What is the power angle and load in the case of a synchronous motor?

11/25/2024

Power Angle and Load in Synchronous Motors

The power angle (Power Angle) and load in synchronous motors have a close relationship. Understanding these concepts helps to better grasp the working principle and performance of synchronous motors. Here is a detailed explanation:

1. Power Angle (Power Angle)

Definition

Power Angle (also known as torque angle or electric angle, denoted as δ) is the phase difference between the rotor magnetic field axis and the stator magnetic field axis. It represents the position of the rotor magnetic field relative to the stator magnetic field.

Impact

  • Power Transfer: The power angle directly affects the active power absorbed by the synchronous motor from the grid. The larger the power angle, the more active power the motor absorbs.

  • Stability: An excessively large power angle can cause the motor to lose synchronization, leading to a "slip" phenomenon.

2. Load

Definition

Load refers to the mechanical load driven by the synchronous motor, typically expressed in power units (kilowatts or horsepower).

Relationship

Power Angle and Load Relationship: The power angle δ and the load P of a synchronous motor have a nonlinear relationship, which can be expressed by the following formula:

e9b7f280c00f91f23a42617692f3a6a9.jpeg

Where:

  • P is the active power absorbed by the motor (watts or kilowatts).

  • E is the no-load EMF (electromotive force) of the motor (volts).

  • V is the grid voltage (volts).

  • Xs is the synchronous reactance of the motor (ohms).

  • δ is the power angle (radians).

3. Graphical Representation of Power Angle Characteristics

Characteristics Curve

  • Characteristics Curve: The relationship between power angle and load can be represented by a characteristic curve. This curve is typically nonlinear and follows a sine function.

  • Maximum Power Point: When the power angle δ reaches 90 degrees (π/2 radians), the motor absorbs the maximum active power Pmax :

33bf6ca92d98fe5cb6dbc986a65e0938.jpeg

Slip Point: When the power angle exceeds 90 degrees, the motor may lose synchronization, leading to a "slip" condition.

4. Influencing Factors

Grid Voltage

Voltage Variation: Changes in grid voltage V affect the relationship between the power angle and load. An increase in voltage allows the motor to absorb more active power.

Motor Parameters

Synchronous Reactance: Synchronous reactance Xs  is an important internal parameter of the motor, affecting the relationship between power angle and load. A higher synchronous reactance results in less active power absorption by the motor.

Load Variation

Increase in Load: When the load increases, the motor automatically adjusts the power angle to absorb more active power until a new equilibrium point is reached.

5. Summary

  • Power Angle δ: Represents the phase difference between the rotor magnetic field and the stator magnetic field, directly influencing the active power absorbed by the motor.

  • Load P: The mechanical load driven by the motor, having a nonlinear relationship with the power angle.

  • Relationship Formula: P=(EV/Xs) sin(δ) describes the relationship between power angle and load.

  • Maximum Power Point: When the power angle δ reaches 90 degrees, the motor absorbs the maximum active power Pmax=EV/ Xs.

  • Slip Point: When the power angle exceeds 90 degrees, the motor may lose synchronization.

Understanding these concepts helps to better design and operate synchronous motors, ensuring their stable operation under various conditions. 

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Ensuring Reliability: A Deep Dive into Transformer Maintenance
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
What factors need to be considered when designing a transformer?
What factors need to be considered when designing a transformer?
Transformer design is a complex process that requires consideration of multiple factors to ensure safe and efficient operation. In addition, compliance with international and local regulations is essential to guarantee that transformers meet safety and performance standards. Below are key factors to consider in transformer design and the relevant regulations to follow:Transformer Design Factors: Voltage and Frequency: Determine the input and output voltage levels and the operating frequency. The
Vziman
09/02/2025
What failure modes are possible in a transformer? How to identify and fix these failures?
What failure modes are possible in a transformer? How to identify and fix these failures?
Transformers are critical components in power systems, and various failure modes can affect their operation. Timely identification and resolution of these failure modes are essential to prevent costly downtime and ensure system reliability. Below are some common transformer failure modes, along with methods to identify and address them: Insulation FailureIdentification: Insulation failure leads to decreased insulation resistance, which can be detected through insulation resistance testing (megge
09/02/2025
Fault Analysis and Treatment of Oil-Immersed Transformers
Fault Analysis and Treatment of Oil-Immersed Transformers
Oil Leakage at Welded JointsOil leakage at welded joints primarily stems from poor welding quality, such as incomplete or detached welds, and defects like pinholes and gas pores. Although oil-immersed transformers are initially coated with solder and paint during manufacturing, potentially masking these issues temporarily, the defects tend to surface during operation. Additionally, electromagnetic vibration can cause weld cracks, leading to oil leakage.To resolve such leaks, the first critical s
08/29/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!