• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Why does the open-circuit test gives core losses while short-circuit test gives copper losses?

Echo
Field: Transformer Analysis
China

Open circuit tests and short circuit tests are two fundamental methods used in transformer testing to separately determine core losses and copper losses.

Open Circuit Test (No-Load Test)

In an open circuit test, a rated voltage is typically applied to one winding while the other winding is left open. This setup is primarily used to measure core losses for the following reasons:

Core losses mainly consist of hysteresis losses and eddy current losses, which occur in the transformer's core. When an AC voltage is applied to the primary winding, it magnetizes the core, generating an alternating magnetic field. The hysteresis and eddy current losses produced during this process can be quantified by measuring the input power.

In the open circuit test, because the secondary winding is open, there is virtually no current flowing through the windings, so copper losses can be neglected. This means that the measured input power almost entirely reflects the core losses.

Short Circuit Test

In a short circuit test, a sufficiently low voltage is applied to one winding to avoid saturation, while the other winding is short-circuited. This test is primarily used to measure copper losses for the following reasons:

Copper losses are mainly due to I²R losses caused by the resistance of the windings. During the short circuit test, since the secondary winding is short-circuited, a significant current (close to the rated current) flows through the primary winding, resulting in substantial copper losses.

Because the applied voltage is low, the core does not reach saturation, so core losses are relatively small and can be neglected. Therefore, under these conditions, the measured input power primarily reflects the copper losses.

By using these two testing methods, core losses and copper losses can be effectively separated and evaluated independently. This is crucial for design optimization, fault diagnosis, and ensuring efficient transformer operation.

Give a tip and encourage the author!
Recommended
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding Electrodes
Impact of DC Bias in Transformers at Renewable Energy Stations Near UHVDC Grounding ElectrodesWhen the grounding electrode of an Ultra-High-Voltage Direct Current (UHVDC) transmission system is located close to a renewable energy power station, the return current flowing through the earth can cause a rise in ground potential around the electrode area. This ground potential rise leads to a shift in the neutral-point potential of nearby power transformers, inducing DC bias (or DC offset) in their
01/15/2026
Distribution Equipment Transformer Testing, Inspection, and Maintenance
1.Transformer Maintenance and Inspection Open the low-voltage (LV) circuit breaker of the transformer under maintenance, remove the control power fuse, and hang a “Do Not Close” warning sign on the switch handle. Open the high-voltage (HV) circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the HV switchgear, and hang a “Do Not Close” warning sign on the switch handle. For dry-type transformer maintenance: first clean the porcel
12/25/2025
Design Principles for Pole-Mounted Distribution Transformers
Design Principles for Pole-Mounted Distribution Transformers(1) Location and Layout PrinciplesPole-mounted transformer platforms should be located near the load center or close to critical loads, following the principle of “small capacity, multiple locations” to facilitate equipment replacement and maintenance. For residential power supply, three-phase transformers may be installed nearby based on current demand and future growth projections.(2) Capacity Selection for Three-Phase Pole-Mounted Tr
12/25/2025
Transformer Noise Control Solutions for Different Installations
1.Noise Mitigation for Ground-Level Independent Transformer RoomsMitigation Strategy:First, conduct a power-off inspection and maintenance of the transformer, including replacing aged insulating oil, checking and tightening all fasteners, and cleaning dust from the unit.Second, reinforce the transformer foundation or install vibration isolation devices—such as rubber pads or spring isolators—selected based on the severity of vibration.Finally, strengthen sound insulation at weak points of the ro
12/25/2025
Related Products
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.