Back-to-Back Test (Sumpner’s Test) on Transformer

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Definition

Conducting a full - load test on a small transformer is quite convenient. However, when it comes to large transformers, this task becomes extremely challenging. The maximum temperature rise in a large transformer is typically determined through a full - load test. This particular test is also known as the back - to - back test, regenerative test, or Sumpner’s test.

Finding a suitable load that can absorb the full - load power of a large transformer is not an easy feat. As a result, a significant amount of energy would be wasted if a traditional full - load test were to be carried out. The back - to - back test is designed to determine the maximum temperature rise in a transformer. Thus, the load is selected in accordance with the transformer's capacity.

Back - to - Back Test Circuit

For the back - to - back test, two identical transformers are utilized. Let's assume that Tr1 and Tr2 are the primary windings of the transformers, which are connected in parallel with each other. A nominal rated voltage and frequency are supplied to their primary windings. Voltmeters and ammeters are connected on the primary side to measure the input voltage and current.

The secondary windings of the transformers are connected in series with each other, but with opposite polarities. A voltmeter V2 is connected across the terminals of the secondary windings to measure the voltage.

To determine the series - opposition connection of the secondary windings, any two terminals are connected, and a voltmeter is connected across the remaining terminals. If the connection is in series - opposition, the voltmeter will show a zero reading. The open terminals are then used to measure the parameters of the transformer.

插图.jpg

Determination of Temperature Rise

In the above figure, terminals B and C are connected to each other, and the voltage is measured across terminals A and D.

The temperature rise of the transformers is ascertained by measuring the temperature of their oil at specific time intervals. Since the transformers operate in a back - to - back configuration for an extended period, the oil temperature gradually increases. By monitoring the oil temperature, the ability of the transformers to withstand high temperatures can be determined.

Determination of Iron Loss

The wattmeter W1 measures the power loss, which is equivalent to the iron loss of the transformer. To determine the iron loss, the primary circuit of the transformer is maintained in a closed state. With the primary circuit closed, no current passes through the secondary windings of the transformer, causing the secondary winding to behave as an open circuit. The wattmeter is connected to the secondary terminals to measure the iron loss.

Determination of Copper Loss

The copper loss of the transformer is determined when the full - load current flows through both its primary and secondary windings. An additional regulating transformer is employed to excite the secondary windings. The full - load current flows from the secondary to the primary winding. The wattmeter W2 measures the full - load copper loss of the two transformers.

Give a tip and encourage the author!
Recommended
What are the safety precautions and guidelines for using AC load banks?
What are the safety precautions and guidelines for using AC load banks?
AC load banks are electrical devices used to simulate real-world loads and are widely applied in power systems, communication systems, automation control systems, and other fields. To ensure personal and equipment safety during use, the following safety precautions and guidelines must be observed:Select an appropriate AC load bank: Choose an AC load bank that meets actual requirements, ensuring its capacity, voltage rating, and other parameters satisfy the intended application. Additionally, sel
Echo
11/06/2025
What should be noted when installing a Type K thermocouple?
What should be noted when installing a Type K thermocouple?
Installation precautions for Type K thermocouples are critical to ensuring measurement accuracy and extending service life. Below is an introduction to the installation guidelines for Type K thermocouples, compiled from highly authoritative sources:1.Selection and Inspection Select the appropriate thermocouple type: Choose the right thermocouple based on the temperature range, medium properties, and required accuracy of the measurement environment. Type K thermocouples are suitable for temperatu
James
11/06/2025
Toroidal vs Square Transformers: Key Differences
Toroidal vs Square Transformers: Key Differences
What Is a Toroidal Transformer?A toroidal transformer is a major type of electronic transformer that has been widely used in household appliances and other electronic equipment with higher technical requirements. Its primary applications are as a power transformer and an isolation transformer. Abroad, toroidal transformers are already available in complete series and are extensively used in computers, medical equipment, telecommunications, instruments, and lighting applications.In China, toroida
Dyson
11/06/2025
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.