• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Barra Protection | Barra Diffarential Protection Scheme

Electrical4u
Electrical4u
فیلڈ: Karkashin Kuliya da Dukkana
0
China

A tafin lokaci na gida an yi amfani da mafi girman relays ta karamin hanyar tsakiyar karamin kasa daga busbar protection. Amma yana neman cewa abu mai lalacewa ko mutumai da ake kara da busbar ba zan iya haifar da systemin busbar. Saboda haka, wakar tsakitsakin relays masu busbar protection suna yi ne a lokacin da ke da zaman. Don haka, idan abu mai lalacewa ya faru a kan busbar, zai iya yi rike da zaman don in bude bus daga mafi girma wanda ya zama da lafiya da sauransu.
A tafin lokacin, an yi amfani da relays masu hanyar tsakitsa da biyu a kan feeders masu inganta, da tsawonsa na 0.3 zuwa 0.5 detari don busbar protection.
Amma wannan yanayi na da mafi kyau. Wannan yanayi ba zan iya sanya babban abubuwan da suka haifar da busbar.
A tafin lokacin, systemin karamin kasa na yi aiki da karamin kasa mai yawa. Saboda haka, idan akwai hadin karamin kasa a duk systemin bus, zai kasance halaye mai yawa ga kamfanin. Saboda haka, ita ce da ya danganta in bude kawai babban abubuwan da suka haifar da busbar a lokacin da abu mai lalacewa ya faru.

Wannan yanayi na da mafi kyau wajen tsakitsa da hanyar tsakitsa da biyu shine, idan lokacin da ake bude abu mai lalacewa, tsawon bude ba zai zama da tsawon da ya danganta don in tabbatar da ciyaron system.
Don in taimaka da kuma haɗa da abubuwan da aka bayar, an yi amfani da yanayi masu tsakitsa da hanyar busbar differential protection da tsawonsa na 0.1 detari, a kan duk SHT bus systems.

Differential Busbar Protection

Current Differential Protection

Yanayin busbar protection, tana ƙunshi, Kirchoff’s current law, wanda ya ce, jami'ar karamin kasa da ke samu cikin node elektriki ce da ke fito da jami'ar karamin kasa da ke rage node.
Saboda haka, jami'ar karamin kasa da ke samu cikin bus section ce da ke fito da jami'ar karamin kasa da ke rage bus section.

Prinsipin busbar differential protection ce da ya fiye. A wannan, secondaries of CTs suna kara da parallel. Yana nufin, S1 terminals of all CTs connected together and forms a bus wire. Similarly S2 terminals of all CTs connected together to form another bus wire.
A tripping relay is connected across these two bus wires.
busbar protection scheme

A nan, a cikin figure above, ana ƙarin cewa, idan lokacin da ya da shiga, A, B, C, D, E and F carries current IA, IB, IC, ID, IE and IF.
Idan kana ƙarin cewa, saboda Kirchoff’s current law,

Essentially all the CTs used for differential busbar protection are of same current ratio. Hence, the summation of all secondary currents must also be equal to zero.

A nan, cewa karamin kasa ta relay connected in parallel with all CT secondaries, is iR, and iA, iB, iC, iD, iE and iF are secondary currents.
A nan, za a ƙara KCL at node X. As per KCL at node X,

Saboda haka, ita ce da ya danganta cewa lokacin da ya da shiga, ba ake samu karamin kasa a kan busbar protection tripping relay. This relay is generally referred as Relay 87. A nan, cewa abu mai lalacewa ya faru a kan duk feeders, waje protected zone. A wannan lokacin, abu mai lalacewa zai taka primary of the CT of that feeder. This fault current is contributed by all other feeders connected to the bus. So, contributed part of fault current flows through the corresponding CT of respective feeder. Hence at that faulty condition, if we apply KCL at node K, we will still get, iR = 0.
busbar protection
Yana nufin, lokacin da ya da abu mai lalacewa waje, ba ake samu karamin kasa a kan relay 87. A nan, za a ƙara abin da abu mai lalacewa ya faru a kan bus itself.
A wannan lokacin, abu mai lalacewa tana ƙunshi, abubuwan da suka haifar da bus. Saboda haka, a wannan lokacin, jami'ar abubuwan da suka haifar da abu mai lalacewa ce da ke fito da jami'ar abu mai lalacewa.
A lokacin da ya da abu mai lalacewa, ba ake samu CT. (a lokacin da ya da abu mai lalacewa waje, both fault current and contributed current to the fault by different feeder get CT in their path of flowing).
busbar protection
Jami'ar abubuwan da suka haifar da abu mai lalacewa ba zai zama da zero. Ita ce da ke fito da secondary equivalent of faulty current.
A nan, idan a ƙara KCL at the nodes, zai iya samu ma'anar iR.
Don haka, a wannan lokacin, karamin kasa tana bude a kan 87 relay and it makes trip the circuit breaker corresponding to all the feeders connected to this section of the busbar.
As all the incoming and outgoing feeders, connected to this section of bus are tripped, the bus becomes dead.
This differential busbar protection scheme is also referred as current differential protection of busbar.

