• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Diagnose Faults in H59 Distribution Transformers by Listening to Their Sounds

Noah
Noah
Field: Design & Maintenance
Australia

In recent years, the accident rate of H59 distribution transformers has shown an upward trend. This article analyzes the causes of failures in H59 distribution transformers and proposes a series of preventive measures to ensure their normal operation and provide effective assurance for power supply.

H59 distribution transformers play a vital role in power systems. With the continuous expansion of power system scale and the increasing single-unit capacity of transformers, any transformer failure not only causes significant losses to enterprises but also greatly disrupts normal production and daily life for the public. As a manager responsible for high-voltage distribution systems, I have accumulated practical experience in my work. By actively analyzing the causes of accidents involving H59 distribution transformers and identifying corresponding countermeasures, we can effectively guarantee the safe operation of the power system.

1.Common Faults of H59 Distribution Transformers

During energization and operation, distribution transformers commonly exhibit the following faults and abnormal phenomena:

  • After being re-energized following a shutdown or during trial energization, abnormal voltage is often observed—such as two phases showing high voltage while one phase is low or reads zero; in some newly commissioned transformers, all three-phase voltages are excessively high, causing certain electrical equipment to burn out due to overvoltage.

  • High-voltage fuses blow, preventing successful energization.

  • Fuses blow during thunderstorms, resulting in failed energization.

  • Abnormal transformer sounds, such as “zizi” (buzzing) or “pipa” (crackling); during operation, it may emit frog-like “jiwa jiwa” calls.

  • Burned high-voltage terminal posts, severely damaged high-voltage bushings with visible flashover marks.

  • Under normal cooling conditions, transformer temperature abnormally rises continuously.

  • Excessive oil discoloration and presence of carbon particles in the oil.

  • Transformer emits roaring sounds, oil sprays out from the pressure relief device or conservator tank, and the tank or radiator tubes deform, leak, or seep oil.

2. Fault Diagnosis Based on Transformer Sounds

2.1 Sound During Phase Loss

When a phase loss occurs:

  • If phase B is open, energizing phase B produces no sound; only when phase C is energized does sound appear.

  • If phase C is open, the sound remains unchanged and identical to the two-phase condition.

Main causes of phase loss include:

  • Missing one phase in the power supply.

  • Blown high-voltage fuse in one phase of the transformer.

  • Broken high-voltage lead due to improper handling during transportation (the conductor is broken but not grounded), especially since high-voltage leads are relatively thin and prone to vibration-induced breakage.

3. Other

3.1 Improper Tap Changer Position or Poor Contact

If the tap changer is not fully engaged during energization, a loud “jiu jiu” sound occurs, potentially blowing the high-voltage fuse. If contact is poor, a faint “zizi” sparking sound is heard. Under increased load, the tap changer contacts may burn out. In such cases, immediate de-energization and repair are required.

3.2 Foreign Objects or Loose Core-Through Bolts

When the through-bolt that clamps the transformer core becomes loose, or if nuts or small metal parts fall into the transformer, a “ding ding dang dang” knocking sound or a “hu… hu…” noise may be heard.

3.3 Dirty or Damaged High-Voltage Bushings on H59 Transformers

When the high-voltage bushings of an H59 transformer become dirty, lose surface glaze, or crack, surface flashover occurs, producing a “si si” or “chi chi” sound. Sparks may be visible at night.

3.4 Broken Core Grounding Connection

If the transformer core grounding wire breaks, a faint “bi bo bi bo” discharge sound is produced.

3.5 Internal Discharge

During energization, a crisp “pi pa pi pa” metallic sound indicates discharge from a conductor through the oil surface to the tank wall. If caused by insufficient insulation clearance, the core must be lifted for inspection, and insulation should be reinforced or additional insulating barriers installed.

3.6 External Line Break or Short Circuit

  • When a conductor breaks at a connection point or T-junction and intermittently makes contact in windy conditions, arcing or sparking occurs, causing the transformer to emit a frog-like “jiwa jiwa” sound.

  • When a ground fault or short circuit occurs on the low-voltage line, the transformer emits a “hong hong” (rumbling) sound.

  • If the short-circuit point is very close, the transformer produces a tiger-like roar.

3.7 Transformer Overload

When the H59 distribution transformer is severely overloaded, it emits a deep, low-pitched “weng weng” hum, similar to a heavily loaded aircraft engine.

3.8 Excessive Voltage

When supply voltage is too high, the transformer becomes over-excited, resulting in louder and sharper operating noise.

3.9 Winding Short Circuit
When interlayer or interturn short circuits occur in the windings and cause burning, the transformer emits a “gu du gu du” sound resembling boiling water.

There are many factors causing abnormal sounds in H59 distribution transformers, and fault locations vary. Only through continuous accumulation of experience can accurate judgments be made. Understanding potential faults during daily operation, strengthening routine inspections and maintenance, implementing regular scheduled maintenance (including minor and major overhauls), and employing scientific diagnostic methods are essential to ensuring the long-term, safe operation of H59 distribution transformers. Only by rationally utilizing electrical equipment, enhancing scientific management of transformers during operation, and strictly adhering to operational procedures can we establish a solid foundation for reliable power supply services.

Give a tip and encourage the author!
Recommended
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
Avoid H59 Transformer Failure with Proper Inspection & Care
Avoid H59 Transformer Failure with Proper Inspection & Care
Measures to Prevent H59 Oil Immersed Power Distribution Transformer from Burning OutIn power systems, H59 Oil Immersed Power Distribution Transformer play an extremely critical role. Once burned out, they can cause widespread power outages, directly or indirectly affecting the production and daily lives of a large number of electricity users. Based on the analysis of multiple transformer burnout incidents, the author believes that a considerable number of such failures could have been avoided or
Noah
12/06/2025
Top Causes of H59 Distribution Transformer Failure
Top Causes of H59 Distribution Transformer Failure
1. OverloadFirst, with the improvement of people's living standards, electricity consumption has generally increased rapidly. The original H59 distribution transformers have small capacity—“a small horse pulling a big cart”—and cannot meet user demands, causing the transformers to operate under overload conditions. Second, seasonal variations and extreme weather conditions lead to peak electricity demand, further causing H59 distribution transformers to run overloaded.Due to long-term overload o
Felix Spark
12/06/2025
How to Diagnose and Eliminate Transformer Core Grounding Faults
How to Diagnose and Eliminate Transformer Core Grounding Faults
The windings and core of a transformer are the primary components responsible for transmitting and transforming electromagnetic energy. Ensuring their reliable operation is a major concern. Statistical data shows that core-related issues account for the third-highest cause of transformer failures. Manufacturers have paid increasing attention to core defects and have implemented technical improvements regarding reliable core grounding, core ground monitoring, and ensuring single-point grounding.
Felix Spark
12/04/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.