Distance Relay or Impedance Relay Working Principle Types

The Electricity Forum
The Electricity Forum
Field: Publishes Electricity
0
Canada

What Is Distance Protection Relay

There is one type of relay which functions depending upon the distance of fault in the line. More specifically, the relay operates depending upon the impedance between the point of fault and the point where relay is installed. These relays are known as distance relay or impedance relay.

Working Principle of Distance or Impedance Relay

The working principle of distance relay or impedance relay is very simple. There is one voltage element from potential transformer and a current element fed from current transformer of the system. The deflecting torque is produced by secondary current of CT and restoring torque is produced by voltage of potential transformer.

In normal operating condition, restoring torque is more than deflecting torque. Hence relay will not operate. But in faulty condition, the current becomes quite large whereas voltage becomes less. Consequently, deflecting torque becomes more than restoring torque and dynamic parts of the relay starts moving which ultimately close the No contact of relay. Hence clearly operation or working principle of distance relay depends upon the ratio of system voltage and current. As the ratio of voltage to current is nothing but impedance so a distance relay is also known as impedance relay.
The operation of such relay depends upon the predetermined value of voltage to current ratio. This ratio is nothing but impedance. The relay will only operate when this voltage to current ratio becomes less than its predetermined value. Hence, it can be said that the relay will only operate when the impedance of the line becomes less than predetermined impedance (voltage/current). As the impedance of a
transmission line is directly proportional to its length, it can easily be concluded that a distance relay can only operate if fault is occurred within a predetermined distance or length of line.

Types of Distance or Impedance Relay

There are mainly two types of distance relay

  • Definite distance relay.

  • Time distance relay.

Let us discuss one by one.

Definite Distance Relay

This is simply a variety of balance beam relay. Here one beam is placed horizontally and supported by hinge on the middle. One end of the beam is pulled downward by the magnetic force of voltage coil, fed from potential transformer attached to the line. Other end of the beam is pulled downward by the magnetic force of current coil fed from current transformer connected in series with line. Due to torque produced by these two downward forces, the beam stays at an equilibrium position. The torque due to voltage coil, serves as restraining torque and torque due to current coil, serves as deflecting torque.

Under normal operating condition restraining torque is greater than deflecting torque. Hence contacts of this distance relay remain open. When any fault occurs in the feeder, under protected zone, voltage of feeder decreases and at the same time currentt increases. The ratio of voltage to current i.e. impedance falls below the pre-determined value. In this situation, current coil pulls the beam more strongly than voltage coil, hence beam tilts to close the relay contacts and consequently the circuit breaker associated with this impedance relay will trip.

Time Distance Impedance Relay

This delay automatically adjusts its operating time according to the distance of the relay from the fault point. The time distance impedance relay will not only be operated depending upon voltage to current ratio, its operating time also depends upon the value of this ratio. That means,

Construction of Time Distance Impedance Relay

time distance impedance relayThe relay mainly consists of a current driven element like double winding type induction over current relay. The spindle carrying the disc of this element is connected by means of a spiral spring coupling to a second spindle which carries the bridging piece of the relay contacts. The bridge is normally held in the open position by an armature held against the pole face of an electromagnet excited by the voltage of the circuit to be protected.

Operating Principle of Time Distance Impedance Relay

During normal operating condition the attraction force of armature fed from PT is more than force generated by induction element, hence relay contacts remain in open position when a short circuit fault occurs in the transmission line, the current in the induction element increases. Then the induction in the induction element increases. Then the induction element starts rotating. The speed of rotation of induction elements depends upon the level of fault i.e. quantity of current in the induction element. As the rotation of the disc proceeds, the spiral spring coupling is wound up till the tension of the spring is sufficient to pull the armature away from the pole face of the voltage excited magnet.

The angle through which the disc travels the disc travel before relay operate depends upon the pull of the voltage excited magnet. The greater the pull, the greater will be the travel of the disc. The pull of this magnet depends upon the line voltage. The greater the line voltage the greater the pull hence longer will be the travel of the disc i.e. operating time is proportional to V.
Again, speed of rotation of induction element approximately proportional to current in this element. Hence, time of operation is inversely proportional to current.
Therefore time of operation of relay,

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
H59/H61 Transformer Failure Analysis and Protection Measures
H59/H61 Transformer Failure Analysis and Protection Measures
1.Causes of Damage to Agricultural H59/H61 Oil-Immersed Distribution Transformers1.1 Insulation DamageRural power supply commonly uses a 380/220V mixed system. Due to the high proportion of single-phase loads, H59/H61 oil-immersed distribution transformers often operate under significant three-phase load imbalance. In many cases, the degree of three-phase load imbalance far exceeds the limits permitted by operational regulations, causing premature aging, deterioration, and eventual failure of th
Felix Spark
12/08/2025
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
Protection Logic Improvement and Engineering Application of Grounding Transformers in Rail Transit Power Supply Systems
Protection Logic Improvement and Engineering Application of Grounding Transformers in Rail Transit Power Supply Systems
1. System Configuration and Operating ConditionsThe main transformers at Zhengzhou Rail Transit’s Convention & Exhibition Center Main Substation and Municipal Stadium Main Substation adopt a star/delta winding connection with a non-grounded neutral point operation mode. On the 35 kV bus side, a Zigzag grounding transformer is used, connected to ground through a low-value resistor, and also supplies station service loads. When a single-phase ground short-circuit fault occurs on a line, a path
Echo
12/04/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.