• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Protection Systems: Gas Protection, Overcurrent, and Differential Relay Design

Noah
Field: Design & Maintenance
Australia

For short-circuit faults on transformer lead-out wires, bushings, and internal components, appropriate protective devices shall be installed, and shall comply with the following provisions:

  • Transformers with a capacity of 10 MVA or above operating individually, and transformers with a capacity of 6.3 MVA or above operating in parallel, shall be equipped with pilot differential protection. Important transformers with a capacity of 6.3 MVA or below operating individually may also be equipped with pilot differential protection.

  • Transformers below 10 MVA may be equipped with instantaneous overcurrent protection and overcurrent protection. For transformers of 2 MVA and above, if the sensitivity factor of the instantaneous overcurrent protection does not meet requirements, pilot differential protection is recommended.

  • For transformers with a capacity of 0.4 MVA and above, primary voltage of 10 kV or below, and delta-star winding connections, two-phase three-relay overcurrent protection may be used.

  • All protective devices specified above shall operate to trip circuit breakers on all sides of the transformer.

During transformer operation, internal faults may sometimes be difficult to detect and handle promptly, potentially leading to accidents. The installation of gas relay protection can help prevent such incidents to a certain extent.

Introduction to Gas Protection

Gas protection is one of the main protections for transformers and belongs to non-electrical protection. It is divided into light gas protection and heavy gas protection. The operating principles differ: Light gas protection operates when minor internal faults cause insulation oil to decompose and generate gas due to heating. The accumulated gas in the upper part of the relay causes the open cup to lose buoyancy and sink, actuating the reed contact to close and send an alarm signal. Heavy gas protection operates when a serious internal fault causes the oil to rapidly expand due to heating or arcing, generating a large volume of gas and a high-speed oil flow toward the oil reservoir. This flow impacts the baffle inside the relay, overcoming spring resistance and moving the magnet to close the reed contact, resulting in a trip command. It should normally be set to trip mode. In addition to gas protection, non-electrical protections for large oil-immersed transformers typically include pressure relief and sudden pressure change protection.

The main difference between light and heavy gas protection lies in the relay's setting values: light gas protection only issues an alarm signal without tripping, while heavy gas protection directly initiates a trip.

The zero-sequence voltage equals the vector sum of the three-phase voltages. The calculation method for zero-sequence current is similar.

The principle of heavy gas protection is based on a float and reed relay design. The relay's oil chamber is connected to the transformer tank. When a fault generates gas, the accumulation of gas lowers the float to a certain position, closing the first-stage contact to trigger a light gas alarm. As gas continues to accumulate, the float descends further, activating the second-stage contact, closing the heavy gas circuit, and tripping the circuit breaker.

Difference in Operating Principles between Light and Heavy Gas Protection

Light gas relays consist of an open cup and reed contacts, and operate to send a signal. Heavy gas relays consist of a baffle, spring, and reed contacts, and operate to trip.

Under normal operation, the relay is filled with oil, and the open cup floats due to buoyancy, keeping the reed contacts open. When a minor internal fault occurs, the slowly rising gas enters the relay, lowering the oil level. The open cup rotates counterclockwise around its pivot, closing the reed contact and issuing an alarm signal. When a serious internal fault occurs, a large volume of gas is rapidly generated, causing a sudden increase in tank pressure and a high-speed oil flow toward the oil reservoir. This flow impacts the relay's baffle, which overcomes the spring resistance, moves the magnet toward the reed contact, closes the contact, and triggers a trip.

The relay's relay characteristic refers to the relationship between its input and output quantities throughout the entire operation process. Whether operating or returning, the relay moves directly from its initial position to its final position without stopping at any intermediate position. This "step-change" characteristic is known as the relay characteristic.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.