• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the common issues in SF₆ gas circuit faults and circuit breaker failure-to-operate faults?

Felix Spark
Field: Failure and maintenance
China

This article categorizes faults into two main types: SF₆ gas circuit faults and circuit breaker failure-to-operate faults. Each is described below:

1.SF₆ Gas Circuit Faults

1.1 Fault Type: Low gas pressure, but density relay does not trigger alarm or lockout signal

Cause: Faulty density gauge (i.e., contact not closing)
Inspection & Handling: Calibrate actual pressure using a standard gauge. If confirmed, replace the density gauge.

1.2 Density Relay Triggers Alarm or Lockout Signal (but pressure is normal)

Cause 1: Signal crosstalk
Inspection & Handling 1: Disconnect the alarm wiring and measure the contact on the density gauge itself. If the contact is normal, resolve the signal crosstalk issue.

Cause 2: Voltage crosstalk
Inspection & Handling 2: Disconnect the alarm wiring and measure the contact on the density gauge. If the contact is normal, troubleshoot and fix the voltage crosstalk.

Cause 3: Faulty density gauge
Inspection & Handling 3: Disconnect the alarm wiring and measure the contact. If confirmed closed when it should not be, replace the density gauge.

1.3 Density Relay Triggers Alarm or Lockout Signal (pressure is low)

Cause: Leak point in the circuit breaker — such as at the charging valve, column flange surface, or sand hole in the rotating housing
Inspection & Handling: Perform lateral pressure comparison; if only one phase shows low pressure and instrument error is ruled out, conduct leak detection and repair accordingly.

1.4 Pressure Too High

Cause 1: Overcharging during gas filling
Inspection & Handling 1: Review gas replenishment records and calibrate the pressure gauge. If confirmed, release gas (pressure must not exceed 0.3 atm above rated, regardless of temperature).

Cause 2: Faulty density gauge
Inspection & Handling 2: Calibrate actual pressure with a standard gauge. If inaccurate, replace the density gauge.

Cause 3: Voltage crosstalk
Inspection & Handling 3: If pressure is normal and no motor operation signal precedes lockout, inspect the secondary circuit and correct any issues.

2.Circuit Breaker Failure-to-Operate Faults

2.1 Circuit Breaker Fails to Operate

Cause 1: Control power not energized
Inspection & Handling 1: Visually inspect relays — if all are de-energized, restore control power.

Cause 2: Remote/local switch is set to "Local" position
Inspection & Handling 2: Check for control circuit disconnection signal. Switch selector to "Remote" mode.

Cause 3: High resistance in opening/closing circuit contacts
Inspection & Handling 3: Measure total resistance of the trip/close circuit. Identify faulty component and repair or replace.

Cause 4: Damaged component in trip/close circuit
Inspection & Handling 4: Measure resistance of the trip/close circuit. Locate and replace the faulty component.

Cause 5: Loose auxiliary switch wiring
Inspection & Handling 5: Measure circuit resistance, identify loose connections, and re-terminate securely.

Cause 6: Faulty mechanism or auxiliary switch
Inspection & Handling 6: Visually inspect mechanism and auxiliary switch. Develop repair plan based on findings.

2.2 Minimum Operating Voltage Does Not Meet Standards

Cause 1: Bypassing lockout relay and auxiliary switch contacts for convenience
Inspection & Handling 1: When testing coil minimum operating voltage, the test must go through auxiliary switch S1 and lockout contact, using momentary operation. Perform test at the terminal block in the circuit breaker control cabinet.

Cause 2: Insufficient test instrument power
Inspection & Handling 2: Before testing, verify instrument reliability (e.g., check for AC or DC offset). Replace the instrument and retest.

Cause 3: Discrepancy between instrument output voltage and display reading
Inspection & Handling 3: Replace or recalibrate the test instrument.

Cause 4: Test instrument outputs AC component (waveform superposition affects low-voltage accuracy and may burn out coil or resistor; must be <10V)
Inspection & Handling 4: Before testing, use a multimeter on AC voltage range to measure AC component output. Replace the instrument if present.

Cause 5: Test instrument outputs DC component
Inspection & Handling 5: Before testing, use a multimeter on DC voltage range to measure DC component output. Replace the instrument if present.

Cause 6: Transient interference spike superimposed on output pulse, causing abnormally low minimum operating voltage
Inspection & Handling 6: Monitor output pulse with an oscilloscope. Confirm issue and replace the instrument; compare results with different testers.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.