Differential Protection of Sectionalized Bus

During explaining working principle of current differential protection of busbar, we have shown a simple non sectionalized busbar. But in moderate high voltage system electrical bus sectionalized in than one sections to increase stability of the system. It is done because, fault in one section of bus should not disturb other section of the system. Hence during bus fault, total bus would be interrupted.
Let us draw and discuss about protection of busbar with two sections.
sectionalized bus protection
Here, bus section A or zone A is bounded by CT1, CT2 and CT3 where CT1 and CT2 are feeder CTs and CT3 is bus CT.
Similarly bus section B or zone B is bounded by CT4, CT5 and CT6 where CT4 is bus CT, CT5 and CT6 are feeder CT.
Therefore, zone A and B are overlapped to ensure that, there is no zone left behind this busbar protection scheme.
ASI terminals of CT1, 2 and 3 are connected together to form secondary bus ASI;
BSI terminals of CT4, 5 and 6 are connected together to form secondary bus BSI.
S2 terminals of all CTs are connected together to form a common bus S2.
Now, busbar protection relay 87A for zone A is connected across bus ASI and S2.
Relay 87B for zone B is connected across bus BSI and S2.
This section busbar differential protection scheme operates in some manner simple current differential protection of busbar.
That is, any fault in zone A, with trip only CB1, CB2 and bus CB.
Any fault in zone B, will trip only CB5, CB6 and bus CB.
Hence, fault in any section of bus will isolate only that portion from live system.
In current differential protection of busbar, if CT secondary circuits, or bus wires is open the relay may be operated to isolate the bus from live system. But this is not desirable.

Ba da kyau kuma kara mai rubutu!
Makarantarƙi:
Tambayar Da Yawanci
Me Kowane Da Tururun Reaktor? Ayyuka Masu Muhimmanci a Tattalin Nau'i
Me Kowane Da Tururun Reaktor? Ayyuka Masu Muhimmanci a Tattalin Nau'i
Rikitar (Indukta): Tushen da Nau'ukanRikitar, wanda ake kira indukta, ya fara zama a cikin al'umma a lokacin da adan ya gudana a kan hanyar. Saboda haka, akwai inductance a cikin duk hanyar da ake gudana abubuwa. Amma, inductance na hanyar mai zurfi ita ce mai yawa da take fara zama a cikin al'umma. Rikitar masu amfani a halitta suka fito a cikin solenoid, wanda ake kira rikitar air-core. Don samun inductance, ana saka core mai ferromagnetic a cikin solenoid, wanda ya fara zama iron-core reactor
James
10/23/2025
35kV Distribusi Linin Yawan Ƙasa Dajiya Daɗi
35kV Distribusi Linin Yawan Ƙasa Dajiya Daɗi
Lambar Taurari: Kungiyar Yawan KuliLambar taurari suna kungiyar yawan kuli. A cikin zabe na gaba da darasi, an yi nasara lambar taurari (don inganta ko fitowa) da suka fi shiga, kamar yadda da suka fi sanya don masu taurari. Ba a nan bayan, an yi nasara kuli na gaba da darasi kan suka yi nasara a kan taurari, kuma an yi nasara kuli a jama'a masu sauki. A cikin kungiyoyi na taurari, ana iya faru abubuwa kamar mafi girma a cikin tsawon gaba, mafi girma (mai mu'amala), da kuma mafi girma a cikin ts
Encyclopedia
10/23/2025
Na Bincike Masu Amfani Da Kisan Tashin Yawan Kirkiro Daga 110kV: Inganci Da Gaskiya
Na Bincike Masu Amfani Da Kisan Tashin Yawan Kirkiro Daga 110kV: Inganci Da Gaskiya
Yadda na Kula Tsarin Maimakon Da Duk 110kVA cikin tattalin karamin zabe, maimakon da duka suna muhimmanci wajen mamaye zabe daga hankali mai yawa. Don yanayi da ke 110kV ko kadan—kamar 35kV ko 10kV sub-stations—yadda na kula tsarin maimakon ta hanyar harkokin zai yi girma wajen iya gaba haske da ya faruwa kan hankalin karamin zabe. Zaman lafiya wannan yadda ce ita ce amfani da teknologi na harkokin zai don inganta halittukan maimakon ba tare da kawo karshen tattalin karamin zabe.Sassan yadda na
Oliver Watts
10/23/2025
Matsayin Yadda Ƙarƙashin MVDC Shaida? Faɗila, Dangantaka da Tashaya na Gaba
Matsayin Yadda Ƙarƙashin MVDC Shaida? Faɗila, Dangantaka da Tashaya na Gaba
Tattalin tsari na kwayoyin karamin kashi (MVDC) yana cikin tashar karamin kashi, wanda ake fadada don dole kungiyoyi na cikin AC na gaba-gaban a tushen kayan aiki. Ta karama kashi a kan DC da kwayoyin karamin kashi daga 1.5 kV zuwa 50 kV, ta haɗa muhimmin abubuwa na karamin kashi a kwayoyin takwas da dalilai na karamin kashi a kwayoyin ƙasa. A lokacin da take daɗe wannan tashar karamin kashi na kwayoyin takwas da kuma tushen karamin kashi masu zamani, MVDC yana faruwa a matsayin bincike mafi muh
Echo
10/23/2025
Makarantar Mai Yawanci
Aika tambaya
Kwamfuta
Samun IEE Business Application
Yi amfani da IEE-Business app don samun abubuwan aikin, samun halayyin, haɗi da malamai, kuma kai tsauraran takaiddun kasoshin duka lokaci, duka wurin—dole bai karfin takamaltar hulɗin ku na alintakargida da kasuwanci.