Construction of a Shunt Reactor

Electrical4u
Field: Basic Electrical
0
China

What Is The Construction Of A Shunt Reactor

Shunt Reactor is used to compensate capacitive reactive power of a long transmission line. The constructional features of a shunt reactor may vary manufacturer to manufacturer but basic of construction is more or less same.

Core of Shunt Reactor

Gapped Core is generally used in shunt reactor. The core is constructed from Cold Rolled Grain Oriented Silicon Steel sheet to reduce hysteresis losses. The sheets are laminated to reduce eddy current losses. Gaps are intentionally provided in the construction by placing spacers of high modulus of electricity between the packets of laminations. Normally the gaps are maintained radially. The laminations are placed in each packet in longitudinal direction. Normally, 5 limb 3 phase structure of core is used. It is shell type construction. The yokes and side limbs are not gapped but the three inner limbs for individual phase is constructed with radial gaps as shown.

Winding of Shunt Reactor

There is nothing special about winding of a reactor. This is mainly made of copper conductors. The conductors are paper insulated. Insulated spacers are provided between turns to maintain the path for oil circulation. This arrangement helps for efficient cooling of the winding.

Cooling System of Reactor

Normally a shunt reactor deals with low current that is why ONAN (Oil Natural Air Natural) cooling is sufficient for shunt reactor even for extra high voltage ratings. The radiator bank is connected with main tank to facilitate faster cooling.

Tank of Reactor

The main tank of larger rated reactor for UHV and EHV system is often of bell tank type. Here, both bottom tank and bell tank are manufactured by steel sheet of suitable thickness. The steel sheets of suitable pieces are welded together to form both of the tanks. The tanks are designed and constructed to withstand full vacuum and positive pressure of one atmosphere. The tanks should be so designed that these can be transported by road and railways.

Conservator of Reactor

Conservator is provided at the top of the tank with main tank to conservator connecting pipe line of suitable diameter. The conservator is generally horizontally aligned cylindrical tank, to provide adequate space to the oil for expansion due to temperature rise. Flexible separator between air and oil or air cell is provided in the conservator for the said purpose. The conservator tank is also equipped with a magnetic oil gauge to monitor the oil level in the reactor. The magnetic oil gauge also gives an alarm through a normally open (NO) DC contact, attached to it when oil level falls below a preset level due to oil leakage or any other reason.
shunt reactor

Pressure Relief Device

Due to huge fault inside the reactor there may be sudden and excessive expansion of oil inside the tank. This huge oil pressure generated in the reactor should be released immediately along with separation of the reactor from the live power system. Pressure Relief Device does the job. This is a spring loaded mechanical device. This is fitted on the roof of the main tank. At the event of actuation, the upward pressure of the oil in tank becomes greater than the downward spring pressure, as a result there will be an opening in the valve disc of the device through which the expanded oil comes out to relief the pressure formed inside the tank. There is a mechanical lever attached to the device which is normally in horizontal position. When the device is actuated, this lever becomes vertical. By observing the alignment of the lever even from ground level one can predict whether the Pressure Relief Device (PRD) has been operated or not. The PRD is accompanied with a trip contact to trip the shunt reactor at the event of actuation of the device.
N B: – PRD or such type of device cannot be reset from remote once it actuated. It can only be reset manually by moving the lever to its original horizontal position.

Buchholz Relay

One Buchholz relay is fitted across the pipe connecting the conservator tank and main tank. This device collects gases generated in the oil and actuates the alarm contact attached to it. It has also a trip contact which is actuated at the event of sudden accumulation of gas in the device or rapid flow of oil (oil surge) through the device.

Silica Gel Breather

When oil becomes hot, it is expanded thus air from conservator or air shell (where air shell is used) comes out. But during contraction oil, air from the atmosphere enters into conservator or air shell (where air shell is used). This process is called breathing of the oil immersed equipment (like transformer or reactor). During breathing, obviously moisture can enter into the equipment if it is not taken care of. An pipe from conservator tank or air shell is fitted with a container filled with silica gel crystal. When air is passed through it, the moisture is absorbed by the silica gel.

Winding Temperature Indicator

Winding temperature indicator is a kind of indicating meter associated with a relay. This consists of a sensor bulb placed in an oil filled pocket on the roof of reactor tank. There are two capillary tubes between sensor bulb and the instrument housing. One capillary tube is connected to the measuring bellow of the instrument. Other capillary tube connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows are filled with a liquid which changes its volume when temperature changes. The pocket in which the sensor bulb is immersed, is surrounded by a heating coil which is fed by a current proportional to the current flowing through the winding of reactor. Gravity operated NO contacts are attached to the pointer system of the instrument to provider high temperature alarm and trip respectively.

Oil Temperature Indicator

Oil temperature indicator consists of a sensor bulb placed in an oil filled pocket on the roof of reactor tank. There are two capillary tubes between sensor bulb and the instrument housing. One capillary tube is connected to the measuring bellow of the instrument. Other capillary tube connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows are filled with a liquid which changes its volume when temperature changes. The pocket in which the sensor bulb is immersed, is fitted at the location of hottest oil.

Bushing

The winding terminals of each phase comes out from the reactor boy through an insulated bushing arrangement. In high voltage shunt reactor, the bushings are oil filled. The oil is sealed inside the bushing that means there is no link between the oil inside the bushing and oil inside the main tank. Oil level gauge is provided on the expansion chamber of the condenser bushings.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.