

Action value requirements:

  • Must comply with manufacturer’s specifications;

  • The difference between activation and return pressure should be less than 0.02 MPa;

  • All pressure values must be converted to standard values at 20°C;

  • Record ambient temperature, measured pressure, and converted  20°C pressure.


5. Connection Methods Between Density Relay and Equipment

There are four common connection types:

  • With Isolation Valve
         A valve (FA) is installed between the relay and equipment. During testing, close FA, connect the test head, then open FB to begin testing.

  • With Check Valve
         After removing the relay, the check valve automatically seals the equipment side, allowing direct connection of the test device to the external port.

  • With Check Valve + Plunger Bolt (see Figure 3)
         No disassembly required. Unscrew the plunger bolt at W2; the check valve F1 automatically isolates the gas path, allowing direct connection of the test head.


图片6.png

Figure 3. Schematic of Density Relay with Check Valve and Plunger Bolt
(Labels: B1—density relay; W1—gas charging port; W2—test port; MA—pressure gauge; F1—check valve)

  • Direct Connection Without Isolation
         This is an unreasonable design. If the relay fails, it cannot be replaced or tested online and must wait until major overhaul. It is recommended to install isolation valves during overhaul for future      maintenance.

Conclusion: The first three connection types allow on-site testing; the fourth does not.


6. Precautions for On-Site Calibration

  • Power-Off Operation: Testing must  be conducted with the equipment de-energized. Disconnect control power and   isolate alarm/lockout contacts at the terminal block to prevent unintended      secondary circuit operation.

  • Confirm Connection Type: Connection  structures vary among equipment. Confirm the type before disassembly to  prevent misoperation and gas leakage.

  • Restore Isolation Valves: After  testing, ensure all isolation valves are restored to their correct  positions and verified.

  • Clean Connectors: Clean all piping  connectors before and after testing. Flush with a small amount of SF6 gas  if necessary to prevent contamination or moisture ingress.

  • Sealing Protection: Protect sealing  surfaces, replace with new gaskets, and perform leak detection after  reassembly.

  • Pressure Unit Conversion: The  JMD-1A tester displays gauge pressure. If the relay uses absolute  pressure (e.g., ABB LTB145D circuit breaker), convert units before  comparison.


7. Conclusion

The SF6 gas density relay is a critical component ensuring the safe operation of SF6 electrical equipment. Its operational performance directly impacts system reliability. Therefore, regular on-site testing must be conducted in accordance with relevant regulations to ensure accuracy and reliability. During testing, strict adherence to prescribed test cycles, procedures, and precautions is essential to eliminate safety hazards and prevent erroneous conclusions.




Give a tip and encourage the author!
Recommended
Sealing Structure for Oil-Filled SF6 Gas Density Relay Contact Lead Wires
Sealing Structure for Oil-Filled SF6 Gas Density Relay Contact Lead Wires
I. CLAIMS A sealing structure for lead wires of contacts in an oil-filled SF6 gas density relay, characterized by comprising a relay housing (1) and a terminal base (2); the terminal base (2) comprising a terminal base housing (3), a terminal base seat (4), and conductive pins (5); the terminal base seat (4) being disposed inside the terminal base housing (3), the terminal base housing (3) being welded onto the surface of the relay housing (1); a central through-hole (6) being provided at the ce
Dyson
10/27/2025
SF6 Density Relay Oil Leakage: Causes, Risks & Oil-Free Solutions
SF6 Density Relay Oil Leakage: Causes, Risks & Oil-Free Solutions
1. Introduction SF6 electrical equipment, renowned for its excellent arc-quenching and insulating properties, has been widely applied in power systems. To ensure safe operation, real-time monitoring of SF6 gas density is essential. Currently, mechanical pointer-type density relays are commonly used, providing functions such as alarm, lockout, and on-site display. To enhance vibration resistance, most of these relays are filled internally with silicone oil.However, oil leakage from density relays
Felix Spark
10/27/2025
Why You Can't Remove Siemens GIS Bushing Cover for PD Testing
Why You Can't Remove Siemens GIS Bushing Cover for PD Testing
As the title suggests, when performing live partial discharge (PD) testing on Siemens GIS using the UHF method—specifically by accessing the signal through the metal flange of the bushing insulator—you must not directly remove the metal cover on the bushing insulator.Why?You won’t realize the danger until you try. Once removed, the GIS will leak SF₆ gas while energized! Enough talk—let’s go straight to the diagrams.As shown in Figure 1, the small aluminum cover inside the red box is typically th
James
10/24/2025
Problems and Precautions in the Operation of Distribution Boxes
Problems and Precautions in the Operation of Distribution Boxes
Outdoor low-voltage power distribution boxes (hereinafter referred to as "distribution boxes") are low-voltage distribution equipment used in 380/220V power supply systems to receive and distribute electrical energy. They are generally installed at locations such as the low-voltage side of distribution transformers. The interior is typically equipped with protective devices like fuses, leakage protectors, and surge arresters; control devices like contactors, circuit breakers, load switches, and
Felix Spark
10/17/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.