What are the requirements for inspecting and maintaining a transformer's no-load tap changer?

Leon
Field: Fault Diagnosis
China
  1. The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions.

  2. The insulating cylinder of the tap changer shall be intact and undamaged, with good insulation properties, and its support bracket shall be firmly secured. The allowable exposure time of the tap changer to air shall be the same as that of the core assembly. If the tap changer is disassembled during maintenance and cannot be reinstalled promptly, it shall be immersed in qualified transformer oil.

  3. All tap changer insulation shall be in good condition, securely bound, neatly arranged, and all joints shall be well soldered with no signs of desoldering or overheating.

  4. The surfaces of all fixed contact posts and moving contact rings shall be smooth, free of oil deposits, oxidation films, or burn marks. The silver-plated layer on the contact surfaces shall show no signs of peeling.

  5. Rotate the tap changer through all tap positions to inspect the contact condition between each moving contact ring and moving contact post, as well as the spring condition. Check the contact pressure—when tested with a feeler gauge, it should not be possible to insert the gauge between the contact surfaces. The contact resistance between any two fixed contact posts shall not exceed 500 μΩ. After inspection, the tap changer shall be returned to its original operating position.

  6. If the tap changer is removed during maintenance, clear markings and records must be made. After reinstallation, the voltage ratio shall be measured and verified.

  7. As part of preventive maintenance, the tap changer shall be rotated annually: move it 10–15 times back and forth from its operating position to remove oil sludge, oxidation films, or other deposits from the contact surfaces through friction. Then return it to the operating position and measure the DC resistance, which must be acceptable (i.e., not higher than the previous measurement result).

Give a tip and encourage the author!

Recommended

What’s the Difference Between Rectifier Transformers and Power Transformers?
What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
01/29/2026
How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
Analysis of Four Major Power Transformer Burnout Cases
Case OneOn August 1, 2016, a 50kVA distribution transformer at a power supply station suddenly sprayed oil during operation, followed by burning and destruction of the high-voltage fuse. Insulation testing revealed zero megohms from the low-voltage side to ground. Core inspection determined that damage to the low-voltage winding insulation had caused a short circuit. Analysis identified several primary causes for this transformer failure:Overloading: Load management has historically been a weak
12/23/2025
Power Transformer Condition Monitoring: Reducing Outages & Maintenance Costs
1. Definition of Condition-Based MaintenanceCondition-based maintenance refers to a maintenance approach where repair decisions are determined by the real-time operational status and health condition of equipment. There are no fixed schedules or predetermined maintenance dates. The prerequisite for condition-based maintenance is the establishment of equipment parameter monitoring systems and comprehensive analysis of various operational information, enabling reasonable maintenance decisions base
12/22/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.