Transformer Protection Systems: Gas Protection, Overcurrent, and Differential Relay Design
For short-circuit faults on transformer lead-out wires, bushings, and internal components, appropriate protective devices shall be installed, and shall comply with the following provisions: Transformers with a capacity of 10 MVA or above operating individually, and transformers with a capacity of 6.3 MVA or above operating in parallel, shall be equipped with pilot differential protection. Important transformers with a capacity of 6.3 MVA or below operating individually may also be equipped with