How does decreasing the excitation of a synchronous motor affect its current draw?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Effects of Reducing Excitation on Current Consumption in Synchronous Motors

Reducing the excitation of a synchronous motor has significant effects on its current consumption, primarily impacting several key aspects:

1. Changes in Armature Current

The armature current (i.e., stator current) of a synchronous motor consists of two components: active current and reactive current. Together, these determine the total armature current.

  • Active Current: Related to the mechanical power output of the motor, typically determined by the load.

  • Reactive Current: Used to establish the magnetic field, closely related to the excitation current.

When the excitation current is reduced, the strength of the motor's magnetic field weakens, leading to the following changes:

Increase in Reactive Current: To maintain the same power factor, the motor needs to draw more reactive current from the grid to compensate for the weaker magnetic field. This results in an increase in the total armature current.

Current Imbalance: If the excitation is too low, the motor may enter an underexcited state where it not only draws active power but also requires a large amount of reactive power from the grid. This can lead to current imbalance, voltage fluctuations, or instability.

2. Changes in Power Factor

The power factor of a synchronous motor is a crucial indicator of its efficiency. The power factor can be categorized into two states:

Leading Power Factor (Overexcited State): When the excitation current is high, the motor generates excess magnetic flux, causing it to supply reactive power back to the grid, resulting in a leading power factor.

Lagging Power Factor (Underexcited State): When the excitation current is reduced, the motor cannot generate sufficient magnetic flux and must draw reactive power from the grid, resulting in a lagging power factor.

Therefore, reducing the excitation current worsens the motor's power factor (making it more lagging), leading to higher reactive current demand and increased total current consumption.

3. Changes in Electromagnetic Torque

The electromagnetic torque of a synchronous motor is related to both the excitation current and the armature current. Specifically, electromagnetic torque 

T can be expressed as:

d8be36fc6488bab29f30f2a76f401b2f.jpeg

where:

T is the electromagnetic torque,k is a constant,ϕ is the magnetic flux in the air gap (proportional to the excitation current),Ia is the armature current.

When the excitation current is reduced, the air gap magnetic flux ϕ decreases, leading to a reduction in electromagnetic torque. To maintain the same load torque, the motor must increase the armature current to compensate for this loss. Therefore, reducing the excitation current leads to an increase in the armature current, thereby increasing the overall current consumption.

4. Stability Issues

If the excitation current is reduced too much, the motor may enter an underexcited state, potentially leading to a loss of synchronism. In this condition, the motor cannot maintain synchronization with the grid, which can cause severe electrical and mechanical failures. Additionally, the stability and dynamic response of the motor will deteriorate in an underexcited state.

5. Impact on Voltage Regulation

Synchronous motors can regulate grid voltage by adjusting the excitation current. If the excitation current is reduced, the motor's ability to support grid voltage also diminishes, potentially leading to a drop in grid voltage, especially under heavy load conditions.

Summary

Reducing the excitation current of a synchronous motor affects its current consumption in the following primary ways:

  • Increase in Armature Current: Due to the need to draw more reactive current from the grid to compensate for the weakened magnetic field, the total armature current increases.

  • Deterioration in Power Factor: Reducing the excitation current worsens the power factor (making it more lagging), further increasing the demand for reactive current.

  • Reduction in Electromagnetic Torque: To maintain the same load torque, the motor must increase the armature current, leading to increased current consumption.

  • Decrease in Stability and Voltage Regulation Capability: Insufficient excitation can lead to loss of synchronism or voltage instability.

Therefore, in practical applications, it is important to adjust the excitation current appropriately based on load requirements to ensure efficient and stable motor operation. 

Give a tip and encourage the author!
Recommended
How to Choose a Thermal Relay for Motor Protection?
How to Choose a Thermal Relay for Motor Protection?
Thermal Relays for Motor Overload Protection: Principles, Selection, and ApplicationIn motor control systems, fuses are primarily used for short-circuit protection. However, they cannot protect against overheating caused by prolonged overloading, frequent forward-reverse operation, or undervoltage operation. Currently, thermal relays are widely used for motor overload protection. A thermal relay is a protective device that operates based on the thermal effect of electric current, and is essentia
James
10/22/2025
How to Choose & Maintain Electric Motors: 6 Key Steps
How to Choose & Maintain Electric Motors: 6 Key Steps
"Selecting a High-Quality Motor" – Remember the Six Key Steps Inspect (Look): Check the motor’s appearanceThe motor’s surface should have a smooth, even paint finish. The nameplate must be properly installed with complete and clear markings, including: model number, serial number, rated power, rated current, rated voltage, allowable temperature rise, connection method, speed, noise level, frequency, protection rating, weight, standard code, duty type, insulation class, manufacturing date, and ma
Felix Spark
10/21/2025
 What Is the Working Principle of a Power Plant Boiler?
What Is the Working Principle of a Power Plant Boiler?
The working principle of a power plant boiler is to utilize the thermal energy released from fuel combustion to heat feedwater, producing a sufficient quantity of superheated steam that meets specified parameters and quality requirements. The amount of steam produced is known as the boiler's evaporation capacity, typically measured in tons per hour (t/h). Steam parameters primarily refer to pressure and temperature, expressed in megapascals (MPa) and degrees Celsius (°C), respectively. Steam qua
Edwiin
10/10/2025
What is the principle of live-line washing for substations?
What is the principle of live-line washing for substations?
Why Do Electrical Equipment Need a "Bath"?Due to atmospheric pollution, contaminants accumulate on insulating porcelain insulators and posts. During rain, this can lead to pollution flashover, which in severe cases may cause insulation breakdown, resulting in short circuits or grounding faults. Therefore, the insulating parts of substation equipment must be periodically washed with water to prevent flashover and avoid insulation degradation that could lead to equipment failure.Which Equipment Is
Encyclopedia
10/10/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.